Cooling Plant Performance · Heat Rejection

Cooling Tower Performance: Range, Approach, Cell Imbalance and the Hot Air That Comes Back Around

Cooling tower performance is how well a tower cools condenser water toward the outdoor wet bulb temperature. Two numbers, range and approach, tell you almost everything about it.

Range is how much heat the plant is dumping into the water. Approach is how close the tower gets that water to the outdoor wet bulb temperature. When approach creeps up while range holds steady, the tower is losing ground.

The chillers pay for it in lift and power. Every degree of warmer condenser water raises compressor work, and on the hottest afternoons it can push a chiller toward a high pressure trip.

Key takeaways

  • Range is entering minus leaving water temperature. Approach is leaving water minus wet bulb. Approach is the number that measures tower health.
  • Range up with approach steady means more load and a tower keeping pace. Range steady with approach rising means the tower has degraded.
  • Dry fill, clogged basins, broken nozzles and a weak cell are all visible on a walk past. So are plumes curling back into the inlets.
  • A formal performance test follows CTI ATC-105, which only counts when test conditions are close to design.

What are cooling tower range and approach?

Range and approach are the two temperature differences that describe a cooling tower's work. Both need the hot water entering the tower, the cold water leaving it and the outdoor wet bulb temperature.

Range

Range is the hot water temperature entering the tower minus the cold water temperature leaving it. A tower receiving 95°F (35°C) water and returning 85°F (29.4°C) water has a range of 10°F (5.6°C).

Range reflects heat load and flow, not tower performance. More heat from the chillers, or less water flow, makes the range wider.

Approach

Approach is the cold water temperature leaving the tower minus the ambient wet bulb temperature. With 85°F (29.4°C) leaving water on a 78°F (25.6°C) wet bulb day, approach is 7°F (3.9°C) (Fabrico).

Wet bulb is the lowest temperature evaporation can reach in the current air. No tower can cool water below it. Lower approach means better performance.

Effectiveness

Effectiveness combines the two. It equals range divided by range plus approach, times 100. In the example, 10 divided by 17 gives about 59%.


Why is approach the number that measures tower health?

Approach measures tower health because it isolates what the tower itself controls: how close it can bring the water to the best the weather allows.

Range moves with the plant's load. Leaving water temperature moves with the weather. Approach strips both out and leaves the tower's own ability to mix air and water.

Say a tower held a 7°F (3.9°C) approach last summer and holds 10°F (5.6°C) now, at similar wet bulb and load. It has lost about 3°F (1.7°C) of cooling. The chillers see that as warmer condenser water every hour they run.

Why chillers care

Warmer condenser water raises the chiller's condensing pressure and lift. Lift drives compressor power and, in centrifugal machines, surge risk. That is covered in Rotating Equipment Part 7.

A healthy tower is one of the cheapest efficiency gains in a chiller plant. A degraded one quietly taxes every chiller it serves.


How do you read range and approach together?

Read them together to separate a load change from a tower problem. Each pattern has a likely meaning.

Range up, approach steady

More load or less flow, and the tower is keeping pace. This is normal on a busy afternoon.

Range steady, approach rising

The tower has degraded. The usual suspects are fouling, airflow loss or poor water distribution (Fabrico).

Range down, approach steady

Less load, or more flow than usual. Check whether extra pumps or cells are running.

Both rising

More load on a tower that is also struggling. Check fans and fill first.

One reading is not enough. Wet bulb changes through the day, and the tower's water takes time to respond. Compare readings at similar wet bulb and load, ideally from the same time of day.


What does uneven water distribution do to a tower?

Uneven water distribution leaves parts of the fill dry. Dry fill does no cooling, and air rushes through it because it offers the least resistance. The tower loses capacity twice: wet areas get less air and dry areas waste the air they get.

Crossflow towers

Crossflow towers feed water into open hot water basins on top. Water drops through orifices in the basin floor onto the fill. Clogged orifices leave dry streaks down the fill face that are often visible from the side.

Counterflow towers

Counterflow towers spray water down from pressurized pipes and nozzles above the fill. Broken, missing or clogged nozzles leave dry zones under them.

Uneven loading

Even with clean basins and nozzles, uneven water loading across the fill reduces performance. A tilted basin, an unequal header split or a partly closed cell valve can all cause it (NTPC performance paper).

Routine visual inspection of basins and spray patterns catches most of these. Photographing the same views each time shows when a clog started.


How do damaged or fouled fill and blocked nozzles show up?

Damaged or fouled fill shows up as a smaller wetted surface and rising approach. Fill is the honeycomb or splash material where air and water meet, so anything that reduces its contact area reduces cooling.

Scaled and biological fill

Scale and biological growth clog the narrow channels in film fill. Water then channels through the open parts, and air follows. Heavy deposits also add weight and can collapse fill packs.

