Sensing · Ultrasonic
Ultrasonic Sensing in Data Centers: Hearing Faults Before They Fail
Ultrasonic inspection listens for sound above human hearing, roughly 20 to 100 kilohertz, that equipment gives off when something is starting to go wrong. Arcing, tracking and corona in electrical gear, friction in a dry bearing and gas escaping through a pinhole all make ultrasound long before they make heat, smoke or a noise anyone can hear.
Because ultrasound travels in short, directional waves, it points straight back to its source, and it escapes closed cabinets through vents and door seams. That makes it one of the few ways to learn what is happening inside energized equipment without opening the door.
This guide covers the science, the sensor family, every major use case in data centers and industrial facilities, and how a FacilityOps robot, its sensor hub and inspection drones carry an ultrasonic ear to the same spot on every pass.
Key takeaways
- Airborne ultrasound sits roughly between 20 and 100 kHz. Instruments shift it down into the audible range and measure it in decibels, so a technician can hear and trend it.
- Arcing, tracking and corona all produce ultrasound. Corona only occurs at 1,000 volts and above, and listening first lets a team assess energized gear before anyone opens it.
- Bearings get louder as lubrication fails. ISO 29821 gives example alarms of 8 dB over baseline for lubrication, 16 dB for audible failure and 35 dB for catastrophic failure.
- Any pressurized gas leak makes ultrasound, whatever the gas: compressed air, refrigerant, nitrogen or insulating gas. The US Department of Energy says leaks can waste 20 to 30 percent of a compressor's output.
- Ultrasound readings are relative, so the change at the same spot over time is what matters. That is exactly what a robot listening from the same position on every pass delivers.
- A FacilityOps robot captures ultrasound with thermal, visual and gas readings at every checkpoint, stationary sensor hubs listen continuously at the riskiest spots, and inspection drones extend the reach upward.
In this guide
What is ultrasonic sensing?
Sound is a pressure wave moving through air or a solid. People hear roughly 20 Hz to 20 kHz, and most adults top out well below that, so anything higher is ultrasound.
Maintenance instruments typically listen between about 20 and 100 kHz. Their electronics shift that band down into the audible range, a process called heterodyning, so the technician hears a crackle, buzz or hiss in a headset while the display shows the level in decibels.
The wavelengths are tiny, roughly 0.3 to 1.6 centimeters, compared with up to 17 meters for audible sound. Short waves travel in straight, narrow paths and fade quickly with distance, which is why ultrasound is directional and local: turn the sensor away and the signal drops, move closer and it climbs.
Airborne and structure borne
Airborne sensing listens to sound that has escaped into the air, usually around 40 kHz. It is how you scan a cabinet seam, a pipe flange or a pump from a distance.
Structure borne, or contact, sensing touches the equipment and listens to sound traveling through metal, usually around 25 kHz. It is how you hear a bearing inside its housing, a valve passing flow inside its body, or arcing inside a cabinet with no air path out.
Hearing versus seeing sound
A single sensor tells you how loud a spot is. An acoustic imaging camera uses an array of many tiny microphones to work out where sound is coming from, and paints it as a colored map over a live video image, so a leak or a discharge shows up as a glowing spot on the picture.
Why does ultrasound find problems so early?
Most failures start as tiny releases of energy. Ionized air at a stressed insulator, metal rubbing metal through a thinning film of grease, and gas forced through a crack all release energy at very small scales, and a good part of it comes out as high frequency sound.
Heat and audible noise come later, once the damage is bigger. That puts ultrasound near the front of the warning curve, alongside vibration and ahead of the hot spot a thermal camera will eventually see.
It also fills two blind spots of infrared. Corona produces little to no heat, so a thermal camera can miss it entirely, and infrared usually cannot see inside a closed cabinet without a viewing port, while ultrasound escapes through the gaps.
The reverse is true too. A corroded connection can run hot through plain resistance without ionizing the air, so a thermal camera sees it and ultrasound does not. The two methods work best together, which is why one sensor is never enough.
Which standards and studies back ultrasonic inspection?
