VOC and Gas Sensing for Data Centers, and the Sensor Family That Smells Trouble First

Updated · FacilityOps researchers and writers

VOC sensing is the measurement of volatile organic compounds, the carbon based vapors that evaporate easily at room temperature, and it is not one sensor. It is a family of sensing methods, each built on different physics, each blind to things the others see.

In a data center that family has a serious job. Overheating insulation, a stressed lithium ion cell, a leaking chiller and a running generator all change the air before they change anything you can see, and the right sensor in the right place reads that change first.

This guide walks through every key member of the family, what each one sees and misses, which gas comes from which piece of equipment, and how robots, drones and stationary hubs carry the right sensors to the right spot.

Key takeaways

  • VOC sensing is a family of technologies: metal oxide, photoionization, electrochemical, infrared and photoacoustic, catalytic and thermal conductivity sensors, plus corrosion monitors for the slow damage gases do.
  • No single sensor sees everything. Photoionization and infrared sensors cannot see hydrogen, and a broad metal oxide sensor cannot tell you which gas it found.
  • In 2024 Sandia National Laboratories research, VOC sensors gave earlier warning of lithium ion cell failure than hydrogen sensors.
  • Where you sample matters as much as what you sample with: hydrogen rises, while heavy gases such as SF6 and most solvent vapors sink.

What does VOC mean, and what is VOC sensing?

Volatile organic compounds are carbon based chemicals that evaporate readily at room temperature: solvents, fuel vapors, the breakdown products of heated plastics, and the electrolyte inside a lithium ion cell. VOC sensing measures how much of them is in the air.

In practice, data center teams use "VOC and gas sensing" to cover a wider set of targets. Hydrogen, carbon monoxide, refrigerants, sulfur hexafluoride and corrosive sulfur gases are not all VOCs, but they come from the same equipment and they need the same discipline of measuring the air.

That is why the honest answer to "which VOC sensor should a data center use" is a set of them. Each sensing method trades breadth for specificity, or sensitivity for durability, and the art is in matching the method to the gas and the place.


Why does the air warn first?

Most equipment failures in a data center are thermal or chemical before they are visible. Insulation that is starting to cook releases vapors before it chars, and a lithium ion cell that is overcharged or damaged can vent electrolyte vapor before it swells or runs hot.

Research published in 2024 by Sandia National Laboratories compared early warning methods on cells and packs pushed into failure. Rapid impedance measurement gave the longest warning, often before the cell vented, followed by VOC sensors, and then hydrogen sensors.

That ordering is the heart of the case for VOC sensing. Gas is often the first signal that leaves the equipment, which makes the air around it the first place a developing problem can be read.

How much warning does off gas give, and what happens without it?

A lithium ion cell often vents twice. In an overcharge test on a 280 Ah lithium iron phosphate cell, the first vent of solvent vapor came about 13 minutes before thermal runaway. Carbon monoxide, hydrogen and carbon dioxide monitors responded only at runaway (Frank, Sandia ESS forum, 2021, presented by a sensor maker).

A 2025 peer reviewed review reached the same order. Gas signatures appeared before any voltage, current or temperature anomaly. One solvent sensor gave more than 15 minutes of warning (Frontiers in Chemistry, 2025).

Without a reading, gas builds up unseen. In 2019, a 2.16 MWh battery system in Surprise, Arizona went into thermal runaway. When crews opened the door about three hours later, the trapped gas exploded and seriously injured four firefighters (UL FSRI, 2020).

The investigators recommended gas monitoring that responders can read remotely before anyone opens a door (same report).


Metal oxide (MOS) sensors: the broad sniffer

A metal oxide sensor is a tiny heated film, typically run at about 250 to 500°C. Oxygen on its surface holds its resistance at a baseline, and when a reducing gas such as a VOC arrives, the resistance changes in proportion to how much is there.

