Finding the Underperforming Chiller: Peer Comparison, kW per Ton and the Slow Drift Nobody Alarms On
An underperforming chiller is one that has quietly lost capacity or efficiency. The fastest way to find it is to compare it with identical machines at the same conditions.
Two identical chillers, piped in parallel and running at the same load and water temperatures, should read like twins. When one draws more power, runs a wider approach or needs more current for the same tons, the difference is the finding.
A plant full of near identical machines is its own test bench. No new instruments are needed, only the discipline to read every panel at the same time and write the numbers down.
Key takeaways
- kW per ton is electrical input divided by cooling output. Lower is better. COP equals 3.517 divided by kW per ton.
- Sibling comparison at matched conditions beats nameplate comparison in the field, because real plants never run at rating conditions.
- A widening gap usually points to fouling, refrigerant loss or mechanical wear, and the reading that differs tells you which.
- Slow drift against a machine's own baseline is the fault nobody alarms on. It only shows up if someone keeps the baseline.
What does it mean for a chiller to underperform?
A chiller underperforms when it delivers less cooling than it should, or uses more power than it should, for the conditions it is running in. Either way, it costs the plant capacity or money.
Underperformance is rarely sudden. A chiller loses a little efficiency as its tubes foul, a little capacity as refrigerant leaks, and a little more as its compressor wears. None of these trip an alarm until they are severe.
The machine still runs, still holds setpoint most days and still looks normal on a quick glance at the panel. That is why it goes unnoticed for months or years.
There are two ways to catch it. One is to compare the chiller with its identical neighbors. The other is to compare it with its own earlier readings. This post covers both.
What is kW per ton, and how does it relate to COP?
kW per ton is electrical input in kilowatts divided by cooling output in tons. It is the standard efficiency measure for chillers in North America. Lower is better.
Converting to COP
COP, the coefficient of performance, is cooling output divided by power input in the same units. One ton of cooling is 12,000 Btu per hour, or about 3.517 kW of heat. So COP equals 3.517 divided by kW per ton.
A chiller at 0.60 kW per ton has a COP of about 5.9. At 0.80 kW per ton, the COP is about 4.4.
What a small change is worth
At one hotel, cleaning fouled condenser tubes was predicted to improve efficiency from about 0.80 to 0.75 kW per ton (ACHR News). That is a 6% cut in chiller power for the same cooling. Fouling is covered in Part 2.
On a 500 ton chiller at full load, 0.05 kW per ton is 25 kW. Over thousands of running hours a year, that is a real line on the energy bill.
Measuring it in the field
Field kW per ton needs power and tons. Power comes from the chiller panel or a meter. Tons come from flow times delta T, divided by 24, using the method in Part 1. Without a flow meter, the pressure drop estimate in Part 3 gives a usable figure.
Why compare a chiller with its siblings rather than its nameplate?
Because real plants never run at rating conditions. A sibling at the same conditions removes those differences, so what is left is the machine itself.
How chillers are rated
Chillers are rated under AHRI 550/590, the Air Conditioning, Heating and Refrigeration Institute standard, at fixed water temperatures, flows and fouling allowances. Compliance with ASHRAE Standard 90.1, the energy standard, is judged on that rating (ASHRAE interpretation).
On a real afternoon, entering condenser water may be warmer, flow may be lower, load may be 55% and the tubes may be dirtier than the allowance. The nameplate number is not wrong. It just describes a different day.
Why siblings work
Identical chillers in the same plant share the same weather, the same towers, the same water and usually the same setpoints. If both run at the same load, any difference in power, approach or lift belongs to the machines.
This turns every plant with two or more identical chillers into a controlled experiment, run every day for free. Sites with different models can still compare each machine with its own baseline, covered below.
Which readings make a fair comparison?
A fair comparison needs matched conditions first and the right readings second. Without matched conditions, every difference has an innocent explanation.
Conditions to match
- Same model and size.
- Same percent load.
- Same entering condenser water temperature.
- Same leaving chilled water setpoint.
If two siblings are running at different loads, compare readings from a time when they matched, or let the controls balance them for an hour first.
Readings to compare
- kW, or percent rated load amps.
- Condenser and evaporator approach.
- Lift, the difference between condensing and evaporating pressure or temperature.
- Compressor discharge temperature.
- Oil pressure.
- Inlet guide vane position or variable frequency drive (VFD) speed.
Most of these are on the chiller's own panel. Photographing every panel on the same round, within a few minutes, gives a clean side by side record. The habit is described in reading the gauges nobody monitors.
What does a widening gap between siblings usually mean?
A widening gap means one machine is changing and the other is not. The reading that differs points to the likely cause.
