Sensing · Smoke Detection

Smoke Sensing for Data Centers, and How Robots and Drones Find the Source

Updated · FacilityOps researchers and writers

Smoke sensing is the measurement of combustion particles in the air, usually by how strongly they scatter or block a beam of light. In a data center it is the earliest physical sign that something is overheating, and the fastest way to lose that sign is to let the cooling system carry it away.

A data hall moves enormous volumes of air, so the first wisp from a failing power supply or a cooking cable is diluted long before it reaches a ceiling detector. The building's listed fire detection is built to raise the alarm and protect lives. Finding the exact rack, cabinet or battery string where the smoke started is a different job.

That job is where a smoke sensor that moves earns its place. Carried by a robot on the floor, by a drone up high, or fixed beside a cabinet that needs watching, it can sample the air where the smoke is born and keep a dated record of every reading.

Key takeaways

  • Smoke sensing measures combustion particles in the air. Detectors are rated in percent obscuration per foot, the share of light that one foot of smoky air blocks.
  • Data center airflow is the main obstacle to early detection. NFPA 72 only gives smoke detector spacing data for rooms up to 60 air changes per hour, while contained aisles can run at 500 to 1,000 or more.
  • Real fires at OVHcloud (2021), Kakao (2022) and South Korea's national data center (2025) all began in power and battery equipment, and the early signals were local to the source.
  • Fixed detection stays in charge of alarms and suppression. A smoke sensor on a robot, a drone or a stationary hub adds location, trend and context, so people can act while a problem is still small.

What is smoke sensing?

Smoke is a cloud of tiny solid and liquid particles released when a material is heated past the point where it starts to break down. Smoke sensing measures how much of that cloud is in the air, almost always optically.

The common unit is percent obscuration per foot: how much light one foot of smoky air blocks. A conventional spot smoke detector alarms somewhere between about 0.5 and 4 percent per foot, while very early warning air sampling systems are commonly set to alert at 0.2 percent per foot, a level you would not see or smell.

Smoke sensing is not the same as particulate sensing. A particulate sensor counts and sizes dust to show how clean a room is, which we cover in our guide to air quality and contamination. A smoke sensor is tuned to the particles that combustion and overheating produce.


How do smoke detectors and smoke sensors work?

There are three main ways to sense smoke, and each sees a different part of a fire.

  • Photoelectric (light scattering): a light source and a sensor sit at an angle inside a dark chamber. Smoke particles scatter light onto the sensor, and the signal grows with the mass of smoke present.
  • Ionization: a tiny radioactive source makes the air in a chamber conduct a small current. Smoke particles disrupt it, and the signal tracks the number of particles, which favors the many small particles of flaming fires.
  • Aspirating, or air sampling: a fan pulls air through a network of pipes with sampling holes into a central laser detection chamber. Because it actively draws air from many points and reads it with a very sensitive chamber, it is the usual choice for very early warning.

Fire type matters. In tests by the National Institute of Standards and Technology (NIST), ionization alarms responded first to flaming fires by 147 seconds on average, while photoelectric alarms responded first to smoldering fires by 562 seconds on average.

Electrical faults in a data center usually begin as smoldering, low energy events: insulation heating, a connection cooking, a component degrading. That is why the industry leans on light scattering and air sampling for the earliest warning.


Why is smoke so hard to catch early in a data center?

The short answer is air. Cooling systems move air through a data hall many times an hour, and every pass dilutes and redirects whatever smoke is in it.

NFPA 72, the National Fire Alarm and Signaling Code, reduces detector spacing as air movement rises, but its spacing data only covers rooms up to 60 air changes per hour. Contained hot and cold aisles can run at 500 to 1,000 air changes per hour or more, which is why engineers turn to air sampling in these spaces.

Containment also changes where smoke goes. Smoke from a server travels with its exhaust into the hot aisle and on toward the cooling return, so a detector in the wrong place may only see it once it has been mixed with the air of the whole room.

Then there is the incipient stage itself. Research for the U.S. Nuclear Regulatory Commission and NIST on very early warning detection found that its length for electrical components is uncertain and highly variable, and that detection inside or close to an enclosure gives the earliest notice. Distance from the source costs time.


What actually produces smoke in a data center?

Most data center smoke starts in the power path and in moving parts, not in the servers themselves.


What do real data center fires show?