  • Sees: a broad range of VOCs, often reported as a total VOC index, plus gases such as hydrogen and carbon monoxide.
  • Misses: which compound it is. Researchers describe these sensors as having poor selectivity, so a rise means "something changed", not "electrolyte" or "solvent".
  • Watch out for: humidity, which is a major interference, slow drift, and poisoning by silicone vapors.
  • Where it earns its place: as a low cost, always on trend sensor, and in arrays called electronic noses, where several different films and pattern recognition together tell gases apart.

Photoionization detectors (PID): the precise VOC reader

A photoionization detector shines ultraviolet light into a small chamber. Any molecule whose ionization energy is below the lamp's photon energy gives up an electron, and the resulting current tracks the concentration, down to parts per billion on good instruments.

  • Sees: most VOCs, quickly and at very low levels, which makes it the reference tool for solvent and fuel vapor.
  • Misses: hydrogen, carbon monoxide and methane, whose ionization energies sit above common lamps, and the main components of clean air.
  • Watch out for: the lamp choice. In published response data from a PID maker, the common 10.6 eV lamp responded weakly to dimethyl carbonate, a common battery electrolyte solvent (response factor 60), while an 11.7 eV lamp read it far better (1.5) but lasts only months. Ethylene carbonate gave no response at all.
  • Where it earns its place: checking electrolyte or fuel vapor at a specific cabinet or tank, and confirming what a broad sensor flagged.

Electrochemical sensors: one gas, one cell

An electrochemical sensor is a small fuel cell built for one target. The gas reacts at an electrode and produces a current proportional to its concentration, which makes it the workhorse for toxic gases at parts per million.

  • Sees: specific gases such as carbon monoxide, hydrogen, hydrogen sulfide, sulfur dioxide, nitrogen dioxide and hydrogen fluoride, each with its own cell.
  • Misses: anything it was not built for. It is a specialist, not a sniffer.
  • Watch out for: a working life typically around two years, and cross sensitivity, where a different gas nudges the reading.
  • Where it earns its place: carbon monoxide near generators and overheating equipment, hydrogen in battery rooms, and hydrogen fluoride after a lithium ion battery fire, which a 2017 study measured at 20 to 200 mg per watt hour of battery capacity.

Infrared (NDIR) and photoacoustic sensors: the stable specialists

Infrared sensors measure how much light a gas absorbs at its own fingerprint wavelength. Photoacoustic sensors use the same absorption but listen for the tiny pressure pulse it creates, which pushes sensitivity lower.

  • Sees: carbon dioxide, refrigerants, hydrocarbons and sulfur hexafluoride, with high specificity.
  • Misses: hydrogen, which has no infrared fingerprint to absorb.
  • Watch out for: higher cost and size than a metal oxide film, though they do not suffer the poisoning that catalytic sensors do.
  • Where it earns its place: refrigerant leaks in chiller plants, SF6 around medium voltage switchgear, and carbon dioxide as a check on ventilation and occupancy.

Catalytic and thermal conductivity sensors: the flammability gauges

A catalytic bead sensor burns a trace of combustible gas on a heated bead and measures the heat, reporting the result as a percentage of the gas's lower flammable limit. A thermal conductivity sensor measures how well the air carries heat, which changes sharply when a light gas such as hydrogen is present.

  • Sees: how close a space is to a flammable mixture, including hydrogen, methane and fuel vapor.
  • Misses: low level VOCs and toxic gases, which sit far below its range.
  • Watch out for: catalytic beads need oxygen and can be poisoned or inhibited by some compounds, so they need regular bump tests.
  • Where it earns its place: battery and fuel rooms, where the question is not "what is in the air" but "how close is it to burning".

Corrosion monitors: reading what the gas has already done

Some gases do their damage slowly. Sulfur bearing gases such as hydrogen sulfide and sulfur dioxide are the most common cause of hardware corrosion in data centers, and chlorine and nitrogen dioxide make them worse.

