Biofilm, Algae and Legionella in Building Water Systems: What a Visual Check Can and Cannot Tell You

Legionella is a waterborne bacterium that grows in warm building water systems such as cooling towers. A visual check can show poor biological control, but never whether Legionella is present.

In the summer of 2025, a Legionnaires' disease outbreak in Central Harlem was traced to 12 cooling towers on 10 buildings, including Harlem Hospital. By August 22, New York City health officials had linked 113 cases and six deaths to the cluster (Contagion Live).

It was the city's most serious outbreak since 2015, when a single Bronx cooling tower was linked to 16 deaths. Both began with the same thing: water systems where bacteria were allowed to grow.

Key takeaways

  • Legionella grows best at about 77°F to 113°F (25°C to 45°C), the normal operating range of most comfort cooling towers.
  • The CDC frames four growth factors: sediment and biofilm, temperature, water age and disinfectant residual. Towers cannot avoid the temperature, so the other three must be controlled harder.
  • ASHRAE Standard 188 expects a documented water management program for buildings with cooling towers and other at risk systems.
  • Algae, slime and empty chemical tanks show biological control is failing. Only a laboratory water test can confirm or rule out Legionella.

What is Legionella, and why do cooling towers matter?

Legionella is a group of bacteria that live in water. When people breathe in fine droplets of contaminated water, the bacteria can cause Legionnaires' disease, a serious form of pneumonia, or a milder illness called Pontiac fever.

Cooling towers matter because they make exactly the kind of fine mist that carries bacteria. Drift from a tower can travel across a neighborhood, which is why tower outbreaks can affect people who never entered the building.

The Harlem outbreak

In 2025, investigators identified 12 cooling towers at 10 buildings in Central Harlem, including Harlem Hospital (ABC7). All 12 were remediated. As of August 22, 2025, health officials linked 113 cases and six deaths to the cluster.

The earlier New York City outbreak, in 2015, was linked to a single Bronx cooling tower and 16 deaths (Gothamist). After it, the city introduced cooling tower registration and inspection rules.

Cooling tower performance is covered in Cooling Plant Performance Part 5. This post is about the water inside them.


What conditions let Legionella grow?

Legionella grows best in warm water, roughly 77°F to 113°F (25°C to 45°C) (NIH Office of Research Facilities). That range overlaps the normal operating range of most comfort cooling towers.

The four growth factors

The Centers for Disease Control and Prevention (CDC) frames four factors that work together (summary of CDC guidance).

  • Sediment and biofilm, which shelter and feed bacteria.
  • Temperature in the growth range.
  • Water age, meaning how long water sits still.
  • Disinfectant residual, meaning how much biocide is left in the water.

A cooling tower cannot run outside the growth temperature range, because that is the range it works in. So the other three factors must be controlled harder: keep the system clean, keep water moving, and keep disinfectant at the right level.

CDC investigations have found that almost all Legionella outbreaks came from problems that better water management could have prevented (PHCP Pros). That is the hopeful part: most of the risk is in things people can see and fix.


What is biofilm, and why does it protect bacteria?

Biofilm is a slimy layer of microbes and the sticky material they produce, growing on any wetted surface. It forms in tower fill, basins, pipes, drain pans and heat exchanger tubes.

Why it matters

Biofilm shelters bacteria from disinfectant. Biocide in the water may kill free floating bacteria while those inside the slime survive. It also feeds bacteria with trapped nutrients and sediment.

Biofilm sheds. Pieces break off and release bacteria back into the water, so a system can test clean one week and not the next.

The energy side

Biofilm also insulates heat exchanger tubes, often more than the same thickness of scale. A slimed condenser runs a wider approach and uses more energy. This is covered in Cooling Plant Performance Part 2.

So biofilm is both a health risk and an efficiency loss. Controlling it pays twice.


What do ASHRAE Standard 188 and the CDC expect from building owners?

ANSI/ASHRAE Standard 188, Legionellosis: Risk Management for Building Water Systems, expects buildings with cooling towers and other at risk systems to have a documented water management program. ASHRAE is the American Society of Heating, Refrigerating and Air Conditioning Engineers.

The CDC publishes a water management program toolkit that walks owners through building one. Many cities and states also have their own cooling tower rules, including registration, regular inspection and testing.

What a water management program covers

  • A team responsible for the program.
  • A description of the building's water systems and where risk sits.
  • Control points, limits and how they are checked.
  • Actions to take when readings go out of range.
  • Records showing the program is followed and reviewed.

The records are what count. A program that exists only as a binder on a shelf protects no one. Inspection rounds that note tower condition, chemical levels and alarms are part of the evidence.


What does visible algae, slime or sludge tell you?

Visible growth tells you biological control is poor. It does not tell you whether Legionella is present.

What to look for in towers

  • Green algae on decks, louvers and distribution basins exposed to sunlight.
  • Brown or black slime on fill faces and basin walls.
  • Sludge and sediment in the basin.
  • Foam on the water surface, which can point to organic load or treatment problems.

