SOC 2, ISO 27001 and PCI DSS: The Physical Controls Auditors Check, and the Evidence That Proves Them
Quick answer: To prepare inspection records for a SOC 2 audit, keep dated evidence that your physical controls worked across the whole audit period, not just a policy that says they should. Capture doors, cameras, cages, power and cooling from the same points on a regular schedule, tie each record to the control it supports, such as CC6.4 and A1.2, and keep it findable by date and location.
SOC 2 (System and Organization Controls 2), ISO/IEC 27001 and PCI DSS (the Payment Card Industry Data Security Standard) are the three assurance frameworks a data center is most often asked to hold. Each one tests physical and environmental controls: who can enter, how the equipment is protected, and whether power, cooling and the space around the systems are kept as described.
An auditor does not take those controls on trust. They ask for evidence that the controls operated, and for SOC 2 Type II, that they operated across the whole review period.
Access systems and cameras cover who went in. The condition of the space between audits is the part most operators struggle to show, and it is the part a dated physical record proves.
Key takeaways
- SOC 2 is the AICPA's System and Organization Controls report, ISO/IEC 27001:2022 is the international standard for an information security management system, and PCI DSS v4.0.1 is the Payment Card Industry Data Security Standard.
- All three test physical controls: SOC 2 through CC6.4 and A1.2, ISO 27001 through 14 physical controls in Annex A, and PCI DSS through Requirement 9.
- Auditors want evidence that a control operated over time, not a policy that says it should. Records built week by week answer that better than records assembled before a review.
- A dated record of doors, cameras, cages, cabling, power and cooling, captured from the same points on every pass, gives the assessor the physical layer. The assessor decides what it proves.
What are SOC 2, ISO 27001 and PCI DSS?
SOC 2, short for System and Organization Controls 2, is an attestation report issued by an independent CPA firm under the AICPA's Trust Services Criteria. Security is required in every SOC 2 report, and availability, processing integrity, confidentiality and privacy are added as needed. A Type I report looks at control design on one date. A Type II report tests whether the controls operated over a period, usually several months to a year.
ISO/IEC 27001 is the international standard for an information security management system, published by ISO and the IEC. The current edition, ISO/IEC 27001:2022, has 93 Annex A controls, 14 of them physical. Certificates to the 2013 edition expired at the end of the transition on October 31, 2025.
PCI DSS, the Payment Card Industry Data Security Standard, is maintained by the PCI Security Standards Council. The current version, v4.0.1, was published in June 2024, and its future dated requirements became mandatory on March 31, 2025. It applies wherever cardholder data is stored, processed or transmitted, including the data centers that host it.
Which physical controls do they test in a data center?
Each framework words it differently, but they ask about the same physical layer.
- SOC 2, CC6.4: physical access to facilities and protected information assets is restricted to authorized people
- SOC 2, A1.2: environmental protections, backup and recovery infrastructure are designed, maintained and monitored, which in a data center means power, cooling, fire and water protection
- ISO/IEC 27001:2022, Annex A 7.1 to 7.4: physical security perimeters, physical entry, securing offices, rooms and facilities, and physical security monitoring
- ISO/IEC 27001:2022, Annex A 7.5, 7.8 and 7.11 to 7.13: protection against physical and environmental threats, equipment siting and protection, supporting utilities, cabling security and equipment maintenance
- PCI DSS, Requirement 9: restrict physical access to cardholder data, including cameras or access control on sensitive areas, with records kept for at least three months, and visitor logs
Where a data center operator hosts other companies, its own reports become the evidence those customers rely on for these controls.
What evidence do auditors ask for?
For physical controls, an assessor usually asks for four kinds of evidence:
- Policies and procedures: how access is granted, reviewed and revoked, and how the environment is protected
- System records: badge logs, visitor logs, camera footage and environmental monitoring alarms, kept for the required period
- Maintenance records: inspections and service of power, cooling and fire protection, with dates and outcomes
- Proof of condition: what the controlled spaces actually looked like, and what was done when something was wrong
The first three are usually well covered. The fourth is where operators struggle, because it depends on someone having walked the spaces and recorded them, week after week, through the whole review period.