In November 2020, at a data center in Sydney, a failing bearing in an air conditioning unit created friction, then heat, then smoke. The smoke set off the gas suppression system, and the noise and force of the discharge damaged disks belonging to the betting company Tabcorp, which said it had no warning of the mechanical fault.

In March 2021, fire destroyed OVHcloud's SBG2 building in Strasbourg, a 2 MW site said to hold up to 30,000 servers. Firefighters' thermal cameras put two UPS units at the heart of the blaze, and reports noted that alarms did pick up the fire, but black smoke kept staff from intervening as it spread within minutes.

In October 2022, a fire in a battery room at SK C&C's Pangyo data center took Kakao's services down for 127 hours and 30 minutes. South Korea's ICT ministry found that the battery monitoring system failed to detect any abnormality.

In September 2025, a lithium ion UPS battery being disconnected for relocation at South Korea's National Information Resources Service in Daejeon went into thermal runaway. The fire burned for almost 22 hours, destroyed 384 battery modules, and took 647 government systems offline.

The pattern is the same each time. The fire began in one piece of equipment, and the earliest physical signs were local to it: heat, gas, then smoke, then everything at once.

What do the first minutes of those fires show?

Detection worked at OVHcloud. A guard saw thick smoke in a power room around 12:35 a.m., and detectors on all six floors triggered within 15 minutes. The French investigator judged that the detectors worked as designed (DatacenterDynamics, 2022).

Detection was not the problem. Emergency power stayed on until 1:13 a.m., and the site had no automatic fire suppression (same report). Knowing where smoke started only helps if someone can act on it.

At Pangyo, firefighters needed about eight hours to bring the battery room fire under control. Uptime Institute notes that local media reported several warnings from the battery management system (Uptime Institute Journal, 2023).

In September 2024, lithium ion batteries burned in third floor battery rooms at Digital Realty's SIN11 in Singapore. Firefighters used a firefighting robot to cool them, and the fire took two days to bring under control (DatacenterDynamics, 2024).

Uptime Institute's 2026 outage analysis says major data center fires have become gradually more frequent, with lithium ion UPS batteries a clear contributing factor (Uptime Intelligence, 2026).


What do the codes ask for?

NFPA 75, the standard for protecting IT equipment, calls for automatic detection that gives early warning of fire, installed and maintained under NFPA 72. NFPA 72 sets how detectors are spaced, tested and maintained.

NFPA 76, written for telecommunications facilities, goes further and defines three levels of detection: very early warning, early warning and standard. Very early warning systems are normally air sampling, include an alert signal separate from the alarm so staff can investigate, and limit each sampling port or sensor to 200 square feet, or 400 square feet with two levels of ports.

In Europe, the EN 54-20 standard rates aspirating detectors as Class A, B or C, and points to Class A, the most sensitive, for places such as data centres. Whichever code applies, the authority having jurisdiction decides what a facility must install.


Why is fixed detection not the whole answer?

Fixed detection is life safety equipment, and it is very good at its job. It is designed to raise a reliable alarm, trigger suppression, and avoid false alarms that empty a building or dump a clean agent for nothing.

That design leaves gaps that a mobile sensor can fill. A detector or sampling pipe reports a zone, not a rack, and everything below its threshold is invisible to the people walking the floor.

  • Location: an air sampling pipe can draw from dozens of holes, so an alert says which pipe, not which cabinet.
  • Trend: a slow rise at one rack that never reaches the alert level does not show up as an event anywhere.
  • Coverage gaps: detectors are sometimes covered with dust caps during work and left that way, or a new rack row changes the airflow they were designed around.
  • Context: a detector cannot tell whether a reading comes with heat, gas or a noise, which is exactly what tells a real problem from nuisance dust.

Why put a smoke sensor on a robot?

A robot can take the sensor to the smoke instead of waiting for the smoke to find the sensor. It samples at rack exhaust height, beside the PDU, in front of the battery cabinet, and at the cooling return, where a faint signal is still concentrated.

Smoke in moving air is patchy and intermittent, so one reading on its own proves very little. A robot that stops at the same checkpoint, in the same pose, on every pass builds a baseline for each spot, and a rise against that spot's own normal is far more meaningful than any single number.

The robot also carries other senses. A smoke reading beside a thermal image, a gas reading and an acoustic signature taken at the same moment turns a vague signal into a likely cause.


What about drones?