Algae needs light, so it shows first where sun reaches wet surfaces. Slime grows in the dark too, inside fill and on basin walls below the waterline.

Routine visual inspection of the same views, photographed each round, shows when growth starts and whether treatment changes are working. A tower that looks clean in photos and fails a lab test needs its program reviewed. One that looks slimed and passes a test is still a warning.


Where else does biological growth hide in a mechanical room?

Cooling towers get the attention, but growth hides in many other places that hold warm, still water.

  • Air handling unit (AHU) drain pans and coils, covered in Part 4.
  • Mold on walls and ceilings near condensation, covered in Part 1.
  • Dead legs and rarely used branches, where water sits for weeks.
  • Eyewash stations and emergency showers that are not flushed.
  • Humidifiers, especially those that hold standing water.
  • Decorative fountains and water features.
  • Hot water systems run too cool to control growth.

Domestic hot water deserves its own mention. Water heaters and loops held too cool to save energy can sit in the growth range for hours. Rarely used fixtures let water stagnate in the pipe.

Dead legs are the most overlooked. A capped branch left after a renovation holds still water at room temperature, which is ideal for growth and can seed the rest of the system.

A water management program should list every one of these places, not just the towers.


What does a water treatment program control?

A cooling tower water treatment program controls three things at once: scale, corrosion and biology. They are linked, so a failure in one usually affects the others.

Scale

Towers evaporate water and leave minerals behind. Blowdown bleeds off concentrated water, and scale inhibitors keep minerals in solution. Scale gives biofilm a rough surface to cling to.

Corrosion

Corrosion inhibitors protect steel and copper in the loop. Corrosion products feed sediment, which shelters bacteria.

Biology

Biocides, often an oxidizing biocide fed continuously and a second biocide fed in slugs, keep microbial growth down. The disinfectant residual is the number that shows whether enough is reaching the water.

A controller usually measures conductivity to manage blowdown and an oxidation or disinfectant reading to manage biocide. Its readings, alarms and log are the best daily view of whether the program is working. In HVAC (heating, ventilation and air conditioning) systems, these readings are often the only continuous water data a site has.


How do water treatment systems fail?

Water treatment systems fail quietly. The tower keeps running and the water looks fine while the chemistry drifts. These are the common failures.

  • Chemical feed pumps that have lost prime or stopped.
  • Empty or low chemical tanks.
  • Leaking dosing lines or injection points.
  • Controllers showing alarms, or with failed probes reading wrong.
  • Blowdown valves stuck open, wasting water and chemicals, or stuck closed, letting minerals concentrate.

Any of these lets disinfectant levels fall or scale and corrosion rise. A tower can go from controlled to uncontrolled in days if a biocide pump stops in hot weather.

Most of these failures are visible on a walk past. Look at the tank level, whether the pump is stroking, the controller screen and the injection point. Reading them on every round is cheap.


What do chemical leaks and low chemical tanks mean?

Chemical leaks and low tanks mean two things: the treatment is probably not being delivered, and there is a safety hazard in the room.

Treatment

A low tank or a leak means less chemical reaches the water than the program assumes. Check the controller readings and the last test results before assuming the water is still in range.

Safety

Treatment chemicals include biocides, acids and corrosion inhibitors. Some are corrosive, some react with each other, and some give off harmful vapors. Leaks and spills need secondary containment, labeling and the right protective equipment.

Look for crystallized residue around fittings, stained containment trays, corroded metal nearby and liquid in containment. Gas and vapor sensing near chemical storage is covered in VOC and gas sensing.


What should happen when a tower sits idle or restarts?

Idle towers and loops are a special risk because water age is one of the four growth factors. Water that sits still in a warm basin or pipe loses its disinfectant and gives biofilm time to grow.

While idle

Either drain and dry the tower, or keep water circulating and treated on a schedule. A tower left half full and untreated for weeks is the worst of both.

Before restart

Most water management programs call for cleaning and disinfecting a tower that has been idle before it goes back into service. Check that chemical feed is working and controller readings are in range before the fans run.

Standby towers and cells

Data centers often keep spare tower cells idle for redundancy. Those cells must be treated like any idle system: circulated, treated and rotated into service, not just left full until they are needed in an emergency.

Record when each tower and cell ran, sat idle and restarted. That record is often the first thing an investigator asks for.


What does a good tower inspection round look like?

A good tower round takes a few minutes per tower and covers the same points every time.

  • Photograph the deck, louvers, distribution basins, fill faces and basin from fixed spots.
  • Note algae, slime, sludge, foam and debris.
  • Read the controller: conductivity, disinfectant level, pH and any alarms.
  • Check each chemical tank level and that each feed pump is running.
  • Look at dosing lines, injection points and containment for leaks.
  • Note drift: wet surfaces and mist beyond the tower.
  • Note which cells are running and which are idle.