Collapsed or sagging fill

Collapsed, sagging or broken fill leaves gaps. Air bypasses through the gaps without touching water. Missing sections are often visible from the air inlet.

What the camera adds

Thermal imaging of the fill face or the air inlet can show warm bands where water is not being cooled. Water vapor and reflections complicate readings, so thermal is best used to compare one area of the same tower with another.

Biological growth, Legionella and water treatment are covered in the Moisture and Air sub-series. Mineral scale and its effect on condenser tubes are covered in Part 2.


What do basin level, overflow, makeup and blowdown tell you?

The basin is the tower's water account. Level, overflow, makeup and blowdown together show whether water is entering and leaving as it should.

Low basin level

Low basin level risks pump vortexing, where the pump pulls air down through a whirlpool at the suction. That causes cavitation and loss of flow. Cavitation is covered in Rotating Equipment Part 3, and flow loss in Part 3.

Overflow

Water pouring from an overflow wastes water and treatment chemicals. The usual cause is a stuck makeup float valve or a level controller fault.

Makeup and blowdown

Towers lose water to evaporation, drift and blowdown, the controlled bleed that keeps minerals in check. Makeup replaces it all. Abnormal makeup points to leaks or overflow. Abnormal blowdown points to a failed blowdown controller.

Reading the makeup and blowdown meters on every round, as covered in reading the gauges nobody monitors, turns these into a daily water balance. A sudden jump is often the first sign of a leak elsewhere in the open loop.


What is drift, and when is it a problem?

Drift is water droplets carried out of the tower with the exhaust air. It is different from the visible plume, which is water vapor condensing as it meets cooler air.

Drift eliminators, rows of shaped blades above the fill or spray zone, catch most droplets and return them to the tower. A small amount of drift is normal and designed for.

Visible water carryover means damaged or missing drift eliminators, or airflow above design. Signs include wet surfaces and puddles downwind, mineral spotting on nearby cars and roofs, and a fine mist you can feel.

Drift wastes water and treatment chemicals. Because tower water can carry bacteria, excess drift is also a health concern, which is covered in the Moisture and Air sub-series.


How do you find a weak cell in a multi cell tower?

In a multi cell tower, each cell should show a similar leaving water temperature. One warmer cell is the weak one.

What to compare

Compare cell outlet temperatures where each cell has its own outlet. Where cells share a basin, compare basin temperatures by cell where piping allows, or compare the water falling from each cell's fill.

Compare by eye too. A cell with dry fill streaks, a quieter fan or less air movement at the inlet stands out next to its neighbors.

What a weak cell suggests

One warmer cell suggests poor distribution, fouled fill, a weak fan or an unequal flow split. Fans and gearboxes are covered in Rotating Equipment Part 8.

Sound helps too. A fan that is slipping a belt, running slow or carrying a damaged blade sounds different from its neighbors. Acoustic monitoring and vibration readings at the fan deck turn that difference into a number you can compare round to round.

A weak cell can hide in the mixed outlet. Healthy cells make up the difference until the hottest day, when there is no margin left.


What is recirculation, and how does tower siting cause it?

Recirculation is warm, moist exhaust air drawn back into the tower's own inlets. When a neighbor tower's exhaust is drawn in, it is called interference. Either way, the tower breathes air with a higher wet bulb than the weather.

A higher entering wet bulb raises the leaving water temperature, even if the tower is in perfect condition. The tower's measured approach against the true ambient wet bulb looks worse than its condition deserves.

What causes it

Walls or screens too close to the inlets, towers placed too close together, and wind patterns around buildings all cause recirculation. Equipment or storage placed near a tower after installation is a common cause.

CTI publication PFM-110 addresses recirculation and interference allowances (NTPC performance paper).

How to spot it

Look for plumes curling back toward the inlets, especially in light wind. Compare inlet air temperature or humidity near the tower with a reading upwind. A thermal image can show warm exhaust air pooling near the inlets.


How is a tower's thermal performance formally tested?

A tower's thermal performance is formally tested under CTI ATC-105, the Cooling Technology Institute's acceptance test code. The test compares measured performance with the tower's design curves.

Test conditions

A valid test needs conditions close to design. CTI's recommended limits allow wet bulb within ±15°F (±8.3°C) of design, range within ±20%, water flow within ±10% and fan power within ±10% (CTI recommended test conditions). Wind is limited to 10 mph.

Testing guidance also checks that water side and air side heat balances agree, commonly within 5% (performance testing guide).

When a test is worth it

A formal test is worth it at acceptance of a new tower and after a major fill or fan upgrade. It also helps when the approach trend says the tower is short and the owner wants proof before paying for a fix.

Between tests, the approach trend at similar wet bulb and load is the practical measure. It is cheap, repeatable and good at catching change.


How do seasons and part load change what you see at a tower?

Towers behave differently through the year, so the same reading can mean different things in July and January. Knowing the seasonal pattern prevents false alarms and missed faults.

