CDU and Technology Cooling Loop Health: Approach, Pressure, Filtration and Fluid Quality Beyond the Leak Alarm
CDU health is whether a coolant distribution unit still moves its design heat at design temperatures, pressures and fluid quality. Not leaking is only part of it.
A coolant distribution unit (CDU) is a small chiller plant in a cabinet: pumps, a heat exchanger, a reservoir, filters and controls. It serves racks that can throttle within seconds if flow or temperature slips.
Its leak alarm covers one failure. The panel, the gauges and the sight glass cover the rest, and they warn earlier.
Key takeaways
- A CDU separates the facility water system (FWS) from the technology cooling system (TCS), the closed loop to the cold plates.
- CDU approach is facility water supply temperature minus TCS supply temperature. A rising approach at steady load points to a fouling heat exchanger.
- Filtration is not optional. ASHRAE based guidance recommends filtering the technology loop to 50 micron, with endpoint filtration on the facility side.
- Reservoir level, coolant color and filter differential pressure are visible on a walk past and often warn before an alarm does.
What does a CDU do?
A CDU moves heat from liquid cooled IT equipment into the building's cooling water, while keeping the two fluids apart. It also controls the temperature, pressure and flow of the coolant that reaches the racks.
Inside the cabinet are pumps to circulate coolant, a heat exchanger, usually a brazed or gasketed plate type, a reservoir or expansion tank, filters and a controller. Many CDUs carry two pumps so one can fail without losing flow.
CDUs come in two broad layouts. In row or floor standing units serve several racks. In rack units sit inside a single rack. Both do the same job at different scales.
This post covers performance and condition. Leak points in CDUs, manifolds and quick disconnects are covered in Leaks Part 5 and in liquid cooling leak detection.
What are the facility water system and the technology cooling system?
The facility water system (FWS) is the building side. It carries water from chillers, cooling towers or dry coolers to the CDU and back.
The technology cooling system (TCS) is the rack side. It is a closed loop from the CDU to the cold plates on processors and back. It usually carries treated water or a propylene glycol mix such as PG25, which is 25% propylene glycol.
The CDU's heat exchanger is the border between them. Heat crosses the plates, but the fluids never mix.
That separation matters. Facility water, especially from open cooling towers, can be dirty and full of microbes. The TCS has very fine passages in its cold plates, so it needs much cleaner fluid. Keeping them apart lets each be treated for its own job.
What are ASHRAE's W classes for liquid cooling?
ASHRAE's W classes describe the facility water temperature a liquid cooled system is designed for. ASHRAE is the American Society of Heating, Refrigerating and Air Conditioning Engineers, and its Technical Committee 9.9 publishes them in its guidelines for data processing environments.
In the 5th edition of those guidelines (2021), the classes W1 to W5 were renamed W17, W27, W32, W40 and W45, plus W+ (Upsite Technologies). Each number is the upper limit of facility water supply temperature in °C.
- W17: up to 63°F (17°C).
- W27: up to 81°F (27°C).
- W32: up to 90°F (32°C).
- W40: up to 104°F (40°C).
- W45: up to 113°F (45°C).
- W+: above 113°F (45°C).
Lower classes generally need chillers. Higher classes can run on cooling towers or dry coolers for most or all of the year (Open Compute Project CDU test methodology).
The class matters for inspection because it sets what normal looks like. Facility water at 86°F (30°C) is a problem for a W27 design and routine for a W32 one.
What is CDU approach temperature, and what does it reveal?
CDU approach is the difference between facility water supply temperature and TCS supply temperature. It shows how well the heat exchanger is transferring heat.
A clean exchanger at design flow brings the TCS supply close to the facility supply. As the plates foul, the gap widens. The CDU needs colder facility water, or more of it, to hold the same TCS supply temperature.
How to read it
A rising approach at similar load points to a fouled or scaled heat exchanger, often from dirty facility water. A rising pressure drop across the exchanger on the facility side confirms it. Fouling in general is covered in Part 2.
Compare with the commissioning value at similar load. The commissioning checklist in data center commissioning is the right place to capture that baseline.
The other temperature differences
Each side also has its own supply to return difference. Those show how much heat is being moved, using the same flow times delta T logic as a chiller, covered in Part 1.
What do CDU pressures and pressure drops tell you?
CDU pressures show whether coolant is moving as designed and whether anything is loading up or leaking.
TCS supply and return pressure
These show the pump's work and the loop's resistance. Differential pressure across the racks shows whether the cold plates and manifolds are getting their share.
Filter and exchanger pressure drop
Rising filter differential means filters are loading. Rising exchanger pressure drop means passages are narrowing. Both should be read against their values after the last service.
Static pressure between top ups
A closed loop should hold its pressure. Falling system pressure between top ups suggests a leak somewhere in the TCS, even if no drip is visible. That is covered in Leaks Part 5.
