Boiler Problems You Can See, Hear and Measure: Combustion, Stack Temperature, Scale, Cycling and Carbon Monoxide
Most boiler problems show up as wasted fuel, poor combustion or unsafe flue gas. Nearly all of them leave evidence you can see, hear or read on a gauge.
The US Department of Energy (DOE) rule of thumb is simple. Boiler efficiency rises about 1% for every 15% cut in excess air, or for every 40°F (22°C) drop in stack gas temperature.
Two numbers on a flue gas analyzer, or a stack thermometer that nobody reads, describe most of a boiler's fuel waste. One more reading, carbon monoxide, describes its most serious hazard.
Key takeaways
- Excess air and stack temperature drive boiler efficiency. DOE puts the gain at about 1% per 15% less excess air or 40°F (22°C) lower stack temperature.
- Stack temperature rising over weeks at the same firing rate points to soot on the fire side or scale on the water side.
- A condensing boiler only condenses when return water is cool enough, roughly below 130°F (54°C). Hot return water turns it into a standard boiler.
- Carbon monoxide is colorless and odorless. It needs a dedicated CO sensor; a general VOC (volatile organic compound) sensor is not a substitute.
Where do boilers sit in commercial buildings and data center campuses?
Boilers in commercial buildings supply heating hot water, domestic hot water, and steam for humidifiers or kitchens. On larger sites, they may also feed campus heating loops.
Data center campuses use boilers mainly for heating office and support space and for humidification. The white space itself rarely needs heat, but the people, the loading dock and the generator rooms often do.
Most commercial boilers burn natural gas. Many are firetube boilers, where hot combustion gas passes through tubes surrounded by water. Newer heating plants often use condensing boilers, which recover extra heat from the water vapor in the flue gas.
Steam systems bring their own faults. Steam traps and steam leaks are covered in Leaks Part 8, and steam hammer in Part 6.
What is excess air, and why does it matter?
Excess air is the air a burner uses beyond the chemically exact amount needed to burn its fuel. Burners need some excess air to burn completely, because fuel and air never mix perfectly.
Too little air
Too little air leaves unburned fuel. The result is soot, smoke and carbon monoxide (CO). It is wasteful and dangerous.
Too much air
Too much air carries heat up the stack. Every extra pound of air is heated from room temperature to stack temperature and thrown away.
What good looks like
DOE says well designed natural gas systems can reach about 10% excess air (DOE Steam Tip Sheet 4). Many burners in the field run far more, because they were set up conservatively or have drifted since their last tuning.
Excess air is measured with a flue gas analyzer, as oxygen or carbon dioxide in the flue. Oxygen trim controls adjust air continuously to hold a target.
What does stack temperature tell you?
Stack temperature tells you how much heat is leaving with the flue gas. The hotter the stack, the more heat the boiler failed to put into the water.
The DOE rule of thumb
Boiler efficiency increases about 1% for each 15% reduction in excess air, or each 40°F (22°C) reduction in stack gas temperature (DOE Steam Tip Sheet 4).
Reading the trend
At a constant firing rate and excess oxygen level, stack temperature rising over time points to fouled heat transfer surfaces. That means soot on the fire side or scale on the water side.
The reading must be compared at the same firing rate. Stack temperature rises naturally as a boiler fires harder. A reading at high fire compared with one at low fire says nothing about fouling.
Many boilers have a stack thermometer that nobody reads. Recording it on every round, with the firing rate, is one of the cheapest efficiency checks in the building, as described in reading the gauges nobody monitors.
How does waterside scale waste fuel?
Scale on the water side of a boiler acts as insulation. Heat from the fire has to cross the scale before it reaches the water, so more of it goes up the stack.
DOE says fuel use can rise by up to 5% in firetube boilers because of scale (DOE Steam Tip Sheet 7). Its table shows about a 2% fuel loss from 1/32 inch (0.8 mm) of normal scale, rising for harder scale types.
Scale also overheats metal. The tube or shell under the scale runs hotter than it should, which can lead to bulging, cracking or tube failure.
Scale comes from hard makeup water and poor water treatment. A boiler that takes a lot of makeup water, because of steam leaks or lost condensate, scales faster. Fouling in chillers follows the same physics, covered in Part 2.
Why does a condensing boiler stop condensing?
A condensing boiler stops condensing when its return water is too warm, or when its flue gas has too much excess air. Either way, it runs like a standard boiler and loses most of the efficiency it was bought for.
Return water temperature
Condensing boilers reach high efficiency only when return water is cool enough to condense water vapor out of the flue gas. One manufacturer's guidance puts the flue gas dew point near 135°F (57°C), so return water must be below about 130°F (54°C) to condense (Deppmann condensing boiler guidance).
Heating loops with low delta T return water too hot, the mirror image of the chilled water problem covered in Part 1. Three way valves, bypasses and oversized valves are the usual causes.