Corrosion monitors measure the result instead of the gas: how fast a thin film of copper or silver corrodes. ASHRAE Technical Committee 9.9 guidance asks data centers to stay at severity level G1 of ISA-71.04, with copper corroding at less than 300 angstroms a month and a similarly tight limit for silver.

It is the slowest member of the family and the most direct. It tells you whether the air is quietly eating the copper traces and silver solder in your servers.


Which gas comes from which equipment?

Every gas in a data center has an address. Knowing it tells you which sensor to carry and where to point it.

  • Lithium ion UPS batteries: electrolyte solvent vapors first, then hydrogen, carbon monoxide and carbon dioxide as a cell degrades, and hydrogen fluoride if it burns.
  • Lead acid batteries: hydrogen during charging, most of all when overcharged. Hydrogen is flammable from about 4 percent in air.
  • Chillers and cooling units: refrigerant. ASHRAE Standard 15 requires refrigerant detection in machinery rooms, and for the lower flammability A2L refrigerants now entering central plants, detection that shuts equipment down at 25 percent of the lower flammability limit.
  • Medium voltage switchgear: sulfur hexafluoride, an odorless gas that displaces oxygen, settles in low areas, and is the most potent greenhouse gas the IPCC has evaluated. Arcing breaks it into toxic byproducts.
  • Generators and fuel: carbon monoxide from exhaust leaks and fuel vapor around day tanks and fill points.
  • Cables, connections and power supplies: VOCs from heated insulation, often well before smoke.
  • The building itself: solvent vapors from paint, adhesives and sealants after construction, and sulfur gases drawn in from outside air.

Why do height and airflow decide where to sample?

Gases do not mix evenly. Hydrogen is about one fourteenth the density of air and collects at ceilings, while sulfur hexafluoride and most solvent vapors are heavier than air and pool low, around cabinet bases, cable trenches and pits.

Airflow then reshapes everything. A data hall's cooling dilutes a leak quickly and carries it toward the return, so a sensor in the wrong place sees a faint, mixed signal or nothing at all.

The practical rule is simple: sample hydrogen high, heavy gases low, and everything as close to the source as you safely can.


Why is one sensor never enough?

Each member of the family answers a different question, and real failures cross several of them. The combination is what turns a reading into a diagnosis.

  • A broad VOC rise with a hot terminal and carbon monoxide points to insulation overheating.
  • A VOC rise at one battery cabinet with no heat yet, confirmed as electrolyte vapor, points to a cell that needs attention now.
  • A VOC rise across a whole room, with no heat, the week after painting, points to construction off gassing.
  • A refrigerant reading creeping up at one chiller, with suction pressure drifting on its gauge, points to a slow leak before cooling is affected.
  • Hydrogen near the ceiling of a lead acid battery room with a charger in boost mode points to a ventilation or charging problem.

How do robots, drones and stationary hubs carry the family?

A fixed gas detector watches one point forever. A robot carries the family to many points, on a schedule, in the same pose each time, so each checkpoint builds its own baseline and a rise against that baseline stands out long before any alarm level.

A robot can also take sensors to the height each gas favors: high for hydrogen in a battery room, low beside cabinet bases and switchgear for heavy gases. Every reading arrives with the thermal image, the photo and the gauge readings from the same moment.

Drones extend the reach to rooftop chillers, cooling towers, generator yards and high bay ceilings where hydrogen collects, though rotor downwash disturbs the air they measure, which we explain in our guide to smoke sensing. Stationary hubs sit where constant watching matters most, such as a flagged battery cabinet or a chiller with a history of leaks.


Where else does VOC and gas sensing matter?

The same family protects any facility where energy, chemistry and continuous operation meet.

  • Battery energy storage sites and UPS rooms, where off gas is the earliest outside sign of a failing cell.
  • Telecommunications central offices, full of batteries and rectifiers.
  • Hospitals, where generator exhaust, medical gases and battery rooms share one building.
  • Semiconductor fabs, where toxic process gases and corrosive contamination are both constant concerns.
  • Utility substations, with SF6 switchgear and battery banks in unmanned buildings.
  • Cold storage and food plants, with large refrigerant charges.