Flow starvation follows the same rules as any loop, covered in Part 3. A pressure drop that falls at the same pump speed means less flow.
How do CDU pumps fail?
CDU pumps fail the same ways as any pump: bearings, seals, cavitation and imbalance.
- Bearing wear, covered in Rotating Equipment Part 1.
- Imbalance and misalignment, covered in Rotating Equipment Part 2.
- Cavitation, often from low reservoir level or air, covered in Rotating Equipment Part 3.
- Seal leaks, covered in Leaks Part 1.
The hidden pump
A CDU with redundant pumps can hide a failing one. The duty pump carries the load, and the standby sits idle until the day it is needed. If the standby has a seized bearing or a failed drive, nobody knows until the duty pump trips.
Running the standby pump on a schedule and recording its readings proves it is ready. Compare its noise, vibration and housing temperature with its partner.
A pump running hotter or noisier than its twin deserves a closer look. Contact ultrasound can pick up early bearing wear before it is audible.
Why do filters matter so much in a technology cooling loop?
Filters matter because cold plates have very fine channels, and particles that would pass harmlessly through a chiller tube can block them. A blocked channel means a hot processor.
The guidance
Guidance based on ASHRAE recommends filtering the technology loop to a maximum particulate size of 50 micron (Lawrence Berkeley National Laboratory).
Facility water from open cooling towers can be dirty. Endpoint filtration on the FWS side of the CDU is therefore necessary, and TCS side filtration is recommended (STACK Infrastructure).
What to watch
Filter differential pressure is the key reading. A slow rise is normal loading. A fast rise means something is shedding particles, such as corrosion, a degraded gasket or debris from recent work.
Note the differential at which each filter was last changed. If filters load faster each time, the source of the particles needs finding, not just more frequent changes.
What do reservoir level and coolant color tell you?
Reservoir level tells you whether coolant is staying in the loop. Coolant color tells you whether it is still healthy.
Reservoir level
A falling reservoir level means coolant is leaving the loop. The leak may be slow, internal or in a place no one can see. Logging level on every round shows the rate.
Coolant color and clarity
Discolored or cloudy coolant in a sight glass suggests corrosion, microbial growth or degraded glycol. Rusty brown points to iron corrosion. Green or blue tints may point to copper. Cloudiness or slime points to biology.
Routine visual inspection of the sight glass, photographed the same way each time, makes color change easy to compare.
Water quality limits
Lawrence Berkeley National Laboratory summarizes the guidance for water based TCS loops. It includes bacteria below 100 CFU/mL (colony forming units per milliliter), chloride below 5 ppm and sulfate below 10 ppm. It also requires a corrosion inhibitor and a biocide (LBNL).
For PG25 loops, follow the Open Compute Project PG25 guidelines, also covered in Leaks Part 5.
What does a CDU's alarm history tell you?
A CDU's alarm history is a record of the moments nobody was watching. Brief pump changeovers, short low flow events, dew point warnings and leak detector trips all leave entries.
Read it on every round, not just after a failure. One low flow alarm is noise. The same alarm every night at the same time points to a sequence, a filter that loads overnight, or a facility water change when chillers stage.
Clear alarms only after recording them. An alarm list that is cleared without notes erases the pattern that would have explained the next failure.
What does air in a technology cooling loop do?
Air in a technology cooling loop causes pump noise and can starve cold plates of coolant.
Air enters when the loop is filled, when racks are connected or disconnected, and when coolant leaves through a leak and is replaced. It collects at high points, including manifolds above racks.
A pump moving air sounds rough and may cavitate. A cold plate with an air pocket runs hot even when the loop's flow and temperatures look fine at the CDU.
Air in hydronic loops is covered in detail in Part 6.
How does a CDU prevent condensation?
A CDU prevents condensation by keeping TCS supply temperature above the room's dew point. Dew point is the temperature at which moisture in the air condenses.
Many CDUs monitor room dew point and raise TCS supply temperature to stay about 2°C (3.6°F) above it (STACK Infrastructure). That keeps cold plates, hoses and fittings dry.
Condensation on IT hardware is a serious risk. Water on boards or connectors can cause shorts and corrosion.
On a walk past, compare room dew point with TCS supply temperature. If they are close, check that the CDU's dew point control is enabled and its humidity sensor is reading correctly. Beads of water on any liquid cooling hardware are a finding.
What should you check at the racks a CDU serves?
The CDU panel reports averages. The racks show where the coolant actually goes. A few checks at the racks complete the picture.
Manifold and hose temperatures
Supply and return manifolds should show a consistent temperature difference rack to rack at similar load. One rack with a much narrower difference may have a blocked branch or a partly closed quick disconnect. Thermal imaging of manifolds and hoses shows this quickly.
Quick disconnects and fittings
Look for seepage, staining and crust at every connection. Leak signs are covered in Leaks Part 5. A fitting that is dry but warmer or colder than its neighbors may be partly open.