Excess oxygen
Excess oxygen lowers the dew point of the flue gas. In the same guidance, 4% more oxygen lowered the required return temperature to about 113°F (45°C). A condensing boiler with too much excess air needs much colder return water to condense at all.
On a walk past, read the return water temperature. A condensing boiler seeing 150°F (66°C) return water is not condensing, whatever its label says.
What do flame, burner sound and soot tell you?
Flame, burner sound and soot are direct evidence of combustion quality. They can be seen and heard on every round.
Flame
A healthy gas flame is stable and mostly blue, though some burners show other colors by design. Yellow, lazy or lifting flames suggest poor air mixing or the wrong air to fuel ratio. Look through the sight port, and compare with what the manufacturer describes as normal.
Burner sound
Rumbling, pulsing or roaring changes in burner sound indicate unstable combustion. A burner that sounds different from its twin deserves a closer look. Acoustic monitoring turns that difference into a recorded comparison.
Soot and discoloration
Soot around burner openings or flue joints shows incomplete combustion. Heat discoloration around burner assemblies shows overfiring or refractory damage. Thermal imaging of the boiler casing and flue connections can show hot spots from failed refractory or insulation.
Routine visual inspection with the same photo views each round makes slow changes in soot and discoloration easy to see.
Why does a boiler short cycle?
A boiler short cycles when it turns on and off frequently instead of running steadily. The usual causes are an oversized boiler, a hot return, or controls with too narrow a differential.
Each cycle wastes fuel. The burner purges the combustion chamber with air before each start and after each stop, and that air carries heat up the stack. Ignition parts and controls wear with every start.
An oversized boiler reaches its high limit quickly at light load, then shuts down. A hot return, often from bypasses or low heating loop delta T, does the same.
Note how often each boiler cycles during a round. Several starts in a few minutes, outside very mild weather, is a finding.
What do boiler pressure, temperature and water level readings mean?
Pressure, temperature and water level are the boiler's basic vital signs. All three are directly visible.
Pressure and temperature
Readings outside the expected range point to control problems, relief valve risk or a failing component. Compare with the boiler's operating setpoints and with its twin where there is one.
Water level
On steam boilers, the water level sight glass shows the level directly. A low or abnormal level is a serious hazard, because tubes and shell surfaces can overheat and fail without water covering them. A dirty or stained sight glass needs cleaning so the level can be read.
Expansion tanks
On hot water systems, a waterlogged expansion tank lets pressure swing with temperature. It can lift relief valves and bring in fresh makeup water with every cycle. Expansion tanks are covered in Part 6 and Rotating Equipment Part 3.
Why is carbon monoxide a separate hazard that needs its own sensor?
Carbon monoxide is a separate hazard because it is colorless and odorless. People cannot detect it, and general air quality sensors are not built to measure it accurately.
Where it comes from
Flue gas leaks at vent joints, blocked flues and poor combustion release CO. A cracked heat exchanger can leak it into supply air on some equipment. Combustion air openings that are blocked or closed starve burners of air, raising CO and soot.
Exposure limits
The OSHA (Occupational Safety and Health Administration) permissible exposure limit for CO is 50 ppm averaged over 8 hours. Boiler rooms and nearby spaces need dedicated CO detection with alarms.
Why a VOC sensor is not enough
A VOC sensor responds to volatile organic compounds, a broad family of gases. It is not a substitute for a dedicated CO sensor, which is built and calibrated for that one gas.
CO also matters for occupants beyond the boiler room. Indoor air quality monitoring in tenant space is covered in indoor air quality monitoring for office buildings.
How do you find gas leaks and blocked combustion air?
Natural gas leaks at fittings and valves can be found by gas sensing. For pressurized leaks, airborne ultrasound picks up the hiss of escaping gas even in a noisy plant room.
Natural gas is odorized, so a smell of gas is always a finding. A leak too small to smell can still be found with a gas detector moved slowly along fittings, regulators and valve trains.
Combustion air openings must stay clear. Louvers blocked by storage, closed dampers, or openings covered in winter to keep the room warm all starve burners. The result is poor combustion, soot and rising CO.
Look at every combustion air opening on every round. Note what is stored near it. A boiler room that has quietly become a storage room is a common finding.
What safety controls should be visible and working?
Boilers carry several safety controls that should be present, in good condition and tested on schedule.
- Low water cutoffs, which shut the burner down if water level drops.
- High limit controls, which shut it down on high temperature or pressure.
- Flame safeguards, which shut off fuel if the flame is lost.
- Relief valves, which open on excess pressure.
ASME CSD-1 covers controls and safety devices for automatically fired boilers in many jurisdictions. ASME is the American Society of Mechanical Engineers.
