Moisture and Air · Airflow

Airflow Problems in Air Handlers and CRAH Units: Weak Airflow, Leaky Ducts and Dampers That Lie

An airflow problem is an air handler or CRAH (computer room air handler) delivering less air than designed, or air to the wrong places. The cause is usually hidden inside the ductwork.

Fan airflow rises in step with fan speed, but pressure rises with the square of speed and power with the cube. That is why a fan pushing air against a clogged filter, a closed damper or a crushed duct burns more energy while delivering less air.

Airflow faults hide inside sheet metal. Their signs show up as pressure, noise and temperature. Most of them can be read on a walk past by someone who knows where to look and listen.

Key takeaways

  • Fan laws: airflow follows speed, pressure follows speed squared, power follows speed cubed. Extra resistance costs steeply in energy.
  • Weak airflow usually comes from loaded filters, dirty coils, slipping belts, closed or stuck dampers, crushed or disconnected duct, or a fan running backward.
  • Duct leaks hiss in the ultrasonic range and show as cool streaks on thermal images. Sudden whistling means a new gap or a damper that moved.
  • Damper indicators can show open while the blades are closed. Only looking at the blades proves the position.

Why does an air handler deliver less air than designed?

An air handler delivers less air than designed when the system resists airflow more than it should, or the fan delivers less than it should. Most causes fall into a short list.

  • Loaded filters, covered in Part 6.
  • Dirty coils, covered in Cooling Plant Performance Part 2.
  • A slipping belt, covered in Rotating Equipment Part 4.
  • A fan running backward after wiring work.
  • Closed or stuck dampers.
  • Crushed or disconnected flex duct.
  • Blocked return grilles.
  • A variable frequency drive (VFD) held below full speed by a setting.

A fan running backward is the strangest on the list. A centrifugal fan turning the wrong way still moves some air in the right direction. It can go unnoticed for months, delivering a fraction of its rated flow.

A quick rotation check catches the backward fan. Look at the arrow on the fan housing and watch the wheel as the fan coasts to a stop after a shutdown. Do this after any motor or drive work.

Several small causes often stack. A slightly loaded filter, a dirty coil and a partly closed damper can together cut airflow far more than any one of them.


What do the fan laws say about speed, pressure and power?

The fan laws describe how a fan behaves as its speed changes in a given system. They are basic physics and apply to every fan in a building.

  • Airflow is proportional to fan speed.
  • Pressure is proportional to speed squared.
  • Power is proportional to speed cubed.

What that means in practice

Slowing a fan to 80% speed cuts airflow to 80%, pressure to about 64% and power to about 51%. That is why variable speed fans save so much energy at part load.

It works the other way too. If the system's resistance doubles, from a loaded filter or a closed damper, airflow falls unless the fan speeds up. Speeding it up to recover the lost air costs power with the cube of speed.

So every unnecessary restriction in an air system is paid for twice: once in lost air, and again in the energy used to push past it. Motor heating from that extra work is covered in Rotating Equipment Part 6.


How does uneven airflow distribution show up?

Uneven distribution shows up as some zones or racks getting too much air while others get too little. The total airflow may be fine; it is going to the wrong places.

Common causes

  • Dampers left unbalanced after changes or repairs.
  • Disconnected branch ducts dumping air into a ceiling space.
  • Closed or blocked diffusers and grilles.
  • New partitions or equipment that changed the air paths.

In an office, the complaints come from the zones at the end of long runs, while zones near the unit are too cold. In a data hall, some racks run hot while their neighbors are fine.

Comparing temperatures across zones or racks at the same time is the quickest way to see it. Rack intake temperatures at several heights show where air is not arriving.


Where do ducts leak, and how do you find leaks?

Ducts leak at seams, joints, access doors and connections to equipment. Old ductwork with dried out sealant leaks more than new, and flexible duct leaks where it is clamped to collars.

Why it matters

Supply leaks into ceiling plenums or mechanical rooms waste conditioned air and may cause sweating, covered in Part 1. Return leaks pull in unconditioned or dirty air, which loads filters and coils.

SMACNA, the Sheet Metal and Air Conditioning Contractors' National Association, publishes duct leakage classes and test methods that set how tight a duct system should be.

Finding leaks

High velocity leaks produce turbulent airflow noise, often in the ultrasonic range above human hearing. Airborne ultrasound picks out a leaking seam from several feet away, even in a noisy room.

Thermal imaging shows cold supply air escaping at seams as cool streaks on surrounding surfaces in cooling mode. In heating mode, the streaks are warm.


What does whistling or rushing air mean?

Whistling means air is being forced through a small gap, a partly closed damper or an undersized opening. The higher the pitch, the smaller the gap and the higher the pressure behind it.

Whistling that has always been there may be a design issue, such as an undersized grille. Whistling that appears suddenly points to a change: a new gap, a damper that has moved, or a door that no longer seals.