Drift matters because it carries water, and anything in it, beyond the tower. Damaged drift eliminators raise both the water loss and the health risk. Drift is covered in Cooling Plant Performance Part 5.

Keep the round record with the water management program. Over a season, it shows whether control held through heat waves, shutdowns and contractor changes.


Why can a visual check never confirm or rule out Legionella?

Legionella bacteria are invisible to the eye and do not change how water looks. Water can be crystal clear and carry high counts, or look murky and carry none.

Visible algae and slime show that biological control is poor, but they cannot establish whether Legionella is present or at what concentration. Only laboratory water testing can do that.

What a visual check does well is catch the conditions that let Legionella grow: biofilm, sediment, stagnant water, empty chemical tanks and failed pumps. Fixing those lowers the risk whatever the test result.

So the two work together. Inspection catches drift between tests, and testing confirms what inspection cannot.

A sensible program ties them together. Take a walk past finding such as slime returning, or a biocide pump down for a day. It should trigger an extra test rather than wait for the next scheduled one. A positive test should trigger a closer look at what the rounds missed.


What looks like biological growth but is not?

Three things are often mistaken for biological growth.

Mineral scale

Scale is white or tan, hard and crusty. Biofilm is slimy, often brown or green, and wipes off. Scale is covered in Cooling Plant Performance Part 2.

Corrosion staining

Rust stains are orange to brown and sit on metal surfaces or below them. They are a corrosion finding, not a biological one, though both can occur together.

Normal treatment chemical color

Some treatment chemicals are dyed, and sight tubes or tanks can look colored. Check the product label before calling it contamination.


What does poor biological control cost?

Poor biological control costs health, money and reputation.

In an office building

Public health risk to occupants and the surrounding neighborhood. Legal exposure and enforcement from health authorities. Fouled condensers and higher energy use.

In a data center

Towers serving critical cooling still carry Legionella risk to staff and neighbors. Biofilm fouls condenser tubes and the facility side exchangers of coolant distribution units, covered in Cooling Plant Performance Part 8.


What can a walk past prove, and what needs a follow up test?

A walk past can see poor control and failed treatment. It cannot see Legionella.

Directly observable

Algae, slime and sludge. Empty chemical tanks and leaking dosing lines.

Controller alarms. Stagnant water.

Strong indicators

Treatment controller readings out of range. Chemical pumps not running. A tower or loop idle for long periods.

Suspected, needs follow up

Legionella presence and concentration. That needs a laboratory water test.

Each round's record of tank levels, pump status, controller readings and tower photos becomes part of the water management program's evidence. It shows inspectors that the control points were checked, not just written down.


Walk up checklist for biological growth and water treatment

  • Tower decks, louvers, fill faces and basins for algae, slime and sludge.
  • Chemical tank levels and feed pump status.
  • Dosing lines and containment for leaks and drips.
  • Water treatment controller displays and alarms.
  • AHU drain pans for slime.
  • Idle towers, dead legs and stagnant water.

How FacilityOps detects it

Coming Soon


Questions to ask about your own equipment

  1. 1. Do you have a written water management program that meets ASHRAE 188?
  2. 2. When was each cooling tower last tested for Legionella, and what was the result?
  3. 3. Who checks chemical tank levels and feed pumps, and how often?
  4. 4. Which towers or loops sit idle for long periods?
  5. 5. Are your towers registered and inspected as your city or state requires?

Frequently asked questions about Legionella, biofilm and water treatment

What temperature does Legionella grow at?

Legionella grows best at about 77°F to 113°F (25°C to 45°C), which overlaps the normal operating range of most comfort cooling towers.

Why are cooling towers linked to Legionnaires' disease?

Towers hold warm water in the growth range and release fine mist. If bacteria grow in the water, the mist can carry them to people nearby.

What is ASHRAE Standard 188?

ANSI/ASHRAE Standard 188 covers Legionellosis risk management for building water systems. It expects a documented water management program for buildings with cooling towers and other at risk systems.

What is a water management program?

A written plan that identifies where Legionella could grow in a building and sets control points and limits. It says what to do when limits are missed and keeps records showing it is followed.

Can you see Legionella in a cooling tower?

No. Legionella is invisible and does not change how water looks. Only a laboratory water test can confirm it.

What is biofilm?

Biofilm is a slimy layer of microbes and the material they produce on wetted surfaces. It shelters bacteria from disinfectant and sheds them back into the water.

What does algae in a cooling tower mean?

Algae shows biological control is poor and sunlight is reaching wet surfaces. It does not prove Legionella is present, but it signals conditions that favor growth.

How often should cooling towers be tested for Legionella?

It depends on local rules and the building's water management program. Many jurisdictions set minimum testing schedules for registered towers.

What caused the 2025 Harlem Legionnaires' outbreak?

Health officials linked it to contaminated cooling towers: 12 towers on 10 buildings in Central Harlem, including Harlem Hospital. All were remediated.