ISO 29821 now has a second edition, published in April 2026, which adds microelectromechanical (MEMS) sensors (ISO). ISO 18436 Part 8 certifies the people who do the work, in three categories tied to training, experience and an exam (ISO).
ASTM E1002 sets two ways to find leaks. One listens for the ultrasound of escaping gas. The other places a tone generator inside an unpressurized space and listens for where the tone gets out (ASTM International).
The method works where nothing else fits. In 2020, a cosmonaut used an ultrasonic leak detector to trace a slow air leak on the International Space Station. Crews narrowed it to the Zvezda module's transfer chamber (NASA, 2020).
Software is catching up with trained ears. A 2024 study trained neural networks on noisy ultrasound from real field failures. They sorted arcing, corona, tracking, looseness and healthy gear with over 94 percent accuracy (IEEE Access, 2024).
What is in the ultrasonic sensor family?
Ultrasonic sensing is a family of tools, not one device. Each member hears something the others miss.
- Heterodyne receivers: the classic handheld scanner. Sees: arcing, tracking, corona, leaks and bearing friction as a level and a sound. Misses: where exactly the sound comes from in a crowded space, unless the user hunts for it.
- Contact probes: a metal rod or magnetic sensor touching the equipment. Sees: bearings, gearboxes, valves, steam traps and internal arcing. Misses: anything it is not touching, and readings shift if the contact point changes.
- Parabolic and focusing attachments: a dish or rubber cone that gathers sound from one direction. Sees: overhead lines, high bus and distant leaks, at more than double the normal range. Misses: anything outside its narrow cone.
- Acoustic imaging cameras: arrays of dozens to hundreds of microphones with a video camera. Sees: the location of leaks and discharges, painted onto the image, often at a distance. Misses: very faint sources hidden behind louder ones, and anything with no air path to the camera.
- Fixed online monitors: sensors mounted inside or on a cabinet, wired to an alarm. Sees: discharge the moment it starts, between inspections. Misses: everything outside its one cabinet.
- Robot and drone payloads: any of the above carried to the equipment by a machine. Sees: the same checkpoints from the same position every pass, across a whole facility. Misses: what the route does not reach, and anything masked by louder ultrasound nearby.
How does ultrasound find electrical faults?
Electrical discharge ionizes air, and ionization makes ultrasound. The three conditions inspectors listen for each have their own voice.
- Arcing: current jumping a gap, at any voltage. It sounds like erratic bursts and pops that start and stop suddenly, and it does the most damage.
- Tracking: a low current path creeping across the surface of an insulator, sometimes called baby arcing. It sounds like a steady buzz with periodic crackles and pops, and it can quickly progress to arcing.
- Corona: ionization of the air around a highly stressed conductor. It sounds like a steady frying buzz, and it only occurs at 1,000 volts and above, so a buzz on lower voltage gear points to looseness or tracking instead.
Recordings can be analyzed too. Corona shows strong harmonics of the 60 Hz line frequency that weaken as it worsens, arcing shows sharp bursts in the time waveform, and mechanical looseness shows 60 Hz harmonics mixed with other frequencies.
Low voltage and medium voltage
On low voltage gear such as 480 volt switchboards, panels, PDUs and busway, the main concern is arcing: at breaker contacts, loose lugs, relays and joints. On medium voltage switchgear, transformers and cable terminations, all of the conditions are possible, including partial discharge inside insulation, which slowly erodes it until it fails.
NFPA 70B now treats electrical maintenance as a requirement rather than a recommendation, and it names airborne ultrasound among the online tests, alongside infrared and partial discharge testing.
Listen before you open
The most important electrical use is also the simplest. Scanning the door seams and vents of energized gear before anyone opens it tells the team whether discharge is already happening inside, so they can step back, plan and protect themselves before facing an arc flash risk.
A real example shows the cost of not listening. An ultrasound survey found arcing on the line side of one phase of a 2,000 amp main breaker, getting worse as load rose, and it had already severely damaged the internal contacts of a part costing about $20,000 to replace.
How does ultrasound find mechanical wear?
Rotating equipment makes friction, and friction makes ultrasound. When grease thins, contaminates or runs out, the rolling elements start to rub, and the ultrasonic level rises above that bearing's own baseline before vibration or temperature change much.