Rushing air at a door or under it points to a pressure difference between spaces. That is covered in Part 8.

Sound is easy to record. Acoustic monitoring at the same points on each round turns a whistle into a dated finding rather than a vague complaint.


How do dampers stick or report the wrong position?

Dampers control airflow with blades that open and close. They fail in ways that are hard to see from outside.

  • Actuators fail and stop moving.
  • Linkages slip on their shafts, so the actuator moves but the blades do not.
  • Blades bind with corrosion, dirt or debris.
  • Position indicators show open while the blades are closed, or the other way round.

A slipped linkage is the classic trap. The actuator's indicator says 100% open, the building management system agrees, and the blades sit closed. Only looking at the blades proves the position.

Outside air dampers

Outside air dampers stuck open waste heating and cooling energy and risk freezing coils in winter, covered in Part 3. Stuck closed, they starve the building of ventilation.

Fire and smoke dampers are a life safety item, inspected under their own rules. They are covered in the Electrical, Controls and Safety sub-series.


How do you check a damper on a walk past?

Checking a damper properly means comparing three things: what the controls command, what the actuator indicates and what the blades actually do.

  • Read the commanded position on the controller or building management system.
  • Read the actuator's position indicator.
  • Look at the blades through an access door, or at the shaft and its position mark.
  • Look for a scribe mark or paint line across the shaft and linkage. If the marks no longer line up, the linkage has slipped.

Where safe, ask for the damper to be stroked from fully closed to fully open while you watch. Blades that lag, stick or stop short are a finding even if the actuator reaches its end.

Mark shafts and linkages with paint when they are known to be right. On later rounds, a mark that has moved is a slipped linkage found in seconds.

Photograph each damper's indicator and blades from the same spot. That record shows when a damper started to drift.


How do static pressure readings help?

Static pressure is the pressure the fan builds in the duct, measured in inches of water column. Many air handlers display it, or have a gauge or test port for it.

It is one of the most useful airflow readings on a walk past. Static pressure that is higher than usual at the same fan speed means more resistance downstream: a closing damper, a loading filter or a blocked duct. Lower than usual can mean a disconnected duct, an open access door or a big leak.

Variable speed systems usually control fan speed to hold a static pressure setpoint. There, watch the fan speed instead. A fan creeping faster over weeks to hold the same pressure is fighting growing resistance somewhere.

Record static pressure and fan speed together on each round. Either one alone can mislead.


When does an air system need balancing again?

Air balancing sets each damper so every zone gets its design airflow. It is done at commissioning by a test, adjust and balance (TAB) contractor. It does not stay right forever.

Signs it is out of balance

  • Persistent hot and cold complaints in the same zones.
  • Balancing dampers found moved, or with their locking quadrants loose.
  • New partitions, tenants or equipment since the last balance.
  • A fan or unit replaced with a different model.
  • In data halls, racks added or moved, and tiles changed.

Rebalancing costs money, so it is worth confirming the simpler causes first: filters, dampers, disconnected branches and blocked grilles. Once those are clear and complaints remain, a new balance is often the cheapest fix left.

Keep the last balance report with the system. It gives the design airflow for every outlet, which turns a vague complaint into a number to check.


What happens when ductwork is damaged or disconnected?

Damaged or disconnected ductwork dumps air where it is not wanted and starves the spaces it was meant to serve.

  • Flex duct that has fallen off its collar, blowing into a ceiling space.
  • Crushed sections, flattened by other trades or stored material.
  • Access doors left open after maintenance.
  • Torn duct wrap and insulation, which let ducts sweat.

A disconnected supply branch can blow conditioned air into a ceiling for years. The zone it was meant to serve gets little air, and the ceiling space gets cold, which can cause condensation on the warm side of ceiling tiles.

Access doors left open are common after filter changes and coil cleaning. An open door on the suction side of a fan pulls in unfiltered air; on the pressure side, it blows conditioned air into the mechanical room.


How do return air paths fail?

Return air paths get less attention than supply ducts, but a blocked return starves a unit just as surely as a blocked supply.

Ceiling plenum returns

Many office buildings return air through the ceiling space instead of ducts. New walls built to the deck, fire stopping and stored material can block those paths. A zone with no return path pressurizes and its supply air slows.

Return grilles

Furniture, boxes and equipment pushed against return grilles block them. In mechanical and electrical rooms, stored material in front of returns is common.

Transfer grilles and door undercuts

Rooms without their own return rely on transfer grilles or gaps under doors. Replacing a door with a tighter one, or blocking a transfer grille, cuts the room off. Air then rushes under the door, which is covered in Part 8.

Data hall returns

In data halls, hot air must find its way back to the CRAH intakes. Ceiling return plenums and hot aisle chimneys only work if their openings stay clear and their panels stay in place.