The 10 minute gas risk walk

Anyone can run this check. Walk the same route each time and note what you see, hear and smell at the same points.

  1. 1. Battery rooms: ventilation running, no odor, no swollen or weeping cases, battery monitor clear
  2. 2. Battery chargers: no unexpected boost or equalize mode, no warning lights
  3. 3. Gas detection panels: no alarm or fault standing, last calibration date current
  4. 4. Chiller and cooling plant: refrigerant detector clear, no oily residue at joints, pressures on the gauges where they normally sit
  5. 5. Switchgear rooms: SF6 pressure gauges in range, no alarm
  6. 6. Generator room: no exhaust smell, no fuel odor around the day tank and fill point
  7. 7. Electrical rooms: no hot plastic smell near panels, PDUs and busway taps
  8. 8. New work: paint, adhesive or sealant work noted, area ventilated
  9. 9. The record: date, time, a gas reading and a photo at each point, with high and low samples where gases settle differently

Anything that smells or looks wrong goes to the person who owns that space. Done every week, this turns gas risk from a nose into a record.


How FacilityOps uses VOC and gas sensing

A FacilityOps robot walks the route through UPS and battery rooms, electrical rooms, chiller plants and generator rooms on a schedule, carrying the FacilityOps sensor hub. Its VOC and gas sensors, with hydrogen and refrigerant sensing fitted where a room calls for them, read the air at fixed checkpoints, and every reading is tied to the place, the time and the asset in front of it.

What the robot does at every checkpoint

  1. 1. Navigates to each sampling point using 3D lidar and simultaneous localization and mapping (SLAM), and samples where each gas collects: low for heavy electrolyte vapor, high for hydrogen.
  2. 2. Confirms the battery cabinet, chiller, panel or tank in front of it is the asset the route names before recording.
  3. 3. Holds the same position and angle as every previous pass and stores that pose with the reading, so this week's number can be laid beside last week's.
  4. 4. Samples at the height each gas favors for that checkpoint: high for hydrogen, low near cabinet bases and switchgear.
  5. 5. Captures thermal, visual, acoustic and gauge readings at the same pose and moment, so every gas reading arrives with context.
  6. 6. Marks a reading invalid when the sensor has not stabilized or a fan is pushing the sample away, instead of logging a number that means nothing.

Six things VOC and gas sensing on the route makes possible

  • Cabinet by cabinet comparison: on a battery string, each cabinet's reading is compared with its own baseline and with its neighbors, so one cabinet drifting away from the rest stands out while the room as a whole looks normal.
  • Gas plus heat plus picture: a VOC rise is reviewed beside the thermal image of the same terminals and the photo of the same cases, so swelling, heat and off gassing are judged together.
  • Slow refrigerant leaks: refrigerant readings at each unit, beside the pressures the camera reads off its gauges, show a leak building over weeks before charge loss affects cooling.
  • Fuel and exhaust watch: fuel vapor near day tanks and carbon monoxide in generator rooms are checked on every pass, not only on test day.
  • Hot insulation before smoke: a VOC rise near a panel or PDU, paired with a warm connection in the thermal image, points to the spot before it smokes.
  • Construction and commissioning: off gassing from new paint, adhesives and sealants is tracked room by room until the air settles, before equipment goes live.

How robots, drones and stationary hubs share the job

  • Robots cover the floors: battery strings, electrical rooms, plant rooms and generator rooms, on a schedule.
  • Drones cover what is high or outside: rooftop chillers, cooling towers, generator yards and high ceilings.
  • Stationary hubs watch what needs constant attention: a flagged battery cabinet, a chiller with a leak history or a room a robot cannot enter. An alert from the hub sends the robot to look.