ISO 29821, the international standard for ultrasound condition monitoring, gives example alarm levels: about 8 dB above baseline means the bearing needs lubrication, 16 dB means the failure stage can be heard, and 35 dB or more warns of catastrophic failure.
Lubrication by ear
Over greasing kills bearings almost as surely as under greasing, because packed grease raises friction and heat. Listening while greasing lets a technician add small amounts only until the reading falls back to baseline, then stop.
Pumps, fans, compressors and valves
Ultrasound hears cavitation in pumps as random crackling, broken gear teeth in gearboxes, leaking valves in reciprocating compressors, and valves passing flow when they should be shut, because a properly seated valve is quiet while a leaking one is turbulent.
One site found the scale of it on its transformer oil pumps. Healthy pumps read 20 to 30 dB, yet 12 of the 14 pumps on one transformer read 50 to 70 dB, a jump of 30 to 35 dB, years before their expected end of life.
How does ultrasound find leaks?
When pressurized gas squeezes through a small opening, the flow turns turbulent and throws off ultrasound. Small leaks put most of their energy above human hearing, so they hiss loudly to an ultrasonic sensor while staying silent to people standing next to them.
The sound comes from the turbulence, not the chemistry, so it works for any gas: compressed air, nitrogen, refrigerant, steam, natural gas or insulating gas in switchgear. Vacuum leaks work the same way in reverse, as air rushes in.
What leaks cost
The US Department of Energy says compressed air leaks often waste 20 to 30 percent of a compressor's output. In one plant example, fixing 160 leaks saved about $57,000 a year, and the 10 largest leaks alone accounted for almost 70 percent of it.
Leaks can often be heard 30 to 40 feet away with a handheld detector, and the signal grows as you close in, which makes hunting them quick.
Refrigerant leaks now carry rules
From January 1, 2026, the US Environmental Protection Agency requires owners of appliances holding 15 pounds or more of HFC refrigerant to repair leaks once leak rates pass set thresholds: 10 percent a year for comfort cooling, 20 percent for commercial refrigeration and 30 percent for industrial process refrigeration. Leaks must be found and repaired within 30 days of adding refrigerant, with periodic leak inspections until the appliance stays below its threshold.
Chillers and large computer room air conditioners easily cross 15 pounds. An ultrasonic sweep of every fitting, valve and flare on a regular route turns that rule from a scramble into a routine.
Sealed systems and tone tests
Some systems cannot be pressurized. In those, a small ultrasonic transmitter is placed inside, and the outside is scanned for sound leaking through gaps, gaskets, seals and failed tubes, which is how heat exchanger tube leaks and door seals are found.
Where does ultrasound earn its place in a data center?
A data center packs nearly every ultrasonic use case into one building, and most of the equipment runs around the clock with no chance to stop and look inside.
- Medium voltage switchgear and transformers: partial discharge, corona on terminations and bushings, and bearing wear in transformer cooling fans and oil pumps.
- Low voltage switchgear, UPS systems, PDUs, RPPs and busway: arcing at breaker contacts, loose lugs and busway joints, heard through door seams and vents.
- Generator plant: bearing wear in engine fans and alternators, leaks in compressed air starting systems and fuel lines, and exhaust leaks at joints.
- Cooling plant: refrigerant leaks at chiller fittings, compressor valve problems, pump cavitation, and bearing wear in CRAH fans, pumps and cooling tower gearboxes.
- Liquid cooled halls: cavitation in coolant distribution unit pumps and pressurized coolant weeping at fittings and quick disconnects.
- Fire protection: leaks in the supervisory air or nitrogen that holds dry and preaction sprinkler piping, which make the compressor run more and can lead to nuisance trips.
- Gas insulated switchgear: insulating gas leaks at seals and fittings, heard as a hiss whatever the gas.
There is one data center catch. Fast switching electronics in UPS systems and drives, compressed air tools and fast moving air from fans also produce ultrasound, so the same reading can be normal in one room and alarming in another. The answer is a baseline for every individual checkpoint, built from the same position over time.
What about industrial facilities beyond the data center?
Ultrasound began in heavy industry, and every lesson there applies to critical facilities.