A walk past that checks return grilles and paths takes minutes and catches problems that supply side checks never will.


How do CRAH airflow problems affect a data hall?

In a data hall, a CRAH delivering too little air leaves rack inlets warm even when its supply air is cold. The unit's own readings may look fine.

Common causes

  • Loaded filters.
  • Failing fans or fan bearings, covered in Rotating Equipment Part 1.
  • Blocked underfloor paths from cable bundles or stored material.
  • Floor tiles in the wrong places, covered in Part 8.

Underfloor blockages are the hidden one. Cable trays, abandoned cables and stored boxes under a raised floor can block air paths that once fed whole rows. The CRAH pushes harder, its fans speed up, and the racks at the end of the blocked path still run hot.

Comparing each CRAH's fan speed with its neighbors' is a quick check. The unit running hardest is often fighting a restriction somewhere.


What looks like an airflow problem but is not?

Three conditions look like airflow faults.

Normal VFD turndown

Variable speed fans slow down at low load by design. Lower airflow at night or in mild weather is expected.

Containment and pressure problems

Air moving the wrong way between spaces or around racks can look like low airflow. It is covered in Part 8.

A cooling problem

Warm supply air is a cooling problem, not an airflow problem. Check the supply air temperature before chasing dampers. Underperforming cooling units are covered in Cooling Plant Performance Part 4.


What do airflow problems cost?

Airflow problems cost energy, comfort and cooling capacity.

In an office building

Hot and cold complaints, higher fan energy, poor ventilation and wasted conditioned air.

In a data center

Hot spots at rack inlets. CRAH fans running at high speed to compensate. Stranded cooling capacity: cold air the plant produces but cannot deliver where it is needed.


What can a walk past prove, and what needs a follow up test?

A walk past can find disconnected duct, wrong damper positions and leaks by sound and temperature. Measuring actual airflow needs instruments.

Directly observable

Disconnected or crushed duct. Open access doors. Damper positions that disagree with indicators. Blocked returns and floor openings.

Strong indicators

Whistling or ultrasonic hiss at seams. Cool streaks on thermal images at duct joints. Supply air temperature normal while room or rack temperatures run warm.

Suspected, needs follow up

Actual airflow in cubic feet per minute (cfm) and leakage rate. That needs a duct traverse, a flow hood or a duct leakage test.

Recurring comfort calls from the same zone often trace back to an airflow fault that was never written down. The pattern is covered in inspection evidence for recurring HVAC failures, where HVAC means heating, ventilation and air conditioning.


Walk up checklist for airflow, ducts and dampers

  • Listen along accessible duct runs and at dampers for whistling or hissing.
  • Damper blade positions checked against actuator indicators.
  • Disconnected flex duct, open access doors and crushed sections.
  • Fan VFD speed and unit static pressure displays.
  • In data halls: floor tiles and underfloor paths for blockages.
  • Supply air temperature compared with rack inlet temperature.

How FacilityOps detects it

Coming Soon


Questions to ask about your own equipment

  1. 1. When was your air system last balanced, and what has changed since?
  2. 2. Which dampers have actuators that have never been stroke tested?
  3. 3. Are outside air dampers confirmed closed on cold nights?
  4. 4. Where does ductwork run through ceiling spaces nobody looks at?
  5. 5. Which CRAH units run their fans hardest, and why?

Frequently asked questions about airflow, ducts and dampers

Why is my air handler not delivering enough air?

Common causes are loaded filters, dirty coils, slipping belts, closed or stuck dampers, crushed or disconnected duct, blocked returns, a fan running backward and VFD speed limits.

What are the fan laws?

Airflow is proportional to fan speed, pressure to speed squared and power to speed cubed. Small speed changes have large effects on energy.

How do you find duct leaks?

Listen for hissing, often with airborne ultrasound, and look for cool streaks at seams with a thermal camera in cooling mode. A duct leakage test measures the total.

Why does my ductwork whistle?

Air is being forced through a small gap, a partly closed damper or an undersized opening. A sudden new whistle points to a new gap or a moved damper.

How do you know if a damper is stuck?

Command it to move and watch the blades, not just the indicator. If the actuator moves and the blades do not, the linkage has slipped or the blades are bound.

Can a damper show open when it is closed?

Yes. A slipped linkage lets the actuator and its indicator move while the blades stay put. Only the blades show the real position.

What happens if an outside air damper sticks open?

It wastes heating and cooling energy and, in freezing weather, can freeze coils.

Why are my rack inlets hot when the CRAH supply air is cold?

The CRAH may be delivering too little air, or the air is not reaching the racks because of blocked underfloor paths, misplaced tiles or recirculation.

Where do air ducts leak most often?

At seams, joints, access doors, flexible duct connections and connections to equipment.