Electrical, Controls and Safety · Electrical Discharge

Arcing, Corona and Tracking: The Electrical Faults You Can Hear, Smell and See Before They Burn

Three different electrical faults can make sound before they make heat. Arcing jumps a gap and crackles. Tracking creeps across a dirty or damp surface and leaves a carbon trail.

Corona glows invisibly around high voltage parts and slowly eats insulation. Each fault leaves its own signature: a sound, a smell, a mark or a powder.

None of them needs a cover opened to be noticed. This post explains how to tell them apart in mechanical room gear, and why ultrasound often hears them first.

Key takeaways

  • Arcing jumps an air gap and crackles erratically. Tracking creeps over contaminated insulation and leaves carbon trails. Corona buzzes steadily and makes ozone.
  • Airborne ultrasound picks up all three through seams and vents, often while there is little or no temperature rise.
  • Burn marks, discoloration, soot and white or green powder at terminals are physical evidence of past or ongoing discharge.
  • Smoke or a burning smell near electrical gear calls for immediate escalation, not more inspection. Work inside energized gear falls under NFPA 70E.

What is the difference between arcing, tracking and corona?

All three are electrical discharges: current going somewhere it should not. They differ in where the current goes and how fast the damage builds.

Arcing

Arcing is current jumping across an air gap. It typically happens at a loose, corroded or damaged connection, a failing contact, or a breakdown between conductors. It causes rapid local heating and can escalate quickly.

Tracking

Tracking is current creeping along the surface of insulation that is contaminated or damp. As it flows, it carbonizes a conductive path. Each event makes the next one easier, so tracking tends to grow.

Corona

Corona is partial ionization of the air around a conductor where the electric field is strong. It happens mostly on equipment at higher voltages. It does not complete a circuit, but it slowly degrades insulation and nearby surfaces.

A simple way to remember them: arcing jumps, tracking creeps and corona glows. Each leaves a different kind of evidence, which is why a walk past looks for sound, smell and marks together.

In practice they can overlap. Corona can weaken insulation until tracking begins, and tracking can carbonize a path until it arcs.


Where do these faults occur in a mechanical room?

Wherever conductors meet, wherever insulation gets dirty or damp, and wherever voltage is high enough to stress the air.

  • Motor control centers (MCCs), especially bucket stabs and line and load lugs.
  • Starters and contactors, where contacts open and close under load thousands of times.
  • Variable frequency drives (VFDs) and their input and output terminals.
  • Disconnect switches beside motors, often in damp or dusty spots.
  • Terminal boxes on large motors, where vibration loosens connections.
  • Medium voltage feeds and motors on large chillers, where corona becomes a real concern.

Mechanical rooms add their own stresses. Pumps vibrate, pipes sweat, filters shed dust and rooms swing between hot and cold. Every one of those conditions makes discharge more likely.


Why do connections loosen and contacts wear in mechanical room gear?

Most arcing starts at a connection that used to be tight. Mechanical rooms are hard on connections in several ways at once.

  • Thermal cycling: loads start and stop, conductors heat and cool, and metal expands and contracts. Over many cycles, bolted and screw connections creep loose.
  • Vibration from pumps, compressors and fans travels through floors, conduit and cabinets.
  • Corrosion from humid air, condensation and chemical fumes raises contact resistance.
  • Contact wear in starters and contactors that switch motors on and off many times a day.
  • Poor workmanship: connections never torqued properly, wrong lugs for the conductor, or aluminum and copper mixed without the right hardware.

A loose connection has higher resistance, so it heats. Heat speeds corrosion and loosening, which raises resistance further. Eventually the gap is large enough for current to jump it, and heating becomes arcing.

Short cycling makes contact wear much worse, because every start is a switching event under load. Cycling is covered in Part 6.


What does each one sound like?

Mostly, you will not hear them with your own ears until they are severe. Their early sound is in the ultrasonic range, above human hearing. An ultrasonic instrument translates it down to something you can listen to.

Arcing

Intermittent, erratic crackling and popping. The pattern is irregular, with bursts and silences, because the gap breaks down, extinguishes and breaks down again.

Tracking

A buzz or sizzle that varies. It often changes with humidity, because damp surfaces conduct more. It may come and go over the day.

Corona

A steady buzz, sometimes described as frying bacon heard from a distance. It is more uniform than arcing because the field around the conductor is constant.

Telling them apart by sound takes practice and a good instrument. Recording the sound and comparing it with the same point on the next round helps more than any single listen.


Why does ultrasound often catch them before heat does?

Because discharge makes high frequency sound immediately, while heating takes time and current. A small corona or tracking event may release very little heat but plenty of ultrasonic noise.

Airborne ultrasound can pick up those signatures through enclosure seams, vents and door gaps without opening anything. That makes it one of the few non contact methods that can screen closed gear for discharge.