Drones extend the same idea upward and outward. They can reach the tops of cable trays, high bay ceilings in warehouses and plant rooms, cooling towers, rooftop equipment and generator yards, where a ground robot cannot see and a person needs a lift.

Drones also come with real physics limits. Rotor downwash stirs the very air being measured: a 2026 study of gas sensing under a propeller rig found readings dropped by up to 52.7 percent, with the strongest effect within about 2 to 3 meters, and placing sensors above or to the side of the airframe is the usual answer.

Flight time, a lithium ion battery on board, and tight aisles full of live equipment all argue for using drones where height and open space make them the right tool. On the data hall floor, the ground robot and the stationary hub do most of the work.


Where else does smoke sensing matter?

Any facility where a small fire would stop something important has the same problem: lots of energy, lots of air, and equipment that has to keep running.

  • Telecommunications central offices and network hubs, the facilities NFPA 76 was written for.
  • Battery energy storage sites and UPS rooms, where gas and smoke are the earliest outside signs of a cell in trouble.
  • Hospital electrical and generator rooms, where a power fault becomes a patient safety problem.
  • Semiconductor fabs and clean rooms, which already rely on very sensitive air sampling.
  • Warehouses and distribution centers that store or charge lithium ion batteries, where high ceilings suit drones.
  • Utility substations and control rooms, often unmanned for long stretches.

The 10 minute smoke risk walk

Anyone can run this check. Walk the same route each time and note what you see, hear and smell at the same points.

  1. 1. Detector heads and sampling pipes: no dust caps or bags left on, no pipes knocked loose, nothing new blocking them
  2. 2. Air sampling panel: no alert or trouble indication standing, airflow within its normal band
  3. 3. PDUs, remote power panels and busway taps: no hot smell, no discoloration, no buzzing
  4. 4. UPS and battery rooms: no swollen cases, no odor, no warning lights on the battery monitor
  5. 5. Cooling units: no grinding or squealing from fans and bearings
  6. 6. Cable trays and floor voids: no damaged jackets, no cables crushed under tiles
  7. 7. Work areas: hot work permits closed, area checked after the work finished
  8. 8. Air intakes: no generator exhaust or outside smoke drawn in
  9. 9. The record: date, time, a smoke reading and a photo at each point, and any point reading above its own baseline

Anything that looks or smells wrong goes to the person who owns that space. Done every week, this turns smoke risk from a feeling into a record.


How FacilityOps uses smoke sensing

A FacilityOps robot walks the route through data halls, UPS and battery rooms, electrical rooms and cable vaults on a schedule, carrying the FacilityOps sensor hub. Its smoke sensor reads airborne smoke by how particles scatter or block light, and every reading is tied to the place, the time and the asset in front of it.

What the robot does at every checkpoint

  1. 1. Drives to each sampling point using 3D lidar and simultaneous localization and mapping (SLAM), stopping at the same rack inlet, UPS cabinet or cable tray each pass so readings compare like for like.
  2. 2. Confirms the rack, cabinet or panel in front of it is the asset the route names before recording, so every reading is filed against the right asset.
  3. 3. Holds the same position and angle as every previous pass and stores that pose with the reading, so this week's number can be laid beside last week's.
  4. 4. Samples the air at the height that matters for that checkpoint, such as rack exhaust, the front of a battery cabinet or a cooling return.
  5. 5. Captures thermal, gas, acoustic and visual readings at the same pose and the same moment, so every smoke reading arrives with context.
  6. 6. Leaves a point blank when the sensor is still settling or the air path is blocked, rather than filling in a smoke value it never measured.

Six things smoke sensing on the route makes possible

  • A baseline for every spot: each checkpoint learns its own normal, so a rise of a few times that normal stands out even while it is far below any alarm threshold.
  • Narrowing the source: readings from neighboring checkpoints on the same pass, each compared with its own baseline, narrow a rise to a row, a rack or a cabinet, and the thermal image at that pose shows whether something there is running hot.
  • Telling a threat from nuisance: smoke with a hot spot points to overheating, smoke with a particulate rise after construction points to dust, and gas rising ahead of smoke beside batteries points to off gassing that needs attention now.
  • Covering the rooms nobody walks: UPS rooms, battery rooms, cable vaults and storage rooms get the same check at 3 a.m. on a Sunday as on a Tuesday afternoon.
  • Watching work periods: after hot work or commissioning, the robot samples the work area on its next passes, and its camera shows whether a detector head still has its dust cap on.
  • Seeing smoke come in from outside: readings near air intakes and economizer inlets show generator exhaust or wildfire smoke entering the building, with a time and a place.