Higher approach
A wider condenser or evaporator approach on one machine suggests fouling on that side, covered in Part 2. On the condenser side, non condensable gases such as air in the refrigerant cause the same signature.
Lower suction pressure
Lower evaporating pressure on one machine, with a wider evaporator approach, suggests refrigerant loss. That is covered in Leaks Part 6.
Higher current at the same output
More amps for the same tons and the same lift points to compressor or motor wear. Possible causes include worn bearings, a damaged impeller, or motor winding problems. These are covered in Rotating Equipment Part 6 and Part 7.
Higher discharge temperature or lower oil pressure
These point to mechanical distress inside the compressor. They deserve a call to the service contractor rather than a wait and watch.
Sound and vibration add another layer. A compressor that sounds different from its twin, or a motor bearing that reads higher on contact ultrasound, often points to wear before the panel numbers move.
How do you track slow drift against a chiller's own baseline?
You track drift by keeping a baseline, the readings taken when the machine was known to be healthy, and comparing with it at similar conditions.
Where baselines come from
The best baselines are commissioning data, start up reports from the manufacturer, and readings taken right after a tube cleaning or major repair. A good baseline records load, entering and leaving water temperatures, approaches, lift, power and current together.
How to compare
Pick conditions that recur often, such as 70% load with condenser water near its usual summer temperature. Each month, find a reading near those conditions and compare it with the baseline.
Slow degradation shows up as a steady creep. Approach rises a fraction of a degree a month, or power at matched load climbs a percent or two a quarter. No single alarm catches it, but a simple trend line does.
Capacity drift
Capacity drift is the clearest form. A chiller that can no longer hold its leaving water setpoint at a load it used to carry, while its peers can, has lost capacity. That needs investigation, not just a note.
How do part load ratings like IPLV fit in?
IPLV and NPLV are single numbers that summarize a chiller's efficiency across part load conditions. They come from AHRI 550/590. IPLV is the integrated part load value at standard conditions, and NPLV is the non standard part load value at a project's own design conditions.
They matter because most chillers spend most of their hours at part load. A chiller can be efficient at full load and much less so at 40%, or the other way around.
For field comparison, IPLV and NPLV are background, not a test. They help explain why one model behaves differently from another at part load. Sibling and baseline comparison at matched conditions still does the real work.
They also matter for operations. Controls that run three chillers at 40% load, when two could run at 60%, may push every machine into a less efficient part of its curve. That pattern often goes with low delta T, covered in Part 1.
How do you compare CRAH and CRAC units the same way?
Air side cooling units serving the same room can be compared exactly like chillers. CRAH means computer room air handler, a unit with a chilled water coil. CRAC means computer room air conditioner, a unit with its own refrigerant compressor.
Readings to compare
Compare supply air temperature, return air temperature, fan speed and chilled water valve position. For CRAC units, add compressor status, suction and discharge pressure where shown.
What a gap means
A unit with its valve wide open but a warm supply air temperature is underperforming. Its coil may be fouled, its water may be starved, or its valve may be stuck. A unit with fans faster than its neighbors for the same return temperature may have dirty filters or a slipping belt, covered in Rotating Equipment Part 4.
Room layout matters. A unit near a hot aisle sees warmer return air than one at the end of a row. Compare like for like positions where possible, and confirm the room effect with rack intake temperature readings rather than return air alone.
Why does lead and lag rotation matter for finding a weak chiller?
Lead and lag rotation decides which chiller runs first and longest. It matters because the machine that runs most is both the one that wears fastest and the one whose losses cost the most.
Many plants rotate the lead chiller weekly or monthly to even out run hours. Others never rotate, and one machine racks up most of the plant's hours. Check the run hour counters on each panel to see which pattern you have.
Rotation also helps comparison. When each sibling takes a turn as lead, there are regular periods when each one carries similar load in similar weather. Those periods are the best moments to compare.
A plant that never rotates has a hidden risk. The lag chiller may sit idle for months and fail when it is finally called on. Running it on a schedule, and recording its readings when it runs, proves it is ready.
What a standby chiller should prove
When a standby machine starts, it should reach setpoint, share load and show approaches and current close to its siblings. If it struggles, the plant has less redundancy than its drawings say, and now is the time to find out.
How do you build a side by side record that holds up?
A side by side record holds up when it is taken the same way every time. Same panels, same screens, same order, close together in time.
Photograph each panel rather than copying numbers by hand, so the record shows exactly what the panel showed. Note the time, the outdoor conditions and which machines were running. A photo of the plant overview screen ties them together.