Mild weather and part load

At light load, range narrows and fans slow or cycle. Approach can look excellent simply because the tower is oversized for the moment. A weak cell or dry fill may stay hidden until summer.

Cold weather

In freezing weather, fans may run in reverse or stop to prevent ice. Ice on louvers and fill is a sign of too much airflow for the load, or of water bypassing parts of the fill. Heavy ice can crush fill and damage fan blades.

Some plants use the tower for free cooling in winter, running condenser water through a plate exchanger to cool chilled water without the chillers. That makes tower approach matter in winter too, because every degree of approach decides how many hours free cooling can carry the load.

Peak summer

Summer is when tower faults cost the most and show the most. The best comparison is this summer's approach against last summer's, at similar wet bulb and load.


What should you record at a tower on every round?

Record entering and leaving water temperature, wet bulb, the number of cells and fans running, and fan speeds. Add basin level, makeup and blowdown meter readings.

Photograph the same views each time: each hot water basin or spray deck, each fill face and each air inlet. A set of matching photos over a year shows slow changes no one notices day to day.


What looks like a tower problem but is not?

Three conditions raise leaving water temperature without any tower fault.

High wet bulb weather

On humid days, leaving water rises even in a healthy tower. Approach stays steady. Always compare with wet bulb, not dry bulb or yesterday's water temperature.

Higher heat load

More load raises range, not approach. A wide range with a steady approach means the tower is working well.

A faulty instrument

A drifted basin or leaving water sensor can make a healthy tower look weak. So can a wet bulb sensor that is dirty or dry. Cross check with a handheld reading before acting.


What does a degraded tower cost?

A degraded tower costs chiller energy every day and plant capacity on the worst days.

In an office building

Warmer condenser water raises chiller energy and can cause high pressure trips on the hottest afternoons. Water and chemical waste from overflow and drift add to the bill.

In a data center

Lost heat rejection shrinks plant capacity and redundancy exactly when outdoor conditions are worst. A plant that is sized N+1, one spare unit beyond the load, may have no spare left on a humid afternoon with one weak cell.


What can a walk past prove, and what needs a follow up test?

A walk past can find most tower problems. Proving the tower's true capacity needs a formal test.

Directly observable

Dry streaks in fill, clogged hot water basin orifices, broken nozzles, low or overflowing basins, visible drift and obstructions near inlets.

Strong indicators

Approach rising at steady range. One cell warmer than its siblings. Thermal images showing uneven fill or exhaust plumes drawn back toward inlets.

Suspected, needs follow up

The tower's true capability against design. That needs a CTI ATC-105 test.


Walk up checklist for cooling tower performance

  • Entering and leaving water temperatures and outdoor wet bulb, with range and approach calculated.
  • Hot water basins or spray patterns for clogs and dry zones.
  • Fill faces for scale, sagging or gaps.
  • Basin level, float valve and overflow.
  • Drift and water carryover downwind of the tower.
  • Cells compared by temperature and by eye.
  • Air inlets checked for obstructions and plumes curling back.

How FacilityOps detects it

Coming Soon


Questions to ask about your own equipment

  1. 1. What is your tower's design approach, and what do you see today at similar wet bulb?
  2. 2. When were hot water basins or spray nozzles last cleaned?
  3. 3. How old is the fill?
  4. 4. Has anything been built or stored near the tower inlets since it was installed?
  5. 5. Has the tower ever had a CTI ATC-105 test?

Frequently asked questions about cooling tower performance

What is cooling tower approach?

Approach is the cold water temperature leaving the tower minus the outdoor wet bulb temperature. Lower approach means better performance. It is the best single measure of tower health.

What is cooling tower range?

Range is the hot water temperature entering the tower minus the cold water temperature leaving it. It reflects heat load and flow, not tower performance.

What is a good approach temperature?

It is the design approach for your tower at the current load and wet bulb. The warning sign is approach rising from its usual value at similar conditions.

Why is my cooling tower not cooling enough?

Common causes are fouled or damaged fill, clogged basins or nozzles, uneven water loading, weak fans, obstructed inlets and recirculation of warm exhaust air.

What causes uneven water distribution in a cooling tower?

Clogged hot water basin orifices in crossflow towers, broken or missing nozzles in counterflow towers, unequal header splits and partly closed cell valves.

What is cooling tower recirculation?

Recirculation is warm, moist exhaust air drawn back into the tower's own inlets. It raises the entering wet bulb and so the leaving water temperature.

What is cooling tower drift?

Drift is water droplets carried out with the exhaust air. Drift eliminators catch most of them. Visible carryover means damaged or missing eliminators or excess airflow.

How do you test cooling tower performance?

A formal test follows CTI ATC-105 under conditions close to design. Between tests, track approach at similar wet bulb and load.

How does cooling tower performance affect chillers?

Warmer condenser water raises the chiller's condensing pressure and lift. That raises compressor power and, in centrifugal chillers, surge risk.