Processor temperatures
Where the IT team shares processor temperatures, compare racks on the same loop. Servers on one branch running hotter than the rest, at similar load, point to flow or air in that branch rather than to the CDU itself.
When should the TCS fluid be sampled?
Sample the TCS fluid on a fixed schedule, and also after any event that could change it. Fixed sampling builds the baseline. Event sampling catches the change.
Events worth a sample include a large top up, a new rack connected, a leak repair, and a pump or heat exchanger replacement. So does any change in coolant color or filter loading rate.
Keep each lab result with the CDU's record, next to approach, filter differential and reservoir level from the same week. Patterns appear when they sit side by side: rising chloride before a corrosion problem, or rising bacteria after a warm spell.
What looks like a CDU problem but is not?
Three conditions change CDU readings without a fault.
Higher IT load
More load raises return temperature and approach together. Approach rising alone, at steady load, is the fouling signature.
Warmer facility water during economizer operation
When the plant runs on free cooling, facility water may be warmer by design. TCS supply temperature rises with it, without any fault in the CDU.
A dirty sight glass
A stained or fogged sight glass looks like dirty coolant. Check the glass before ordering a fluid change, and take a sample if in doubt.
What does a degraded CDU cost?
A degraded CDU costs compute before it costs equipment.
In a data center
GPUs (graphics processing units) and CPUs (central processing units) throttle or shut down when TCS supply temperature or flow drifts. Redundancy is lost when one CDU pump, or one CDU in an N+1 set, degrades. N+1 means one spare unit beyond what the load needs.
Fouling slowly removes cooling headroom. The site may look fine at today's load and run short when a new cluster is added.
In office and mixed use buildings
A small liquid cooled room in an office or lab building has the same failure modes. It often has less monitoring, and fewer people who know what normal looks like.
What can a walk past prove, and what needs a follow up test?
A walk past can read nearly everything a CDU reports about itself. Fluid chemistry needs a lab.
Directly observable
CDU panel temperatures and pressures, filter differential gauges, reservoir level, coolant color, alarms and pump status.
Strong indicators
Approach rising at steady load. Filter differential climbing fast. One pump running hotter or noisier than its partner. Falling static pressure between top ups.
Suspected, needs follow up
Fluid chemistry and microbial levels. That needs a lab sample, tested against the water quality limits above or the PG25 guidelines.
As with every system in this series, one sensor is never enough. A CDU's own alarms plus a walk past record of approach, pressures, level and color make a far stronger case.
Walk up checklist for CDU and technology loop health
- FWS supply and return and TCS supply and return temperatures, with approach calculated.
- TCS pressures and filter differential pressure.
- Pump status, noise and housing temperature on both duty and standby pumps.
- Reservoir level and coolant color in the sight glass.
- Room dew point against TCS supply temperature.
- Alarm history on the CDU panel.
How FacilityOps detects it
Coming Soon
Questions to ask about your own equipment
- 1. Which ASHRAE W class is your facility water designed for?
- 2. What was each CDU's approach at commissioning, and what is it now?
- 3. When were CDU filters last changed, and at what differential?
- 4. When was the TCS fluid last sampled, and what did it show?
- 5. When was each CDU's standby pump last run?
Frequently asked questions about CDU and technology cooling loop health
What does a CDU do in a data center?
A coolant distribution unit moves heat from liquid cooled IT equipment into facility water through a heat exchanger. It keeps the two fluids apart and controls coolant temperature, pressure and flow to the racks.
What is the difference between FWS and TCS?
The facility water system (FWS) is the building side, carrying water from chillers or towers to the CDU. The technology cooling system (TCS) is the closed loop from the CDU to the cold plates.
What are ASHRAE W17, W27, W32, W40 and W45?
They are ASHRAE liquid cooling classes, renamed in the 2021 thermal guidelines. Each number is the upper limit of facility water supply temperature in °C, from 17°C (63°F) to 45°C (113°F).
What is CDU approach temperature?
CDU approach is facility water supply temperature minus TCS supply temperature. A rising approach at steady load points to a fouled heat exchanger.
Why is filtration important in liquid cooling?
Cold plates have very fine channels that particles can block. A blocked channel means a hot processor, so both the facility side and the technology loop need filtration.
What filter size is recommended for a technology cooling loop?
Guidance based on ASHRAE recommends filtering the technology loop to a maximum particulate size of 50 micron.
What does discolored coolant mean?
Discolored or cloudy coolant suggests corrosion, microbial growth or degraded glycol. Check the sight glass is clean, then send a sample to a lab.
How does a CDU prevent condensation?
It monitors room dew point and keeps TCS supply temperature about 2°C (3.6°F) above it, so cold plates, hoses and fittings stay dry.
How do you know if a CDU heat exchanger is fouled?
Approach rises at steady load and pressure drop across the exchanger rises on the facility side. Compare both with commissioning values.