Heat Exchanger Fouling: How Scale, Biofilm and Debris Quietly Steal Chiller Capacity
Heat exchanger fouling is any deposit, such as scale, biofilm or debris, that slows heat through a surface. It quietly cuts a chiller's capacity and efficiency.
At the New Orleans Airport Hilton, scale building up in the condenser tubes of the centrifugal chillers did more than waste energy. It pushed condenser pressure high enough to drive the compressors into surge.
Fouling is invisible from the outside of a heat exchanger. Its effects are not. They show up in approach temperatures, pressures and kilowatts on every panel reading downstream.
Key takeaways
- A fouling factor is the extra thermal resistance a deposit adds. Chillers are rated with a small standard allowance, so a dirtier tube means performance below the rating.
- Condenser fouling raises head pressure and compressor power. Bad enough, it trips the chiller or pushes a centrifugal compressor into surge.
- A thin biofilm can insulate more than the same thickness of mineral scale. Biological control matters as much as scale control.
- Rising approach temperature at similar load is the best everyday sign of fouling. Most chiller panels already show it.
What is fouling in a heat exchanger?
Fouling is any unwanted deposit on a surface that is meant to pass heat. In a chiller, those surfaces are the inside of the evaporator and condenser tubes. In a coil, they are the fins and tubes. In a plate heat exchanger, they are the plates.
Every deposit adds thermal resistance. Heat now has to cross the deposit before it reaches the metal. The exchanger needs a bigger temperature difference to move the same heat, or it moves less heat at the same difference.
Fouling builds slowly. A tube that loses a fraction of a percent of performance each week shows no alarm and no single bad reading. Over a cooling season, the losses add up to real capacity and real money.
Fouling also compounds. A rough, scaled surface catches debris and gives bacteria a place to attach, and a biofilm traps silt and minerals. Once a deposit starts, it tends to grow faster.
That slow build is why fouling is best found by comparison: today against the last cleaning, and one machine against its siblings. The second method is covered in Part 4.
What is a fouling factor?
A fouling factor is a number for the extra thermal resistance a deposit adds. In US units it is given in hr·ft²·°F/Btu. A bigger number means a thicker or more insulating deposit.
The rating allowance
Chillers are rated under AHRI 550/590, the Air Conditioning, Heating and Refrigeration Institute standard for water chilling packages. It sets standard field fouling allowances of 0.0001 for evaporators and 0.00025 for condensers, in hr·ft²·°F/Btu (ASHRAE interpretation of the AHRI allowances).
New machines are tested clean, then their ratings are adjusted to include these allowances. In other words, the published rating already assumes a small amount of dirt.
What that means in the field
A chiller in service that is dirtier than the allowance will perform worse than its rating. It will draw more power, run a wider approach and deliver less capacity at the same conditions.
The allowance for condensers is larger for a reason. Condenser water usually comes from an open cooling tower, which pulls in dust, pollen and microbes from the air. Closed chilled water loops stay cleaner.
What kinds of fouling form in chillers and heat exchangers?
Four main kinds of fouling form in HVAC (heating, ventilation and air conditioning) heat exchangers. Most real deposits are a mix of two or more.
Mineral scale
Hard minerals such as calcium carbonate come out of solution on hot surfaces. Condenser tubes are hot, so they scale first. Scale forms when water treatment or blowdown does not keep up with the minerals the tower concentrates.
Biofilm and slime
Bacteria attach to surfaces and wrap themselves in a sticky layer. Biofilm traps silt and feeds corrosion underneath it. Open towers give it light, warmth and food.
Corrosion products
Rust and other corrosion products build up as layers or flakes. They also travel and settle in low flow areas. Pipe corrosion is covered in Leaks Part 3.
Silt and debris
Dirt, leaves, fill fragments and sludge enter through towers and settle in tubes, strainers and plate exchangers. Debris can block whole tubes, not just coat them.
How does condenser fouling raise energy use and surge risk?
Condenser fouling raises energy use because the compressor has to push refrigerant to a higher pressure to reject the same heat. It raises surge risk because that higher pressure narrows the compressor's stable operating range.
Higher lift, more power
With a dirty condenser, refrigerant has to condense at a higher temperature to drive heat through the deposit. Higher condensing temperature means higher condensing pressure. The gap between evaporating and condensing pressure is called lift, and compressor power rises with lift.
Trips and surge
If deposits get thick enough, head pressure can exceed the chiller's limits and shut it down. In a centrifugal chiller, high lift at low load can push the compressor into surge, where flow briefly reverses. Surge is covered in Rotating Equipment Part 7.
One hotel's numbers
At the New Orleans Airport Hilton, condenser tube scale caused surge as well as rising wastewater and chemical costs (ACHR News). The article cites a fouling factor of 0.003, about 0.036 inch (0.9 mm) of scale.
For a 500 ton chiller, it put the added energy cost at about $25,300 a year. It predicted that cleaner tubes would improve efficiency from about 0.80 to 0.75 kW per ton. These are that site's figures, not general rules, but they show the scale of the loss.