What happens when something changes

  • The FacilityOps platform compares every reading with the same checkpoint's last passes, so a change since the last round stands out.
  • A VOC rise at one cabinet goes to the battery or UPS owner on duty, with that cabinet's gas trend, thermal image and photo together, and is tracked as a work order in FacilityOps or in your existing system.
  • The next pass confirms the reading is back at its baseline, so the record shows the fix as well as the finding.

An illustrative record entry

UPS room 2, battery cabinet B5 · Run 41, checkpoint 9, low sample · Captured from the same pose as run 40

Change found: VOC reading about three times this checkpoint's baseline, with cabinets B4 and B6 unchanged. Hydrogen unchanged. Thermal shows module 4 at 2°C above the modules beside it. No case swelling in the photo.

Routed to: battery technician and facilities manager within the hour, work order opened. Closed: run 43 shows B5 back to baseline after module 4 was isolated and replaced.

Fixed checkpoint rounds are already in daily use: a FacilityOps robot has run them at the CRSC Data Center, powered by Solutions IS, in Houston, since July 28, 2026.

The off gas warning: a timeline from one test cell

Data from an overcharged 280 Ah LFP cell, presented at the 2021 Energy Storage Safety and Reliability Forum by a maker of off gas sensors:

  • 0 seconds: overcharge begins.
  • 810 seconds: first vent. The cell releases 0.5 to 3.0 liters of mostly electrolyte solvent vapor. A VOC or off gas sensor sees it; carbon monoxide, hydrogen, CO2 and LEL sensors do not respond.
  • 810 to 1,575 seconds: about 12.75 minutes of warning. In DNV GL tests of one off gas sensor, stopping the charge in this window prevented runaway.
  • 1,575 seconds: thermal runaway. Gas output jumps by one to two orders of magnitude, and only now do the hydrogen and CO sensors respond.
  • Hours later: the room is still the hazard. At McMicken in 2019, the container exploded about three hours after runaway began, when a door was opened onto unventilated gas.

The window that matters is the first one, and only a sensor tuned for electrolyte vapor sees it open. That is why a FacilityOps round samples low at every cabinet for VOCs, not only high for hydrogen.

Coming next: parking beside a cabinet that shows a first vent signature and sampling it continuously until a person confirms the charge is stopped, so the whole warning window is watched.

What the evidence says

  • In DNV GL testing, an off gas sensor gave 6.4 minutes of warning before thermal runaway, and in a Sandia led study hydrogen was detected only at runaway, Honeywell reports.
  • DNV GL's battery testing for Con Edison and NYSERDA found the explosion hazard lies in the gases a battery may generate, observed repeated gas flashovers, and named carbon monoxide the primary signature, in its final report.
  • At the McMicken site in Arizona in April 2019, thermal runaway began about 4:54 p.m. and the explosion came shortly after 8:00 p.m., IEEE Spectrum reported.
  • The UL report on McMicken listed the absence of flammable gas detection among the contributing factors, as Honeywell summarizes.

A fixed detector knows one point. A robot carrying the whole family knows which cabinet, which gas, how high, and whether it is getting worse.


What won't the robot do?

The FacilityOps robot is not a listed gas detection system, and it does not replace the fixed detection, ventilation controls or shutdowns that codes require in battery rooms, machinery rooms and fuel rooms. It sends no alarm to a fire or gas panel and triggers no ventilation or shutdown.

It does not enter a space that is in alarm, and it does not replace calibrated instruments carried by qualified people. It records conditions, people act on them, and the authority having jurisdiction decides what protection a facility needs.


Five questions to ask about the air in your facility

If you cannot answer these, the first warning from a failing cell may reach nobody.

  1. 1. Which gases can each of your critical rooms produce, and which sensor is watching for each one?
  2. 2. Are your hydrogen sensors high and your heavy gas sensors low, and when was each last calibrated?
  3. 3. Can you show the VOC trend at each battery cabinet for the last three months?
  4. 4. How would you know about a slow refrigerant leak before it showed up as a cooling problem?
  5. 5. After the last construction or refit, how long did the air take to settle, and who checked?