Why do physical controls fail audits?
Physical controls rarely fail because the policy is wrong. They fail because the space drifted between reviews.
- 1. A secure area door is propped open during a delivery and stays that way.
- 2. A camera is knocked out of alignment or blocked by a new cable tray.
- 3. A cage or rack door is left open after work.
- 4. Boxes and equipment end up stored in a secure room or against power equipment.
- 5. An environmental alarm fires, and there is no record of what was found or done.
- 6. The evidence for the review period is assembled in the week before the audit.
An assessor can usually tell the last one. A record put together for the occasion reads differently from one that has simply been accumulating.
What makes physical evidence credible?
It exists before anyone asks for it, and each item carries when, where and what was observed.
The same points are revisited, so there is a series rather than a snapshot. Findings link to what was done, and the next pass shows whether the condition changed.
It is retrievable a year later by someone who was not there. None of that is unique to these frameworks. It is what a record has to be to survive being examined.
The 10 minute physical controls walk
Anyone can run this check without touching a system. Walk the same route each time and photograph each point from the same spot.
- 1. Secure area doors: closed, latched, not propped
- 2. Cameras: in place, pointing where they should, not blocked
- 3. Cages and racks: doors closed, nothing left open after work
- 4. Storage: nothing stored in secure rooms or against power and cooling equipment
- 5. Cabling: trays tidy, no loose runs across walkways, nothing unlabeled left behind
- 6. Environment: temperature and humidity at the equipment, no water, no alarms on local panels
- 7. Power and cooling: units running, no unusual heat or noise
- 8. The record: date, time, a photo of each door, camera and reader, and any control that looked different from last time
Anything out of place goes to the owner of that space. Done every week, this builds the proof of condition an assessor asks for, without a scramble before the audit.
How FacilityOps produces physical evidence for audits
FacilityOps produces the proof of condition layer: a dated, repeatable record of every controlled space, built by a FacilityOps robot on every pass and kept in one place for the whole review period. It sits beside your access control, camera and monitoring systems, not in place of them.
What the robot does at every checkpoint
- 1. Navigates a fixed route through data halls, secure rooms, cages, electrical rooms and plant rooms using 3D lidar and simultaneous localization and mapping (SLAM), on a schedule that does not slip in a busy week.
- 2. Confirms the space or asset in front of it is the one the route names, and captures from the same position and angle as every previous pass, storing that pose with the capture.
- 3. Images each point with a pan tilt zoom camera: secure area doors and whether they are closed, cameras and whether they are in place and unblocked, cage and rack doors, cabling and signs.
- 4. Measures the space. Every pass updates a 3D digital twin, so equipment moved, boxes stored in a secure room or a cable run that appeared shows up as a measured change.
- 5. Reads the environment the controls protect: thermal capture of power and cooling equipment, temperature and humidity at rack intake height, and the FacilityOps sensor hub's leak, smoke, gas and air quality readings.
- 6. Notes a door it found shut, a cage it could not enter or a camera it could not see as out of view for that pass, so an assessor never reads a gap as a passed control.
What every record entry contains
- The asset and space, the run, the checkpoint, the date and time, and the pose it was captured from
- The images and readings taken at that point
- What changed since the last pass, if anything
- Who it went to, the work order, and the pass that confirmed it was fixed
An illustrative record entry
Secure room 1, cage C 4 · Run 211, checkpoint 52 · Captured from the same pose as run 210
Change found: cage door C 4 open with no work order active; two boxes stored against PDU 4B. Not present on run 210.
Routed to: security and facilities, work order opened. Closed: run 212 shows the cage door closed and the boxes removed.