- Refineries and chemical plants: steam traps, valves, flanges and compressors. A single failed steam trap can waste an average of 43 tons of steam a year, and one chemical company reported $1 million in savings from a single plant's trap survey.
- Power utilities and substations: corona and tracking on insulators, bushings and switchgear, often scanned from a distance with dishes or imaging cameras.
- Manufacturing: compressed air leak programs, often the single fastest energy payback in a plant, plus bearing and gearbox routes.
- Water and wastewater: pump cavitation, valve condition and blower bearings.
- Hospitals, labs and semiconductor fabs: medical gas, vacuum and specialty gas leaks, where any leak is a safety issue as well as a cost.
Oil and gas operators already send legged inspection robots on routes with 360 degree acoustic imagers to pinpoint pressurized gas leaks. The idea is proven: the next step is a robot that listens with the same discipline across every system in a critical facility.
Why does consistency matter so much?
Ultrasound readings are relative. Distance, angle, sensitivity setting and where the probe touches all change the number, so two people scanning the same breaker can get different readings without anything having changed.
That is why ISO 29821 and every serious program build around a baseline for each point and alarm on the rise above it. The method only works if each reading is taken the same way as the last.
People rarely do that perfectly. They stand a little closer, angle the sensor differently or change the gain, and a route walked once a quarter leaves months of silence in between. A robot removes both problems at once.
How does a FacilityOps robot listen?
A FacilityOps robot carries ultrasonic sensing in the FacilityOps sensor hub, alongside fisheye, zoom, close up and thermal cameras, a 3D lidar, gas and smoke sensing and more. It walks its listening route on its own, and a technician can take the controls at any point to aim it at a sound someone reported. At each checkpoint it confirms the asset, settles into its stored pose and listens.
Because the pose is stored and checked, the sensor sits at the same distance and angle, with the same settings, every pass. A rise of a few decibels at a door seam then means something changed inside, not that the listener moved.
Every reading is captured at the same moment as the thermal, visual and air readings of that spot. A buzz at a seam with no heat, a crackle next to a warm lug and a hiss beside a rising gas reading each tell a different story, and the record keeps them together.
Technicians can also ask for more. Through the robot's voice agent they can say "listen to cubicle 3 every pass this week" or "check the bearing on pump 2 after I grease it", and the robot adds the checkpoint and reports back.
Which spots need a listening hub or a drone?
Inspection drones
Some of the loudest problems sit where a ground robot cannot reach: rooftop chillers, cooling tower fans and gearboxes, outdoor substation insulators and high pipe racks. FacilityOps inspection drones, in development, carry the same sensor hub to those places.
Drones bring their own challenge, because rotor wash is fast moving air, and fast moving air is itself a source of ultrasound. Drone listening therefore favors hovering at a set standoff, directional sensing aimed away from the rotors, and a baseline for each hover point, so the drone's own noise is part of what is expected.
Stationary sensor hubs
The FacilityOps sensor hub also works fixed in place, listening continuously at the riskiest spots, such as a medium voltage lineup with a history of discharge or a cabinet flagged on a previous pass. A hub catches discharge that starts between rounds and sends the robot to look.
After a repair, a hub can keep listening for a set period to prove the fix held, so the record shows the problem stayed gone, not just that it was quiet on one night.
Coming next: a FacilityOps robot that sets a contact ultrasonic probe on the grease fitting of a bearing it has flagged, so a technician can grease it while the robot listens and says stop the moment the level falls back to baseline.
What does one night of ultrasonic listening look like?
On this illustrative night, a FacilityOps robot aims its ultrasonic sensor at the same door seams, bearings, joints and fittings as every pass and compares each decibel reading with that spot's own baseline. Ultrasound is directional and short range, so a rise at one seam belongs to that seam. Seven moments stood out.
1:40 a.m. · The buzz with no heat
At the medium voltage lineup, the robot hears a steady frying buzz at the door seam of cubicle 3, 9 dB above that seam's baseline, with strong 60 Hz harmonics. The thermal camera shows nothing unusual, which fits corona: it makes sound, not heat.
The robot opens nothing. It files the reading with the recording and images, flags the cubicle so nobody opens it unassessed, and routes it to the electrical engineer for a partial discharge test.