Its limits

Ultrasound cannot hear through every enclosure. A well sealed cabinet, a thick door or loud background noise can hide a real problem. A quiet reading is therefore not proof of health.

This is why ultrasound and thermal imaging complement each other. Heat finds resistive connections that are not yet arcing. Ultrasound finds discharge that is not yet hot. The method itself is covered in the ultrasonic sensing post.


What smell and visual evidence do they leave?

Discharge leaves marks. Many of them are visible on the outside of gear, or around its vents, without opening anything.

  • Burn marks and scorching on enclosure surfaces, vents and seams.
  • Melted or discolored insulation on conductors that are visible.
  • Darkened paint around vents, louvers and door edges where hot gases escaped.
  • White or green powder at terminals, from corona byproducts and corrosion.
  • Soot on surfaces above or around the gear.
  • Dark, branching carbon trails on insulators, the signature of tracking.

Smells

Corona makes ozone, a sharp smell often compared to chlorine or the air after a thunderstorm. Arcing and overheating insulation smell of hot or burning plastic. Either smell near electrical gear is a finding.

Photograph the marks from fixed positions. A visual inspection record shows whether a mark is new, growing or old damage that was never cleaned.


How do you screen gear with ultrasound on a round?

The method is simple. Its value comes from doing it the same way every time.

Where to listen

  • Door seams and gaps, top and bottom.
  • Ventilation louvers and grilles.
  • Cable entry points and conduit fittings.
  • Around meter, indicator and window openings.

How to record it

Use the same instrument settings, the same distance and the same points on each round. Record the level and a short sound clip. Note the load on the equipment, since a lightly loaded starter may be quiet one day and noisy the next.

Compare each point with its own history and with similar gear nearby. A new sound, or a level well above its neighbors, moves that unit up the list. A sound that matches a known harmless source, such as a fan or an air leak, gets noted and set aside.


Why do moisture and dust make tracking worse?

Clean, dry insulation is a poor conductor. Add a film of dust and moisture and the surface starts to conduct. Current then has a path across the insulator instead of through it.

Mechanical room sources

  • Condensation on cold surfaces near electrical gear, covered in Moisture and Air Part 1.
  • Water intrusion from leaks, washdowns or roof drains reaching enclosures.
  • Dust and fiber from filters, insulation work and construction.
  • Humid outside air in rooms that are poorly sealed.

Dirty, damp insulators are the classic tracking site. Tracking often starts where dust settles on a flat surface and humidity is highest. Typical spots are the bottom of a cabinet and the top of a busbar support.

Cleaning and drying are the fix, done by qualified people with the power isolated. The walk past finds where dust and water are reaching the gear.


Where does corona occur, and why does voltage matter?

Corona needs a strong electric field at the surface of a conductor. That depends on voltage and on shape. Sharp edges, small radius conductors and protruding strands concentrate the field.

At the low voltages of most building gear, corona is uncommon. It becomes a real concern on medium voltage equipment, such as large chiller motors, medium voltage starters and their cable terminations.

Why it matters

Corona produces ozone and ultraviolet light invisible to the eye but visible to ultraviolet (UV) cameras. In humid air, corona byproducts can form nitric acid. That acid attacks insulation and metal and leaves the white or green powder seen at terminals.

Corona damage is slow. It may run for months, or even years, before insulation fails. That makes it a good candidate for routine screening rather than emergency response.


What does smoke or a burning smell near electrical gear mean?

It means active overheating or arcing. At that point the gear is no longer a candidate for inspection. It is an incident.

Smoke or a burning plastic or electrical smell from or near gear calls for immediate escalation under site procedures. That usually means alerting the people who can isolate power safely and keeping others away.

Do not open the enclosure to look. Arc flash and shock hazards make work inside energized gear qualified work under NFPA 70E. Smoke detection itself is covered in the smoke and particulate sensing post.


What sounds or smells like discharge but is not?

Contactor and relay clicks

Normal switching makes a sharp click when a contactor pulls in or drops out. It is brief and tied to an operation. Arcing crackle continues without any switching.

Transformer and ballast hum

Transformers and ballasts hum steadily at line frequency harmonics. The sound is uniform and predictable. Arcing is erratic, and corona is a steady buzz with a different, hissing texture.

Compressed air leaks

Air leaks hiss steadily in the ultrasonic range, and they are common near pneumatic controls. They are covered in Leaks Part 7. Following the sound to a fitting rather than a terminal usually settles it.

Harmless odors

New paint, cleaning products and hot dust on the first heating start up of the season all smell. They usually fade quickly and are not tied to one piece of electrical gear.


What do these faults cost?

In an office building

Escalating damage to starters and MCCs, fire risk in mechanical rooms, and sudden loss of pumps and fans. A tracking fault left for months can end in a failure that takes days to repair.