How robots, drones and stationary hubs share the job

  • Robots cover the floors: every aisle, room and cabinet face on the route, on a schedule.
  • Drones cover what is high or outside: cable tray tops, high bays, cooling towers, roofs and generator yards.
  • Stationary hubs watch what needs constant attention: a flagged battery cabinet, a hot PDU or a small room a robot cannot enter. An alert from the hub sends the robot to look.

What happens when something changes

  • The FacilityOps platform compares every reading with the same checkpoint's last passes, so a change since the last round stands out.
  • A smoke reading above a checkpoint's own baseline goes straight to the facilities lead on shift, with the thermal image and photo from that spot, and becomes a work order in FacilityOps or in your existing system once someone has looked.
  • The next pass confirms the reading is back at its baseline, so the record shows the fix as well as the finding.

An illustrative record entry

UPS room 1, battery cabinet B3 · Run 57, checkpoint 12 · Captured from the same pose as run 56

Change found: smoke reading about four times this checkpoint's four week baseline, with no rise at checkpoints 11 or 13. Thermal shows the terminal on string 2 at 41°C against 30°C for the strings beside it. Gas reading unchanged.

Routed to: electrical supervisor, work order opened. Closed: run 59 shows the terminal at 30°C and smoke back to baseline after the connection was serviced.

The fixed checkpoint method behind these readings is already proven in production: a FacilityOps robot has run autonomous rounds at the CRSC Data Center, powered by Solutions IS, in Houston, since July 28, 2026.

The first minutes: how an overheating part announces itself

An illustrative timeline for a failing power supply in a rack, with the detection thresholds that apply at each stage. The thresholds come from NRC and manufacturer documents.

  • Before any smoke: the part runs hot. A thermal image on the robot's pass shows the supply several degrees above its neighbors, while no smoke detector has anything to see.
  • Incipient stage: insulation and board coatings begin to break down and release fine particles. A very early warning aspirating system sends an Alert near 0.2 percent per foot obscuration at the sampling port.
  • Several hundred seconds later: in NRC and NIST cable heating tests, that is roughly the lead an aspirating detector held over an ionization spot detector.
  • Alarm: the very early warning system alarms at 1 percent per foot at the port. Spot detectors typically sit around 1 to 2 percent per foot, so they are only now near their own threshold.
  • Fire 1 and Fire 2: heavier smoke. Fire 2 is reserved for an advanced fire, and by then suppression is the story, not detection.

The robot works both ends of that timeline: a thermal and smoke baseline that can catch the hot part before the incipient stage, and a dated reading at the exact rack once an Alert sounds, so responders know where to look.

Coming next: driving to the zone that raised an aspirating Alert as soon as the fire panel reports it, and returning a thermal image of that zone within minutes.

What the evidence says

  • An NRC fire protection FAQ applying NFPA 76 defines very early warning detection as an alert at 0.2 percent per foot and an alarm at 1 percent per foot at each port; spot detectors that meet only NFPA 72 do not qualify, per FAQ 08 0046.
  • In full scale NRC and NIST tests on heated cable insulation, an aspirating detector generally alerted several hundred seconds before an ionization spot detector alarmed, the SUPDET 2015 paper reports.
  • A current VESDA detector offers four thresholds, Alert, Action, Fire 1 and Fire 2, adjustable from 0.005 to 20 percent obscuration per meter, per the Xtralis datasheet.
  • The NRC estimates that four days of detector downtime cuts system effectiveness by about an order of magnitude, and one day by about a factor of three, in the same FAQ.

A ceiling detector tells you the building has smoke. A sensor that comes to the rack tells you where it started, what it came with, and whether it is getting worse.


What won't the robot do?

The FacilityOps robot is not a fire alarm system, and it does not replace listed smoke detection, air sampling or suppression. It never sends an alarm to the fire panel, triggers a release or calls the fire department.

It does not fight fires, enter a space during an evacuation, or stand in as a fire watch. It records conditions, people act on them, and the authority having jurisdiction decides what protection a facility needs.


Five questions to ask about smoke risk in your facility

If any answer here is a guess, that is where an incipient fire would go unnoticed.