2:20 a.m. · The crackle at the UPS breaker
In UPS room 1, the robot hears erratic bursts and pops at the vents of an input breaker, the voice of arcing. The thermal camera shows the breaker's surface a few degrees warmer than last week.
Sound plus heat at the same spot is the strongest signal on the route. The robot alerts the on call electrician within the minute, opens an urgent work order and adds a listening checkpoint to every pass until it is closed.
2:55 a.m. · The busway joint
Under the busway in data hall 2, the robot aims its ultrasonic sensor up at joint 14 and hears a buzz with crackles that the neighboring joints do not make. Its zoom camera reads the joint's inspection label: last torque check, two years ago.
It routes the finding to the electrical team with the recording, the image and the label, so they can plan a torque check during the next maintenance window instead of finding out the hard way.
3:30 a.m. · The pump that needs grease
In the cooling plant, the bearing on chilled water pump 2 reads 9 dB above its baseline, past the 8 dB point that means lubrication is due. Its temperature is normal and the vibration hub on the pump has only just begun to trend upward.
A technician greases it the next morning, listening until the level falls back, and asks the robot to check it. The next pass reads within 1 dB of baseline.
4:05 a.m. · The hiss at the chiller
At chiller 2, the robot hears a steady hiss at a flare fitting on the refrigerant line, and the refrigerant sensor at that checkpoint reads above its baseline. The close up camera shows a light film of oil around the fitting.
It routes the finding to the mechanical contractor with all three pieces of evidence, which also starts the clock and the paper trail the refrigerant leak repair rules expect.
4:30 a.m. · The coolant pump that crackles
In the liquid cooled hall, the robot hears random crackling at a coolant distribution unit pump that was quiet last week, and its camera reads the pump's inlet pressure gauge lower than usual. Low inlet pressure and crackling together point to cavitation, which erodes impellers.
The finding goes to the cooling team before cavitation eats the impeller and before cooling capacity drops under a live AI load.
4:50 a.m. · The leak in the sprinkler air
At the preaction riser, the robot hears a hiss at a union on the supervisory air line, and its camera reads the air compressor's run counter higher than last week. A leak there makes the compressor work harder and can eventually trip a trouble alarm.
The robot routes it to the fire protection contractor with the recording and photo. Before the day shift arrives, each finding carries its decibel rise over baseline and a clip a technician can play back before opening anything.
What does a FacilityOps ultrasonic record show?
Each ultrasonic reading carries its decibel level against that spot's baseline, the sound itself shifted down into the range people can hear, the sensor's aim, the run and the time, plus the thermal and visual images from the same moment. Readings are compared with that checkpoint's own history, so a change stands out against what is normal for that exact spot.
An illustrative record entry
MV switchgear, cubicle 3, door seam checkpoint · Run 52 · Captured from the same pose as run 51
Change found: airborne ultrasound 9 dB above this checkpoint's baseline, steady buzz with strong 60 Hz harmonics; thermal at the same seam unchanged; door closed, no visible damage. Recording and images attached.
Routed to: electrical engineer for partial discharge testing; cubicle flagged "assess before opening"; stationary hub assigned to listen continuously. Closed: after repair, run 58 and two weeks of hub data back at baseline.
A spot that climbs above its own baseline opens an exception and a work order, and a reading back at baseline after the repair confirms the fix.
Worked example: what a decibel rise over baseline means for a bearing
Ultrasound programs judge a bearing by how far it has climbed above its own baseline, not by an absolute number. UE Systems' guidance puts about 8 dB over baseline at lubrication due, about 12 dB at the start of failure, about 16 dB at advanced failure and 35 to 50 dB at catastrophic failure. Chilled water pump 2 above, at 9 dB, sits just past the first line: grease now, not a new bearing.
Electrical faults need the same discipline in reverse. Corona makes sound but little heat, and a Level III thermographer's switchgear case studies show it can earn only a minor severity rating when judged on temperature rise alone. A FacilityOps robot records both at the same seam on every pass, so a loud, cool cubicle is never mistaken for a healthy one.
