Icing and Freeze Damage in Mechanical Systems: Coils, Chillers, Cooling Towers and Exposed Pipe
Icing in mechanical systems is ice or frost forming on coils, refrigerant lines, chillers, towers and pipe. It is a warning sign in summer and a cause of burst equipment in winter.
Water expands by about 9% when it freezes, and no pipe, coil or heat exchanger tube is built to contain that. Trapped water that freezes splits the metal around it.
Yet the most common ice in a mechanical room forms in July, not January. It grows on a cooling coil starved of airflow, or on a refrigerant line running too cold. Ice is a symptom in summer and a cause of damage in winter.
Key takeaways
- Summer ice on a cooling coil means too little air or too little heat: dirty filters, a failed fan, low refrigerant charge or very cold supply.
- Frost on a suction line back at the compressor, or on the compressor itself, can mean liquid refrigerant is coming home. That is a compressor risk.
- A chiller evaporator can freeze at low flow or low load. A split tube lets water into the refrigerant circuit and can take the chiller out for months.
- In winter, stuck outside air dampers, poorly mixed air and failed preheat valves freeze coils. Towers need written freeze procedures, and glycol needs its concentration checked.
Why does ice form on cooling equipment in warm weather?
Ice forms on cooling equipment in warm weather when a surface that normally runs just above freezing drops below it. Cooling coils and refrigerant lines run cold by design, so it does not take much to push them over the edge.
A direct expansion coil might run at a refrigerant temperature near 40°F (4°C). If airflow drops, or the refrigerant pressure falls, the coil surface slips below 32°F (0°C). Moisture removed from the air then freezes on the fins instead of draining.
Once ice starts, it feeds itself. Ice blocks airflow, so less warm air reaches the coil, so the coil gets colder, so more ice forms. A lightly iced coil can become a solid block within hours.
That is why summer ice is a symptom. The ice is not the fault. It is the result of a fault upstream that needs finding before the unit is simply defrosted and restarted.
What causes a cooling coil to ice?
A cooling coil ices when it gets too little heat from the air, or runs too cold on the refrigerant or water side. The common causes fall into those two groups.
Too little air
- Clogged filters, covered in Part 6.
- A failed or slow fan, or a slipping belt, covered in Rotating Equipment Part 4.
- Closed dampers or blocked returns, covered in Part 7.
- A dirty coil face that restricts air through the fins.
Too cold on the inside
- Low refrigerant charge, which lowers evaporating pressure and temperature, covered in Leaks Part 6.
- Very low chilled water supply temperature.
- Running at very low load, when the coil has little heat to absorb.
In a data hall, an iced CRAH (computer room air handler) or CRAC (computer room air conditioner) coil starves the racks it serves of cold air. The unit may still look like it is running, with cold air near the coil and warm air at the racks.
What should you do when you find an iced coil?
When you find an iced coil, the goal is to thaw it safely and find the cause before it happens again.
Shut off cooling to the coil while leaving the fan running if that is safe, so warm air melts the ice. Expect a lot of water: the drain pan and drain line must handle it, or it will end up on the floor. Condensate drains are covered in Part 4.
Never chip ice off fins. It bends them and can puncture tubes.
While it thaws, check the usual causes in order: filters, fan and belt, dampers, refrigerant pressures or chilled water temperature, and load. Write down what was found. A coil that ices twice in a season with no cause recorded will ice a third time.
What does frost on a refrigerant line or compressor mean?
A little sweating on a suction line is normal. Heavy frost that runs all the way back to the compressor, or frost on the compressor body itself, is not.
Floodback
Frost at the compressor can mean liquid refrigerant is returning from the evaporator instead of vapor. This is called floodback. Compressors are built to pump vapor, and liquid can wash out oil and damage valves and bearings.
An evaporator running too cold
Frost on the suction line can also mean the evaporator is running far colder than designed, often from low airflow or low charge. The coil itself may be iced as well.
Either way, it is worth a call to the refrigeration technician rather than a wait and watch. Compressor distress is covered in Rotating Equipment Part 7.
Frost on the outside of a compressor shell is never normal. Even if the unit is still cooling, it is running in a way that shortens compressor life.
Frost is easy to see and easy to photograph. A frosted suction line on one unit, next to a dry one on its twin, is a strong finding.
How does a chiller evaporator freeze?
A chiller evaporator freezes when the water in its tubes is cooled below 32°F (0°C). That happens when flow is too low or the refrigerant runs too cold, especially at low load.
With less water passing through, each gallon gives up more heat and gets colder. Refrigerant pressure falls with it. Low load makes this worse because there is less heat in the water to keep it above freezing.
What a frozen tube does
Ice expands and splits the tube. Once the tube is split, water can enter the refrigerant circuit, where it mixes with oil and refrigerant and can destroy the compressor and the chiller's internals. Repair can take months.