How does evaporator fouling show up?
Evaporator fouling shows up as a wider gap between the leaving chilled water and the refrigerant. The chiller has to run its refrigerant colder to make the same water temperature.
Colder refrigerant means lower suction pressure, which also raises lift and compressor power. At its worst, a very cold evaporator risks freezing water in the tubes at low load. Low flow can cause the same freeze risk, covered in Part 3.
Evaporators foul more slowly than condensers, because closed chilled water loops are cleaner than open tower water. When an evaporator does foul, the cause is usually poor loop treatment, corrosion debris, or dirt left in after construction or a major repair.
A sudden rise in evaporator approach is less likely to be fouling. It more often means low refrigerant charge, covered in Leaks Part 6, or a flow problem.
Why can biofilm be worse than scale?
Biofilm can be worse than scale because it is a far better insulator. A thin biological layer can resist heat more than the same thickness of mineral scale. It can also shut a chiller down faster than typical scale (water treatment technical bulletin).
Biofilm is mostly water held in a slimy matrix, which is a poor conductor of heat. It is also soft and can be hard to see on a quick tube inspection.
Biofilm also causes harm that scale does not. It shelters bacteria from biocides and creates pockets where corrosion runs fast. In an open tower system, uncontrolled biology is also a health issue, covered in the Moisture and Air sub-series.
The practical lesson is that scale control alone is not enough. A condenser loop needs biological control too, and a sudden jump in approach after a warm spell is worth a check for biology, not just minerals.
What is approach temperature, and why is it the best fouling indicator?
Approach temperature is how close the water gets to the refrigerant temperature. It is the best everyday fouling indicator because it measures heat transfer directly and most chiller panels show it.
Condenser approach
Condenser approach is the refrigerant condensing temperature minus the leaving condenser water temperature. A clean condenser runs a small approach. As deposits build, the refrigerant has to run hotter than the water, and the approach widens.
Evaporator approach
Evaporator approach is the leaving chilled water temperature minus the evaporating refrigerant temperature. It also widens as the evaporator fouls.
How to read it
Rising approach at similar load, over weeks, is the classic early sign of fouling. Compare readings at similar percent load and similar entering water temperature, because approach naturally changes with load.
The best baseline is the chiller's own approach after its last tube cleaning, or at start up. Logging approach on every round, as described in reading the gauges nobody monitors, turns a single number into a trend.
Other causes to rule out
High approach also comes from low water flow, high entering condenser water temperature, non condensable gases such as air in the refrigerant, and low refrigerant charge. A rising approach is a reason to look closer, not proof of fouling by itself.
How do coil and CDU heat exchanger fouling differ?
Coils foul mostly on the air side, while coolant distribution unit (CDU) exchangers foul mostly on the facility water side. Both show up as lost heat transfer, but the evidence is different.
Air side coil fouling
Dust and debris on coil fins raise air pressure drop across the coil and lower heat transfer. The fan works harder, the valve opens wider and more water goes through the coil for the same cooling. That narrows delta T, covered in Part 1.
A dirty coil face is often visible, and a differential pressure gauge across the coil rises as it loads. Thermal imaging of the coil face can show cold and warm patches where airflow is uneven.
CDU heat exchangers
A CDU moves heat from a liquid cooling loop serving racks into the building's facility water. Its plate exchanger has narrow passages, so dirty facility water fouls it fast.
A rising approach between facility water supply and technology loop supply, together with a rising pressure drop across the exchanger, points to fouling. CDU health is covered in Part 8.
What does visible scale on equipment tell you?
Visible scale tells you the water is scale forming, and that the same scale is likely forming where you cannot see it, inside the condenser tubes.
White or tan crust on cooling tower fill, basin walls, valves and drift eliminators is the most common sign. It is easy to catch on routine visual inspection and easy to photograph for comparison.
Scale on the outside of pipes and valves near leaks is a different story. That is dried mineral from a leak, covered in Leaks Part 4.
Scale on tower components should prompt three questions. When were the condenser tubes last inspected, and is water treatment keeping cycles of concentration in range?
The third question is whether the blowdown controller is working. Cooling tower performance is covered in Part 5.
How do you clean fouled tubes, and how do you prove it worked?
Fouled chiller tubes are cleaned mechanically, chemically or both. The proof that it worked is the same approach reading that raised the question, taken again after the cleaning at similar conditions.
Mechanical cleaning
Mechanical cleaning means opening the water boxes and running brushes or projectiles through each tube. It removes soft scale, biofilm and debris. It is the standard annual task on many condensers.
Chemical cleaning
Hard scale that brushes cannot remove may need a chemical descaling by a water treatment specialist. Chemical cleaning needs care, because the wrong chemistry or contact time can attack tube metal. It should always be followed by a flush and inspection.
Online tube cleaning systems
Some plants fit systems that clean tubes while the chiller runs, using brushes or sponge balls that circulate with the water. They slow fouling between shutdowns rather than replacing inspection.