On a walk past, check that relief valve discharge pipes are open and unobstructed, that test tags are current, and that nothing is wired around or bypassed. A relief valve that weeps or a low water cutoff that has not been tested is a finding.
How often should combustion be tuned, and what should the record show?
Combustion should be checked with a flue gas analyzer at least once a year, and after any burner repair, fuel change or control replacement. Many jurisdictions and insurers expect a record of it.
A useful tuning record shows oxygen, carbon dioxide, CO and stack temperature at low, medium and high fire, before and after adjustment. It also notes the firing rate and the technician.
Keep that record with the boiler's round readings. Then a stack temperature that creeps up between tunings can be compared with the last tuning at the same firing rate. Inspection evidence that ties readings to the asset is covered in keeping inspection evidence for audits and insurers.
What looks like a boiler problem but is not?
Three normal conditions are often mistaken for faults.
A condensing boiler's plume
A white plume from a condensing boiler vent is water vapor. It is normal and shows the boiler is condensing.
Stack temperature changes with firing rate
Stack temperature rises as firing rate rises. Compare at the same firing rate before concluding that the boiler is fouled.
Short burner cycles in very mild weather
In very mild weather, even a correctly sized boiler may cycle more. Short cycling is a finding when it happens at moderate load.
What do boiler problems cost?
Boiler problems cost fuel every day, equipment when they go far enough, and safety when combustion goes wrong.
In an office building
Wasted fuel from excess air, scale and short cycling. Occupant CO exposure risk from flue leaks or poor combustion. Tube or heat exchanger damage from low water or scale.
On a data center campus
Lost heating to support spaces in winter, and lost humidifier steam. CO risk in shared mechanical rooms where boilers sit near other equipment and the people who maintain it.
What can a walk past prove, and what needs a follow up test?
A walk past can see and hear most boiler problems and read the gauges that describe the rest. Combustion efficiency needs an analyzer.
Directly observable
Flame color and shape through sight ports, soot, water level in the sight glass, pressure and temperature gauges, CO alarm displays and blocked combustion air openings.
Strong indicators
Stack temperature rising over weeks at the same firing rate. Frequent cycling. CO readings near the boiler or flue joints.
Suspected, needs follow up
Combustion efficiency and excess air. That needs a flue gas analysis by a qualified technician.
The strongest record combines all of these. No single sensor is enough for a system where a fuel problem, a water problem and a safety problem can share the same symptom.
Walk up checklist for boilers and combustion
- Stack temperature, boiler pressure and temperature, with the firing rate noted.
- Flame through the sight port.
- Water level sight glass.
- Soot at burner openings and flue joints.
- CO and gas detector displays.
- Combustion air openings confirmed clear.
- Cycling: how often each boiler starts and stops.
- Condensing boilers: return water temperature.
How FacilityOps detects it
Coming Soon
Questions to ask about your own equipment
- 1. When was each boiler's combustion last tuned with a flue gas analyzer?
- 2. What is the stack temperature today compared with right after the last cleaning?
- 3. What return water temperature do your condensing boilers actually see?
- 4. Where are your CO sensors, and when were they last tested?
- 5. When was each low water cutoff last tested?
Frequently asked questions about boilers and combustion
What is excess air in a boiler?
Excess air is the air a burner uses beyond the exact amount needed to burn its fuel. Some is needed for complete combustion. Too much carries heat up the stack, and too little creates soot and carbon monoxide.
What should stack temperature be?
It depends on the boiler and firing rate. The useful test is the trend: at the same firing rate and oxygen level, rising stack temperature points to soot or scale.
How does scale affect boiler efficiency?
Scale insulates the water side, so more heat goes up the stack. DOE says fuel use can rise by up to 5% in firetube boilers, with about 2% from 1/32 inch of normal scale.
Why is my condensing boiler not condensing?
Return water is too warm, or excess air is too high. One manufacturer's guidance says return water must be below about 130°F (54°C) to condense, and lower with more oxygen.
What causes boiler short cycling?
An oversized boiler, a hot return from bypasses or low heating loop delta T, or controls with too narrow a differential. Each cycle wastes fuel in purge air and wears ignition parts.
What does a yellow boiler flame mean?
On most gas burners, a yellow, lazy or lifting flame suggests poor air mixing or the wrong air to fuel ratio. It needs a combustion check, as it can mean soot and carbon monoxide.
What is the OSHA limit for carbon monoxide?
The OSHA permissible exposure limit for carbon monoxide is 50 ppm averaged over an 8 hour work shift.
Can a VOC sensor detect carbon monoxide?
Not reliably. A VOC sensor responds to a broad family of volatile organic compounds. Carbon monoxide needs a dedicated CO sensor built and calibrated for that gas.
What is a low water cutoff?
A safety control that shuts the burner down if boiler water level drops too low. It protects tubes and shell surfaces from overheating and should be tested on schedule.
Sources