VOC and gas sensing questions we hear most

What is a VOC sensor?

VOC sensor is a name for a family of technologies that measure volatile organic compounds in air. The main ones are metal oxide and photoionization sensors, with electrochemical, infrared, catalytic and thermal conductivity sensors covering the other gases a data center produces.

Is there one sensor that detects every gas?

No. Photoionization and infrared sensors cannot see hydrogen, metal oxide sensors cannot tell which gas they found, and electrochemical cells see only their target gas. Critical rooms need a combination chosen for the gases they can produce.

What gas does a lithium ion battery release before failing?

A stressed lithium ion cell can vent electrolyte solvent vapors first, then hydrogen, carbon monoxide and carbon dioxide as it degrades, and hydrogen fluoride if it burns. Sandia research found VOC sensors warned earlier than hydrogen sensors.

Can a PID detect lithium ion battery electrolyte?

It depends on the lamp. Published response data shows the common 10.6 eV lamp reads dimethyl carbonate weakly, while an 11.7 eV lamp reads it well but has a much shorter life, and ethylene carbonate does not register at all.

Where should hydrogen sensors be mounted in a battery room?

High. Hydrogen is far lighter than air and collects at the ceiling, so sensors and sampling points belong near the highest points of the room, while heavy gases are sampled low.

Do data centers need refrigerant detection?

ASHRAE Standard 15 requires refrigerant detection in machinery rooms, and A2L refrigerants require detection that shuts equipment down at 25 percent of the lower flammability limit. The authority having jurisdiction confirms what applies.

What gases cause corrosion in data centers?

Sulfur bearing gases such as hydrogen sulfide and sulfur dioxide are the most common, made worse by chlorine and nitrogen dioxide. ASHRAE TC 9.9 guidance targets ISA-71.04 severity level G1, with copper corrosion below 300 angstroms a month.

What is an electronic nose?

An electronic nose is an array of broad metal oxide or similar sensors with different responses, read together by pattern recognition software. The combined pattern can tell gases apart even though each sensor alone cannot.

Can a robot detect gas leaks?

Yes. A robot carrying VOC and gas sensors can sample at fixed checkpoints and at the right height on every pass, compare each reading with that spot's baseline, and pair it with thermal and visual evidence. Listed fixed detection stays in charge of alarms and shutdowns.

How does FacilityOps use VOC and gas sensing?

A FacilityOps robot carries the FacilityOps sensor hub on a scheduled route, samples VOC and gas at fixed checkpoints and the right heights, pairs each reading with thermal, visual and gauge readings, and turns every change into a work order. Drones and stationary hubs extend the same record to high places and to equipment that needs constant watching.

How much warning does off gas detection give before thermal runaway?

Off gas detection typically gives several minutes of warning. In DNV GL tests one off gas sensor signaled 6.4 minutes before thermal runaway, and cutting the charge at that signal stopped runaway in the tested cell. In a separate Sandia led study, hydrogen showed up only at runaway. A FacilityOps robot round helps by taking dated gas and thermal readings along battery strings between fixed sensor checks.

What does 25 percent of the lower flammable limit mean in a battery room?

It is the ceiling NFPA 855 explosion control sets for flammable gas wherever it could collect. Keeping concentrations below 25 percent of the lower flammable limit leaves a wide margin before the mix can ignite, usually through exhaust ventilation or explosion prevention systems. A FacilityOps robot round helps by recording gas readings and dated photos of exhaust fans, louvers and ceiling pockets on every pass.

Why can a battery room explode hours after a battery fails?

Flammable gas keeps building in a closed space after a cell fails, and it only needs air and a spark. At the 2019 McMicken site, thermal runaway started near 4:54 p.m. and the container exploded shortly after 8:00 p.m., when a door was opened onto unventilated gas. A FacilityOps robot round helps by keeping dated gas readings that show whether a room has been venting normally.


If you want to see how a gas reading, a thermal image and a fix are recorded together, we can send you a sample inspection record.