The method is proven in a live data center. At the CRSC Data Center, powered by Solutions IS, in Houston, a FacilityOps robot completed 19 autonomous inspection runs and collected more than 1,600 observations from fixed checkpoints in its first three weeks, and a reading it flagged was confirmed within 1.1°F by a handheld check.
From control to evidence: what one walk hands an auditor
Each line pairs a physical control, summarized from its framework, with what a dated FacilityOps pass produces for it.
- SOC 2 CC6.4, physical access to the data center: each controlled door photographed closed and latched, the reader status light, and any door found propped.
- ISO 27001:2022 controls 7.1 and 7.2, perimeters and physical entry: perimeter doors, the mantrap and the loading dock captured from the same pose on every pass.
- ISO 27001:2022 control 7.4, physical security monitoring: a photo of every camera on the route showing it is present, aimed and undamaged.
- ISO 27001:2022 controls 7.8, 7.11 and 7.12, equipment siting, utilities and cabling: thermal images of power gear, temperature and humidity readings, and cable tray photos.
- PCI DSS 9.2.1.1, cameras or access controls on sensitive areas: camera and reader presence on each pass, so a disabled or knocked device is dated within days instead of found at the next annual assessment.
- PCI DSS 9.4.1.2, offline backup media locations: the backup storage room's door, lock and shelves photographed every lap, supporting the review due at least once every 12 months.
- PCI DSS 9.5.1.2, payment terminal surfaces: close photos of each terminal and its seals, compared pass to pass for tampering or substitution.
The auditor still tests the control. What changes is the population behind the sample: instead of one walkthrough on audit day, every week in the period has a photo behind it.
Coming next: exporting a period's captures as an evidence package indexed by control number, ready to answer an auditor's request list line by line.
What the evidence says
- Certificates issued against ISO/IEC 27001:2013 had to move to the 2022 edition on or before 31 October 2025 under IAF MD 26, so current certifications are audited against the revised physical controls, Schellman notes.
- PCI DSS v4 Requirement 9.5.1.2 calls for periodic inspection of payment terminal surfaces for tampering and substitution, per the v4.0.1 control text, and 9.5.1.2.1 lets the entity set how often through a targeted risk analysis, Basis Theory explains.
- Offline backup media locations must have their security reviewed at least once every 12 months under PCI DSS 9.4.1.2, per the same guide.
- Visitor logs for PCI DSS sensitive areas must be kept at least three months, CompliancePoint notes.
Every controlled space, from the same spot, on every pass of the review period. That is the difference between a policy that says a control operates and a record that shows it did.
The robot does not grant access, watch people or replace your badge, camera or monitoring systems. It documents physical condition, and what an assessor concludes from it remains theirs to decide.
How FacilityOps maps to SOC 2, ISO 27001 and PCI DSS, control by control
FacilityOps carries the physical documentation load, so the compliance team spends its time on the controls only people can run.
- SOC 2 CC6.4 and ISO 27001 7.1 to 7.3: secure area doors, cages and rack doors are recorded closed or open on every pass, with the date and an image.
- ISO 27001 7.4 and PCI DSS Requirement 9: cameras on the route are photographed in place and unblocked, so a camera knocked out of position is found on the next pass, not at the audit.
- SOC 2 A1.2 and ISO 27001 7.5: temperature, humidity, leak, smoke and thermal readings show the environmental protections working, and every exception has a dated response.
- ISO 27001 7.8: the 3D digital twin shows when equipment is moved or something is stored against it.
- ISO 27001 7.11 and 7.12: power and cooling equipment and cabling are captured on every pass, so their condition is on record, not assumed.
- ISO 27001 7.13: findings become work orders, and the next pass confirms the fix, which is the maintenance evidence an assessor looks for.
- SOC 2 Type II and ISO 27001 surveillance audits: the record covers every week of the review period, not only the week before the audit.
The same route produces the records for NFPA 75, NFPA 70B, ASHRAE 180 and the rest of all nine compliance surfaces, so the audit evidence is part of one facility record.