The protections
Flow switches and low temperature safeties exist to trip the chiller before the tubes freeze. They only protect it if they are set correctly, wired in and tested. A flow switch jumpered out after a nuisance trip is a frozen evaporator waiting to happen.
Low flow and its warning signs are covered in Cooling Plant Performance Part 3.
How do heating and preheat coils freeze in winter?
Heating, preheat and chilled water coils freeze in winter when freezing outside air reaches them faster than the water inside can warm it. A few minutes is enough.
Common causes
- Outside air dampers stuck open, or opened too far, in freezing weather.
- Economizers that mix air poorly, so a stream of cold outside air stratifies across part of the coil.
- Preheat coil valves that fail closed, so no hot water flows when it is most needed.
- Chilled water coils left full of water in units that see outside air in winter.
Stratification is the hidden one. The mixed air temperature sensor may read 50°F (10°C) while the bottom third of the coil sees 20°F (minus 7°C) air.
Freeze protection
A freeze stat is a long capillary temperature sensor stretched across the coil face. It trips the unit, closes outside air and opens the heating valve if any part of the coil face gets too cold. It only works if it covers the face, is set correctly and is tested before winter.
Stuck dampers are covered in Part 7.
What happens to cooling towers in freezing weather?
Cooling towers in freezing weather build ice on louvers, fill and fan blades. Heavy ice can crush fill, break louvers, unbalance fans and damage the structure (US Patent 10,345,056 background).
Over cooling
Running fans at full speed in very cold weather can over cool the water and freeze parts of the tower. Towers in winter usually run fans slower, cycle them or bypass water around the fill to keep it warm enough.
De icing
Reversing fans melts ice on the air inlets by blowing warm air out through them. It works, but it adds wear to gearboxes, covered in Rotating Equipment Part 8.
Basins and exposed piping
Basins and exposed piping need heaters, heat trace, drain down or another written freeze procedure. A tower cell that sits idle and full of water in freezing weather is a freeze risk.
The November 2025 CME outage at CyrusOne's Aurora, Illinois data center was attributed by CyrusOne to tower drain procedures not being followed ahead of freezing weather (DatacenterDynamics). It is covered in Rotating Equipment Part 8.
Where does exposed pipe freeze first?
Exposed pipe freezes first wherever outside air reaches it. Inside a heated building, that means a few predictable places.
- Lines near louvers and outside air intakes.
- Pipes along exterior walls, especially in corners.
- Unheated penthouses, attics and rooftop runs.
- Pipes near doors that are propped open or close slowly.
- Lines behind damaged louvers or missing panels.
Cold air infiltration creates local freeze spots inside rooms that are otherwise warm. A thermometer in the middle of the room tells you nothing about the pipe two feet from a broken louver.
Thermal imaging finds those spots quickly. Cold streaks running from a louver or door, and pipe surfaces near 32°F (0°C), stand out against a warm room.
Building wide freeze preparation for office buildings is covered in the Texas hard freeze checklist. This post focuses on what freezes inside HVAC (heating, ventilation and air conditioning) equipment.
How does glycol protect a loop, and when does it fail?
Glycol protects a loop by lowering the freezing point of the fluid. Loops exposed to outside air, such as dry coolers, rooftop runs and some heat recovery systems, often run a water and glycol mix.
How much protection
Protection depends on concentration. PG25 is a 25% propylene glycol mix, with inhibitors, common in liquid cooling loops. An Open Compute Project (OCP) draft guideline puts its freeze point at about 9°F to 14°F (minus 13°C to minus 10°C) (OCP draft).
How it fails
Glycol fails quietly through dilution. Every leak that is topped up with plain water lowers the concentration and raises the freezing point. After a few top ups, a loop designed for a hard freeze may be protected only to a mild one.
Glycol also degrades with age and heat, losing its corrosion inhibitors. Checking concentration and inhibitor levels before winter, and logging the makeup water added through the year, are the simple controls. Leak points in liquid cooling are covered in Leaks Part 5.
How do you get a mechanical room ready for winter?
Winter readiness is a short list done before the first hard freeze, not during it. Most freeze damage comes from something that was known and not checked.
Air handlers
Stroke every outside air damper and confirm it closes fully, with the indicator matching the blades. Test every freeze stat and confirm it trips the unit and closes outside air. Check preheat valves open on command.
Towers and outdoor water
Confirm basin heaters and heat trace work. Review the written freeze procedure with every shift, including which cells drain and when. Check that drain valves are reachable and work.
Glycol loops
Test concentration and inhibitor levels. Compare the makeup water added this year with the loop volume to see whether dilution is likely.
The building
Find and fix broken louvers, gaps around penetrations and doors that do not close. Insulate or heat trace pipes that run past them.