Keep the record with the asset, not in someone's notebook. An entry in a computerized maintenance management system (CMMS) or an inspection report for each chiller makes the trend easy to pull when a contractor or insurer asks. Acoustic notes, such as a compressor that sounds different from its twin, belong in the same record.
What looks like an underperforming chiller but is not?
Three conditions create a gap between siblings without any fault in the machine. Rule them out first.
Unequal loading
Controls do not always share load evenly. One chiller may run at 80% while its twin runs at 50%. Compare at matched load, or the gap is meaningless.
Different entering water temperatures
Piping layout or tower cell differences can send slightly warmer condenser water to one chiller. A weak tower cell is covered in Part 5. Check entering temperatures before blaming the machine.
Sensor or gauge errors
One drifted temperature sensor or one stuck gauge can make a healthy chiller look sick. Instrument faults belong to the Electrical, Controls and Safety sub-series. A quick cross check with a handheld reading settles most doubts.
What does an underperforming unit cost?
An underperforming unit costs energy every hour it runs and capacity the day it is needed most.
In an office building
The least efficient machine is often the one the controls run most, because it is the lead. Every lead hour on a worn or fouled chiller costs more than the same hour on its healthy twin. The effect shows up in the building's energy score, covered in the ENERGY STAR Portfolio Manager guide.
In a data center
A chiller that has silently lost capacity reduces real redundancy. When it is called on during a failure, it may not carry its share. The site that counted on N+1, one spare chiller beyond the load, discovers it was running closer to N.
The cost of finding it early is small. A side by side panel record on every round, kept for a year, is enough to see which machine is drifting.
What can a walk past prove, and what needs a follow up test?
A walk past can prove that one machine differs from its siblings or its own past. Finding the root cause takes a closer look.
Directly observable
Panel readings of current, approaches, temperatures and pressures on each machine, side by side. Which chiller is lead and how many hours each has run.
Strong indicators
One machine consistently worse than its siblings at matched conditions. A steady downward trend against its own baseline. A chiller that cannot hold setpoint at a load its peers carry.
Suspected, needs follow up
The root cause. That needs tube inspection, a refrigerant charge check, oil analysis or a formal performance test.
The comparison is only as good as the record behind it. No single sensor is enough, and no single round is either. The value is in readings taken the same way every time.
Walk up checklist for an underperforming chiller
- Every chiller panel photographed on the same round, at the same time.
- Percent load, current, approaches, lift and setpoints recorded for each machine.
- Lead chiller and run hours for each machine.
- CRAH and CRAC units in the same room: supply air temperature, valve position and fan speed.
- Comparison with last month at similar conditions.
How FacilityOps detects it
Coming Soon
Questions to ask about your own equipment
- 1. Do you know each chiller's kW per ton at typical load?
- 2. Which chiller runs most, and is it the most efficient one?
- 3. Do you have commissioning or post cleaning baselines for each machine?
- 4. Do your controls rotate lead chillers?
- 5. Which CRAH units in the same room run their valves wider than their neighbors?
Frequently asked questions about chiller performance
What is a good kW per ton for a chiller?
It depends on the type, size and conditions. The useful test in the field is whether a chiller matches its identical siblings and its own baseline at the same load and water temperatures.
How do you convert kW per ton to COP?
COP equals 3.517 divided by kW per ton, because one ton of cooling is about 3.517 kW of heat. A chiller at 0.60 kW per ton has a COP of about 5.9.
How do you know if a chiller is losing efficiency?
Compare its power, approaches and lift with an identical chiller at the same conditions, and with its own baseline. A steady rise in kW per ton or approach at matched load is the sign.
Why compare chillers to each other?
Identical chillers share weather, water and setpoints, so differences at matched load belong to the machines. It is more useful in the field than comparing with nameplate ratings.
What is IPLV?
IPLV, the integrated part load value, is an AHRI 550/590 figure that weights chiller efficiency across part load conditions. NPLV is the same idea at a project's own design conditions.
Why does one chiller use more power than an identical one?
Common causes are fouled tubes, refrigerant loss, non condensable gases and compressor or motor wear. Unequal load or warmer entering water can also explain it, so check those first.
How do you track chiller performance over time?
Keep a baseline from commissioning or after a cleaning. Each month, compare readings at similar load and water temperatures with that baseline and plot the trend.
How do you compare CRAH units?
Compare supply air temperature, return air temperature, fan speed and valve position for units in the same room. A unit with its valve wide open and warm supply air is underperforming.
Does chiller efficiency drop with age?
Efficiency drops with fouling, refrigerant loss and wear, which tend to accumulate with age. Good maintenance and a tracked baseline keep that loss visible and recoverable.