Proving the result
Record condenser and evaporator approach, kW per ton and pressure drop before the work. Record them again after start up, at similar load and entering water temperature. That pair of readings becomes the new baseline.
A cleaning that does not bring approach back near its baseline points somewhere else. The likely suspects are non condensable gases, a refrigerant problem or flow.
Keeping before and after readings with the work order is good evidence for insurers and auditors too. It shows not just that maintenance happened, but that it restored performance, as described in keeping inspection evidence.
What looks like fouling but is not?
Three common conditions raise approach or cut capacity without any deposit. Ruling them out first avoids an unnecessary tube cleaning.
Low condenser water flow
Low flow through the condenser widens the approach and raises head pressure, just like fouling. A low pressure drop across the condenser barrel points to flow, covered in Part 3.
A poorly performing cooling tower
A tower that sends warm water raises condensing pressure, but the condenser approach may stay normal. The problem is the water arriving, not the tubes. That is covered in Part 5.
Refrigerant undercharge
A chiller short of refrigerant shows a wide evaporator approach and low suction pressure. That is a leak, covered in Leaks Part 6.
What does fouling cost?
Fouling costs energy all year and capacity at the worst moments, because it is worst on the hottest, most loaded days.
In an office building
Fouling raises kW per ton and energy bills. On hot afternoons, it causes nuisance high pressure trips just when tenants need cooling most.
In a data center
Fouling cuts chiller capacity and raises surge risk at the moments the plant is most loaded. Fouled CDU exchangers limit heat removal from liquid cooled racks, which can lead to processor throttling. Both erode the margin that redundancy is supposed to provide.
What can a walk past prove, and what needs a follow up test?
A walk past can show that a heat exchanger is losing ground. Proving the deposit type and thickness needs the machine opened or tested.
Directly observable
Approach temperatures on the chiller panel. Visible scale on tower components. High strainer or exchanger pressure drop on gauges.
Strong indicators
Approach rising at similar load over weeks. kW per ton drifting upward. One chiller worse than its identical neighbor.
Suspected, needs follow up
The deposit type and thickness. That needs tube inspection, eddy current testing or a deposit sample sent to a lab.
No single reading is conclusive, which is why one sensor is never enough. Approach, pressure drop, power and visual evidence together make the case.
Walk up checklist for fouling
- Condenser and evaporator approach on every chiller panel.
- Entering and leaving water temperatures and percent load for each chiller.
- Pressure drop gauges across heat exchangers and strainers.
- Scale on tower fill, basin walls and valves.
- Last tube cleaning date for each chiller.
How FacilityOps detects it
Coming Soon
Questions to ask about your own equipment
- 1. What is each chiller's condenser approach today compared with when it was new?
- 2. When were the condenser tubes last brushed or inspected?
- 3. How is biological growth controlled in the condenser water?
- 4. Do you trend kW per ton for each chiller?
- 5. How does CDU approach compare with the commissioning value?
Frequently asked questions about heat exchanger fouling
What is a fouling factor?
A fouling factor is the extra thermal resistance a deposit adds to a heat transfer surface, given in hr·ft²·°F/Btu. AHRI 550/590 rates chillers with allowances of 0.0001 for evaporators and 0.00025 for condensers.
What is chiller approach temperature?
Condenser approach is the refrigerant condensing temperature minus leaving condenser water temperature. Evaporator approach is leaving chilled water temperature minus evaporating refrigerant temperature. Both widen as tubes foul.
How does condenser fouling affect chiller efficiency?
Deposits force refrigerant to condense at a higher temperature and pressure. That raises lift and compressor power, so kW per ton rises. In one hotel, cleaner tubes were predicted to improve efficiency from about 0.80 to 0.75 kW per ton.
Can fouling cause chiller surge?
Yes. Heavy condenser fouling raises head pressure and lift. In a centrifugal chiller, that can push the compressor into surge, especially at low load, as happened at the New Orleans Airport Hilton.
Is biofilm worse than scale?
It can be. A thin biofilm can insulate more than the same thickness of mineral scale, and it can shut a chiller down faster. It also shelters bacteria and speeds corrosion.
How often should chiller tubes be cleaned?
It depends on water quality and the approach trend. Many sites clean condenser tubes once a year. The approach trend against the last cleaning is the best guide to whether that is often enough.
What is a normal condenser approach?
It depends on the machine. Use the chiller's own approach at start up or after its last cleaning as the baseline. A steady rise from that value at similar load is the warning sign.
What causes high evaporator approach?
Evaporator fouling, low refrigerant charge, low chilled water flow and sensor errors. A sudden rise is more likely charge or flow; a slow rise over months is more likely fouling.
How do you know if a heat exchanger is fouled?
Look for rising approach at similar load, rising pressure drop across the exchanger and rising energy use. Confirm with tube inspection, eddy current testing or a deposit sample.
Sources
Everything in this piece, as a checklist you can take on your rounds
Turn the key points from this article into a practical inspection checklist.