In a data center

Loss of drives and starters serving critical cooling. An arcing fault can also trip upstream protection and take out more than one load. One bad connection then becomes a cooling event.

Overheated connections that have not yet started to arc are covered in Part 1.



Which gear should get attention first?

Not all gear carries the same risk. A short ranking helps decide what to screen most often and what to escalate first.

  • Gear serving equipment with no backup, such as a single fire pump or the only chilled water pump on a loop.
  • Medium voltage gear on large chillers, where faults release more energy.
  • Gear in damp spots, near pumps, drains or condensing pipe.
  • Gear with a history of findings, replaced parts or nuisance trips.
  • Gear that switches often, such as starters on short cycling equipment.

Ranking also helps the follow up team a great deal. When a qualified electrician arrives, the list tells them which unit to open first and why.

Record every finding with the date, location, sound clip or image, and the load at the time. That record is what turns a one time observation into evidence that a fault is growing.


What does a qualified follow up look like?

The follow up is planned work, not a quick look. Typical steps include the following.

  • Review the walk past evidence: the sound clip, images, location and load at the time.
  • Decide whether the gear can be examined energized through windows or seams, or must be isolated from power first.
  • Prepare the work permit, personal protective equipment and isolation steps NFPA 70E requires.
  • Inspect, clean, tighten or replace the damaged parts.
  • Rescan the same points after the repair so the record shows the fault gone.

The last step is the one most often skipped. Without a rescan, nobody knows whether the repair fixed the source or only the damage it left.


What can a walk past prove, and what needs a follow up test?

Directly observable

Burn marks, discoloration, soot, white or green powder at terminals, smoke and burning odor.

Strong indicators

Erratic crackling or steady buzzing ultrasonic signatures at seams and vents. An ozone smell near higher voltage equipment. A signature that is louder than the same point last round.

Suspected, needs follow up

The location and severity inside the enclosure. That needs inspection by qualified personnel, often with covers removed under an energized work permit or with the equipment isolated from power.

The walk past narrows the search to one bucket or one terminal box. That makes the follow up faster and safer, because fewer covers come off.


Walk up checklist for arcing, tracking and corona

  • Listen with ultrasound at enclosure seams, vents and door gaps on MCCs, starters, VFDs and disconnects.
  • Look for scorch marks and discoloration on enclosure surfaces and vents.
  • Note any odor: ozone, burning or hot plastic.
  • Look for condensation, water or dust buildup around electrical gear.
  • Record and compare each reading with the same point last round.

How FacilityOps detects it

Coming Soon


Questions to ask about your own equipment

  1. 1. Has any mechanical room electrical gear been surveyed with ultrasound?
  2. 2. Where does moisture reach electrical enclosures in your mechanical room?
  3. 3. Which equipment runs at medium voltage?
  4. 4. When were MCC buckets last cleaned and their connections inspected?
  5. 5. What is your procedure when someone smells burning near electrical gear?

Frequently asked questions about arcing, tracking and corona

What is the difference between arcing and corona?

Arcing is current jumping a gap, usually at a bad connection, with erratic crackling and fast heating. Corona is ionized air around a high voltage conductor, with a steady buzz, ozone and slow insulation damage.

What is electrical tracking?

Current creeping across the surface of contaminated or damp insulation. It carbonizes a conductive path and leaves dark, branching trails. Each event makes the next one easier, so tracking tends to grow until the surface is cleaned or the insulation is replaced.

What does electrical arcing sound like?

Intermittent, erratic crackling and popping, mostly in the ultrasonic range at first. An ultrasonic instrument makes it audible. By the time you can hear it unaided, the fault is usually advanced.

Can ultrasound detect arcing?

Yes. Airborne ultrasound picks up arcing, tracking and corona through enclosure seams and vents. A quiet reading is not proof of health, because some enclosures block the sound.

What does ozone smell like near electrical equipment?

Sharp and clean, often compared to chlorine or the air after a thunderstorm. Near higher voltage gear it suggests corona.

Why do burn marks appear on electrical panels?

They come from arcing, tracking or overheating inside or at the surface. Hot gases escaping through vents and seams darken paint around them. A new or growing mark should be escalated to a qualified electrician.

Does moisture cause electrical tracking?

Moisture combined with dust or other contamination does. Damp, dirty insulators are the classic tracking site.

Can you detect corona with a camera?

Yes, with an ultraviolet (UV) corona camera. Corona's ultraviolet light is invisible to the eye and to ordinary cameras. These cameras are used mostly on medium and high voltage equipment, where corona is common enough to justify them.

What should you do if you smell burning near electrical equipment?

Escalate immediately under your site procedures and keep people away. Do not open the enclosure. Energized work is qualified work under NFPA 70E.