A handheld survey tells you how loud a cabinet was on one afternoon. A robot that listens from the same spot every night tells you when it started getting louder.
What does FacilityOps ultrasonic sensing add?
- Consistency: same position, angle and settings every pass, so the dB trend is real.
- Frequency: every night instead of once or twice a year, so discharge and wear are caught early in their curve.
- Context: ultrasound captured with thermal, visual, gauge and gas readings of the same spot, so each finding arrives with its explanation.
- Coverage: every checkpoint on the route, including the rooms nobody walks at night, with missed checkpoints recorded honestly.
- Follow through: exceptions, work orders and a confirmed fix on the next pass, with hubs watching the riskiest spots in between.
- One route, many records: the same pass feeds electrical maintenance records for NFPA 70B, cooling records for ASHRAE 180 and refrigerant leak records, alongside everything else on the nine compliance surfaces.
What are the limits of ultrasonic sensing?
Here are the limits, stated once. Airborne ultrasound needs an air path out of the equipment, so discharge buried deep in solid insulation may stay silent; a reading shows that something changed, not exactly what or where inside; and loud ultrasound from drives, UPS switching or compressed air can mask quieter sources.
It does not replace partial discharge measurement, electrical testing on de energized equipment, or the judgment of qualified people. A FacilityOps robot listens and reports without opening, touching or operating equipment, and people decide what happens next.
Has it worked in a live data center?
Yes. Since July 28, 2026, a FacilityOps robot has listened to switchgear, bearings and cooling units on its rounds at the CRSC Data Center, powered by Solutions IS, in Houston.
Sound already mattered there. Intermittent temperature spikes of up to 15.5°F on the second cooling unit, seen from several angles, matched belt noise reported on site, and the unit was flagged for inspection while it was carrying the facility's cooling load.
What the evidence says
- SKF, a bearing maker, attributes roughly 36 percent of premature bearing failures to incorrect or insufficient lubrication, ahead of fatigue, poor fitting and contamination (vendor data). That is the failure an 8 dB rise catches.
- The U.S. Department of Energy calls an ultrasonic acoustic detector the best way to find compressed air leaks, which cluster at couplings, hoses, fittings, quick disconnects, valves and flanges, in its compressed air tip sheet.
- The same tip sheet works an example: ten 1/4 inch (6.4 mm) leaks at 100 psig (690 kPa) cost about $40,000 a year at $0.05 per kWh.
- Corona judged by heat alone can be rated minor while it is serious, James Brady's case studies show, which is why listening and thermal belong on the same pass.
What should you ask any ultrasonic inspection program?
- 1. Is every reading taken from the same position, angle and settings, and how do you prove it?
- 2. Does each checkpoint have its own baseline, and what rise above it triggers action?
- 3. Are electrical enclosures scanned before they are opened, every time?
- 4. Is ultrasound captured together with thermal and visual readings of the same spot?
- 5. How often is each checkpoint heard: once a year, once a quarter, or every night?
- 6. Which rooms and assets are never scanned, and why?
- 7. When a reading rises, who is told, how fast, and how is the fix confirmed?
- 8. Can the program produce refrigerant leak and electrical maintenance records without extra paperwork?
Five questions to ask about your facility
- 1. When was the last time anyone listened to your medium voltage switchgear while it was energized?
- 2. Do your technicians scan cabinets before opening them, or only after?
- 3. How many of your pump and fan bearings are greased on a calendar rather than by condition?
- 4. How much refrigerant did you add last year, and do you know exactly where it went?
- 5. How long would a small air or nitrogen leak in your sprinkler piping go unnoticed?
Frequently asked questions
What is ultrasonic inspection?
Ultrasonic inspection listens for high frequency sound, roughly 20 to 100 kHz, that equipment makes when electrical discharge, friction or leaking gas begins. Instruments shift it into the audible range and measure it in decibels, so changes can be heard and trended long before heat or visible damage appear.
What can an ultrasonic sensor detect in a data center?
It detects arcing, tracking and corona in switchgear, UPS systems, PDUs and busway; bearing wear and cavitation in pumps and fans; and pressurized leaks of refrigerant, compressed air, nitrogen and insulating gas. Most of it can be heard through vents and seams without opening equipment.