  1. 1. Where in the building would the first smoke from a failing PDU or battery string go, and how long until a detector sees it?
  2. 2. Which air sampling alerts did you have last year, and how many were traced to a specific rack or cabinet?
  3. 3. Which rooms with power or battery equipment go unvisited overnight and at weekends?
  4. 4. After the last construction or hot work, who checked that every detector head was uncovered?
  5. 5. Can you show the readings around your UPS and battery rooms for the last three months?

Smoke sensing questions we hear most

What is smoke sensing?

Smoke sensing measures combustion particles in the air, usually by how much they scatter or block light. Detectors are rated in percent obscuration per foot, the share of light that one foot of smoky air blocks.

What is the difference between smoke sensing and particulate sensing?

A particulate sensor counts and sizes dust to show how clean the air is. A smoke sensor is tuned to the particles that overheating and combustion produce, which is why FacilityOps carries them as separate sensors.

Why do data centers use air sampling smoke detection?

Data center cooling moves so much air that smoke is diluted quickly. Air sampling actively draws air from many points into a very sensitive laser chamber, so it can alert at levels far below what a conventional spot detector needs.

What does NFPA 76 require for very early warning fire detection?

NFPA 76 defines very early warning, early warning and standard detection for telecommunications facilities. Very early warning systems include an alert signal before the alarm and limit each sampling port or sensor to 200 square feet, or 400 square feet with two levels of ports.

Do photoelectric or ionization detectors work better in a data center?

NIST found photoelectric detectors respond sooner to smoldering fires and ionization detectors respond sooner to flaming fires. Electrical faults usually start smoldering, so data centers lean on light scattering and air sampling detection.

What causes most data center fires?

Power equipment is the usual starting point: UPS systems and their batteries, loose electrical connections, overloaded cables and failing fans or bearings in cooling units. The OVHcloud, Kakao and Daejeon fires all began in UPS or battery equipment.

Can a robot detect smoke?

Yes. A robot carrying a smoke sensor can sample the air at rack, cabinet and battery level on every pass, compare each reading with that spot's own baseline, and pair it with thermal and gas readings. It adds location and trend to the building's fire detection, which stays in charge of alarms.

Can drones be used for smoke detection indoors?

Drones suit high and open spaces such as high bays, cable tray tops, cooling towers and generator yards. Rotor downwash disturbs the air being measured, so sensors are mounted above or to the side of the airframe, and ground robots do most of the work in tight data hall aisles.

Does a robot replace smoke detectors or a fire watch?

No. Listed detection and suppression stay in charge of life safety, and a fire watch is a trained person. The robot adds a dated record of readings and conditions that helps people find and fix problems earlier.

How does FacilityOps use smoke sensing?

A FacilityOps robot carries the FacilityOps sensor hub on a scheduled route, samples smoke at fixed checkpoints from the same position every pass, pairs it with thermal, gas, acoustic and visual readings, and turns every change into a work order. Drones and stationary hubs extend the same record to high places and to equipment that needs constant watching.

What do Alert, Action, Fire 1 and Fire 2 mean on an aspirating smoke detector?

They are four escalating smoke thresholds on one aspirating detector. Alert and Action flag very faint smoke so staff can investigate during the incipient stage, while Fire 1 and Fire 2 mark heavier smoke, with Fire 2 reserved for advanced fire stages. A FacilityOps robot round helps by giving responders dated thermal images and particle readings at the rack an alert points to.

How much earlier does aspirating detection warn than a spot smoke detector?

In NRC and NIST cable heating tests, an aspirating detector generally alerted several hundred seconds before an ionization spot detector alarmed. The gap comes from sensitivity: about 0.2 percent per foot for very early warning systems versus roughly 1 to 2 percent per foot for spot detectors. A FacilityOps robot round helps by recording thermal and particle data around the source once an alert sounds.

How much floor area can one air sampling hole cover?

Under NFPA 76, one sampling port or sensor can cover at most 200 square feet. Where ports are installed at two levels, such as ceiling and below the floor, each level is limited to 400 square feet per port. Closer spacing catches smoke sooner. A FacilityOps robot round helps by photographing sampling pipe, holes and caps on a dated schedule so blocked or broken ports are noticed.


If you want to see how a smoke reading, a thermal image and a fix are recorded together, we can send you a sample inspection record.