Record it
Photograph damper positions, freeze stat settings and heater status as they are checked. When the cold snap arrives, the team knows what was confirmed and what was not.
What should you check after a hard freeze?
After a hard freeze, the damage often shows only when things thaw. Ice in a split tube holds the water in; the leak starts when it melts.
Check these first
- Coils exposed to outside air, for leaks as they warm up.
- Chiller evaporators and condensers on idle machines, before restart.
- Tower basins, makeup lines and exposed piping, for splits and leaks.
- Fire sprinkler and domestic water lines near outside walls.
- Freeze stat trips and alarms logged during the event.
Restart slowly and watch. A coil that drips once the unit comes back on, or a chiller that loses refrigerant pressure, needs testing before it carries load.
Internal tube damage is not always visible. A pressure test or eddy current testing confirms whether coils and heat exchanger tubes survived.
What does freeze damage cost?
Freeze damage costs equipment, water damage and lost capacity, often all at once.
In an office building
Burst coils and pipes flood ceilings and floors as ice thaws. Heating or cooling is lost until coils are replaced, which can take weeks if parts are not in stock.
In a data center
Frozen tower cells or coils cut cooling capacity. A frozen chiller evaporator can take a chiller out for months. Both reduce redundancy at a time when the site may already be under stress.
What looks like icing but is not?
Three conditions look like ice or frost but are not a freeze problem.
Condensation
Condensation is liquid water, not frost. A sweating cold surface above freezing is a moisture problem, covered in Part 1.
Normal defrost frost
Heat pumps and refrigeration units frost their evaporators as part of normal operation and clear it in a defrost cycle. Light frost that clears on schedule is expected.
Mineral scale
White mineral scale on valves and fittings can look like frost from a distance. It is crusty and stays put when the equipment warms. Scale is covered in Leaks Part 4.
What can a walk past prove, and what needs a follow up test?
A walk past can see ice and frost and the conditions that cause them. Internal damage after a freeze needs testing.
Directly observable
Ice and frost on coils, lines, compressors, towers and louvers. Open outside air dampers in freezing weather. Frozen drains.
Strong indicators
Surface temperatures near or below 32°F (0°C) on water filled components. Low suction pressure together with low airflow.
Suspected, needs follow up
Internal tube damage after a freeze. That needs a pressure test or eddy current testing.
In winter, timing matters. A walk on the coldest night, or just after a cold front, sees what a daytime round misses. Visual inspection of damper positions and freeze stat status at those times is cheap insurance.
Walk up checklist for icing and freeze
- Cooling coils and refrigerant lines for frost or ice.
- In winter: outside air damper positions and freeze stat status.
- Pipes near louvers, intakes and exterior walls, imaged for cold spots.
- Tower louvers, fill and basin for ice, with basin heaters confirmed running.
- Glycol concentration records for glycol loops.
- Doors or louvers left open in cold weather.
How FacilityOps detects it
Coming Soon
Questions to ask about your own equipment
- 1. Which coils have iced up this year, and what was found?
- 2. Where are your freeze stats, and when were they last tested?
- 3. What is your written tower freeze procedure?
- 4. When was glycol concentration last tested in each glycol loop?
- 5. Which pipe runs sit next to outside air paths?
Frequently asked questions about icing and freeze damage
Why does my cooling coil freeze in summer?
Usually because of too little airflow or a coil running too cold. Common causes are clogged filters, a failed fan, low refrigerant charge, very cold supply and very low load.
What does frost on a refrigerant line mean?
Heavy frost back at the compressor can mean liquid refrigerant is returning, called floodback, or that the evaporator is running far too cold. Both deserve a technician's attention.
How does a chiller evaporator freeze?
Low water flow or low refrigerant temperature, often at low load, lets the water in the tubes fall below freezing. Ice splits the tubes and can let water into the refrigerant circuit.
What is a freeze stat?
A freeze stat is a capillary temperature sensor stretched across a coil face. It trips the unit and closes outside air if any part of the coil gets too cold.
How do you protect a cooling tower in winter?
Control fans to avoid over cooling, use de icing when needed, heat or drain basins and exposed piping, and follow a written freeze procedure.
Where do pipes freeze first in a mechanical room?
Near louvers, outside air intakes, exterior walls, open doors and unheated spaces such as penthouses and rooftops.
Does glycol prevent freezing?
Glycol lowers the freezing point. PG25 freezes at about 9°F to 14°F (minus 13°C to minus 10°C). Dilution from water top ups weakens the protection, so concentration must be checked.
How much does water expand when it freezes?
About 9% by volume. Water trapped in a pipe, coil or tube can split it when it freezes.
What should you check after a hard freeze?
Check coils, idle chillers, tower basins and piping near outside walls for splits as they thaw. Restart slowly, and pressure test anything in doubt.
Sources