Can ultrasound detect problems inside closed electrical cabinets?
Yes, when there is an air path out. Ultrasound escapes through vents, louvers and door seams, so scanning them reveals arcing, tracking and corona inside. Where there is no air path, a contact sensor on the enclosure can pick up sound traveling through the metal.
What is the difference between ultrasound and infrared inspection?
Infrared sees heat, and ultrasound hears discharge, friction and turbulence. Corona makes little heat, so infrared can miss it, while a corroded connection can run hot without making ultrasound. Used together, they catch far more than either alone.
Does corona occur on 480 volt equipment?
No. Corona only occurs at 1,000 volts and above. On 480 volt switchboards and panels, a buzz usually points to arcing, tracking or loose components instead.
How does ultrasound show that a bearing needs grease?
Bearing friction rises as lubrication fails. ISO 29821 gives example alarms of about 8 dB above a bearing's baseline for lubrication, 16 dB for audible failure and 35 dB for catastrophic failure. Technicians can grease while listening and stop when the level returns to baseline.
Can ultrasound find refrigerant leaks?
Yes. Any pressurized gas escaping through a small opening makes ultrasound, regardless of the gas, so ultrasound finds refrigerant leaks at fittings, valves and flares. It helps owners meet US EPA leak repair rules that apply from 2026 to appliances with 15 pounds or more of HFC refrigerant.
Why do ultrasonic readings need to be taken from the same position?
Ultrasound readings are relative. Distance, angle, settings and contact point all change the decibel level, so only readings taken the same way can be compared. A robot that holds a stored pose at every checkpoint makes the trend trustworthy.
Can a robot do ultrasonic inspection?
Yes. A FacilityOps robot carries ultrasonic sensing in its sensor hub and listens at every checkpoint on its route, from the same position each pass, together with thermal, visual and gas readings. Changes become exceptions and work orders, and the next pass confirms the fix.
Can drones carry ultrasonic sensors?
Yes, for high and outdoor equipment such as rooftop chillers, cooling towers and substation insulators. Rotor wash adds its own ultrasound, so drone listening relies on fixed hover points, directional sensing and per point baselines. FacilityOps inspection drones are in development.
Does ultrasonic sensing replace electrical testing?
No. It screens energized equipment and shows that something has changed, which tells qualified people where to look. Partial discharge measurement, testing on de energized equipment and the judgment of qualified people are still required.
What does a FacilityOps sensor hub do with ultrasound?
The FacilityOps sensor hub rides on the robot or sits fixed at high risk spots. Fixed hubs listen continuously, catch discharge that starts between rounds, send the robot to look, and keep listening after a repair to prove the fix held.
What is the most common cause of bearing failure?
Lubrication problems top most lists. SKF, a bearing maker, attributes roughly 36 percent of premature bearing failures to incorrect or insufficient lubrication, ahead of fatigue, poor fitting and contamination. Friction from thin grease raises the ultrasonic reading early, and repeat readings from the same spot, as a FacilityOps robot takes, make that rise visible.
How much does a compressed air leak cost?
More than most people expect. In a U.S. Department of Energy example, ten 1/4 inch (6.4 mm) leaks at 100 psig (690 kPa) cost about $40,000 a year at $0.05 per kWh, and the department names an ultrasonic detector as the best way to find them.
What does corona sound like on an ultrasonic detector?
Corona usually sounds like a steady buzzing or frying noise. Tracking sounds similar but with pauses and changes in intensity, while arcing comes in sharp bursts and pops. Because ultrasound is very directional, an inspector, or a FacilityOps robot listening from a fixed pose, can follow the loudest signal back toward its source.
If you want to see an ultrasonic reading recorded together with thermal and visual evidence, we can send you a sample inspection record.
Or choose the switchgear, bearings and pressurized lines you most need to hear and have a FacilityOps robot listen to them every night through a scoped pilot, with the checkpoints and the success measures agreed in writing first.
Every ultrasonic reading on that route also feeds the electrical, cooling and refrigerant leak records across all nine compliance surfaces.
Everything in this piece, as a checklist you can take on your rounds
Turn the key points from this article into a practical inspection checklist.