FacilityOps documents conditions. It does not certify compliance or issue opinions: that stays with your auditors, certification bodies and qualified security assessors.
Five questions to ask before your next audit
An assessor tests each of these by pulling a sample. When a dated record answers the sample, the walkthrough is short.
- 1. Can you show the condition of every secure room for each week of the review period?
- 2. When was each camera on your sensitive areas last checked for position and obstruction?
- 3. Which environmental alarms fired last quarter, and where is the record of what was done?
- 4. Was anything stored in a secure room or against power equipment in the last month?
- 5. For every physical finding in the period, where is the proof it was fixed?
SOC 2, ISO 27001 and PCI DSS questions we hear most
What does SOC 2 stand for?
SOC 2 stands for System and Organization Controls 2. It is an attestation report issued by an independent CPA firm under the AICPA's Trust Services Criteria, covering security and, where chosen, availability, processing integrity, confidentiality and privacy.
What is ISO 27001?
ISO/IEC 27001 is the international standard for an information security management system, published by ISO and the IEC. The current edition, ISO/IEC 27001:2022, has 93 Annex A controls, 14 of them physical.
What does PCI DSS stand for?
PCI DSS stands for Payment Card Industry Data Security Standard. It is maintained by the PCI Security Standards Council, and the current version is v4.0.1, published in June 2024.
Which SOC 2 criteria cover physical security?
CC6.4 covers restricting physical access to facilities and protected information assets. A1.2, in the availability criteria, covers environmental protections, backup processes and recovery infrastructure.
What are the physical controls in ISO 27001:2022?
Annex A 7.1 to 7.14: physical security perimeters, physical entry, securing offices, rooms and facilities, physical security monitoring, protection against physical and environmental threats, working in secure areas, clear desk and clear screen, equipment siting and protection, security of assets off premises, storage media, supporting utilities, cabling security, equipment maintenance, and secure disposal or reuse of equipment.
What does PCI DSS Requirement 9 require?
Restricting physical access to cardholder data: cameras or access control on sensitive areas with records kept for at least three months, visitor identification and logs, protection of media, and inspection of payment devices.
What is the difference between SOC 2 Type I and Type II?
Type I looks at whether controls are designed properly on one date. Type II tests whether they operated over a period, usually several months to a year, so the evidence has to cover that whole period.
Can robot inspection records be used as audit evidence?
They can be one input. A dated record of physical condition, captured from the same points on every pass, supports controls such as CC6.4, A1.2 and the ISO 27001 physical controls. Whether it is relevant and sufficient is the auditor's decision.
How does FacilityOps help with SOC 2, ISO 27001 and PCI DSS audits?
A FacilityOps robot records the condition of secure rooms, doors, cameras, cages, cabling, power and cooling from the same points on every pass, sends every exception to a person and confirms the fix. The result is a proof of condition record that covers the whole review period.
How long must CCTV footage be kept for PCI DSS?
Keep it at least three months. PCI DSS v4 Requirement 9.2.1.1 says data from cameras or access control systems watching sensitive areas must be stored for that long unless a law sets a different period, and the devices themselves must be protected from tampering. A FacilityOps robot round helps by photographing each camera and reader on every lap, so a missing or knocked lens is dated.
How often should payment terminals be inspected for tampering?
As often as your own targeted risk analysis says. PCI DSS v4 Requirement 9.5.1.2 asks for periodic inspection of payment terminal surfaces for tampering and substitution, and 9.5.1.2.1 has the entity set the frequency and type of check through that analysis. A FacilityOps robot round helps by capturing dated photos of each terminal and its seals for side by side review.
Does ISO 27001 require CCTV?
It requires monitoring, and CCTV is the usual way to deliver it. Control 7.4 in ISO 27001:2022, physical security monitoring, is commonly met with cameras, guard monitoring and environmental monitoring such as smoke and fire detection, all matched to the risk of the site. A FacilityOps robot round helps by adding dated photos, thermal images and sensor readings of the spaces cameras cannot see clearly.