Fire Protection · NFPA 25

NFPA 25 for Data Centers: Sprinkler Inspection, Testing and Maintenance, and the Closed Valve Nobody Sees

Updated · FacilityOps researchers and writers

NFPA 25 is the National Fire Protection Association standard for keeping water based fire protection systems ready to work. It covers how sprinklers, valves, gauges, fire pumps and the rest of the system are inspected, tested and maintained, and it puts the responsibility on the building owner.

A sprinkler system almost never fails because the design was wrong. When sprinklers do not operate in a fire, the most common reason in NFPA's research is that the system had been shut off, and the rest of the risk sits in ordinary conditions: a closed valve, a painted head, storage pushed up under the deflectors, a gauge nobody read.

Those conditions appear and clear between scheduled inspections. NFPA 25 is one of the nine compliance surfaces a data center carries, and the weeks in between are where its record is usually thinnest.

Key takeaways

  • NFPA 25 is the Standard for the Inspection, Testing, and Maintenance of Water Based Fire Protection Systems. The 2026 edition is the newest, and jurisdictions enforce the edition they have adopted.
  • The building owner is responsible for the program under Chapter 4. Qualified contractors do the testing and maintenance, while simple visual checks such as valve position and gauge readings can be done by trained site staff.
  • In NFPA's research on fires large enough to activate them, sprinklers operated 92 percent of the time, and the leading reason for failure to operate was a system that had been shut off. Valve position is the single most important thing to watch.
  • A dated record of valves, gauges, sprinklers and clearances from the same points on every pass shows how the system actually stood between inspections. Qualified people and the authority having jurisdiction decide compliance.

What is NFPA 25?

NFPA 25 is the Standard for the Inspection, Testing, and Maintenance of Water Based Fire Protection Systems, published by the National Fire Protection Association (NFPA). Where NFPA 13 tells you how to design and install a sprinkler system, NFPA 25 tells you how to keep it working for the life of the building.

It covers sprinkler systems, standpipes and hose systems, private fire service mains, fire pumps, water storage tanks, water spray systems, foam water systems, and the valves and trim that connect them. Each system type has its own chapter.

The standard becomes enforceable through adoption. The International Fire Code (IFC), in Section 901.6 and Table 901.6.1, points to NFPA 25 for water based systems, and insurers and contracts often require it too.


Which edition of NFPA 25 applies?

NFPA revises the standard on a three year cycle, and the 2026 edition is the newest. A state, city or insurer chooses which edition to enforce, so many data centers still work to the 2023 or 2020 edition.

The 2026 edition adds detail that matters to owners. It requires notification for emergency impairments as well as planned ones, treats piping found to contain ice as an impaired system, and asks for a fuller spare sprinkler list, according to industry summaries of the 2026 changes.

Your authority having jurisdiction, usually the fire marshal, is the authority on which edition applies. The organization of the standard has stayed stable across recent editions, so the chapter references in this guide hold for each of them.


Who is responsible for NFPA 25 compliance?

Chapter 4 puts the program on the property owner or the owner's designated representative. That includes making sure the system is inspected, tested and maintained, that records are kept, and that changes to the building or its use are reviewed for their effect on the system.

The work itself is done by qualified people. Testing and maintenance belong to a licensed fire protection contractor, while trained site staff can handle simple visual tasks such as confirming a control valve is open or reading a gauge.

Records are part of the obligation. Inspection, testing and maintenance records must be kept and made available to the authority having jurisdiction, and they are what an insurer's risk engineer asks to see first.


What is the difference between inspection, testing and maintenance?

NFPA 25 separates three kinds of work. An inspection is a visual check that the system looks right and nothing has changed, a test is a physical operation that proves a component works, and maintenance is the work that keeps it in operating condition.

  • Inspection: looking at valves, gauges, sprinklers, pipe and signage to confirm normal condition. Many of these items come up more often than once a year.
  • Testing: operating something, such as flowing water through a main drain or an inspector's test connection, tripping a dry pipe or preaction valve, or running the fire pump.
  • Maintenance: lubricating, repairing, replacing and adjusting, from exercising valves to replacing a corroded sprinkler.

Inspections are the frequent, visual part of the program, and they are the part most often skipped or done from memory. They are also the part a camera can document.


What does NFPA 25 look for on the sprinklers themselves?

Chapter 5 covers sprinkler systems. Sprinklers are inspected from the floor each year, and the inspector is looking for anything that would stop a head from opening on time or spraying the way it was designed to.

  • Condition: leaks, corrosion, physical damage, paint, and heavy loading of dust or debris. A head with any of these is replaced, not cleaned, apart from light dust.
  • Orientation: a head that has been knocked or twisted out of position.
  • Glass bulbs: a bulb that has lost its liquid.
  • Escutcheons and cover plates: missing or damaged trim, which the 2026 edition addresses directly.
  • Obstructions: anything that blocks the spray pattern, including storage within 18 inches of the deflector, the clearance the IFC also sets in Section 315.3.1.
  • Spare sprinklers: a stocked cabinet with a wrench for each type and a posted list of the sprinklers it holds.

In a data center, the obstruction list grows with every project. A new cable tray, a containment panel, a stacked set of spare servers or a ceiling mounted cabinet can all end up under a head that was clear when the system was accepted.


Why do control valves matter most?

A sprinkler system with a closed valve is a pipe full of water that will not reach the fire. In NFPA's research on fires from 2015 to 2019, the most common reason sprinklers failed to operate was that someone had turned the system off before the fire started.

Chapter 13 covers valves, valve components and trim. A control valve is inspected to confirm it is in its normal position, which for a control valve is open, that it is sealed, locked or electrically supervised, that it is accessible, that it is free of leaks, and that it carries a sign naming the part of the system it controls.

How often a valve is inspected depends on how it is secured. Valves that are only sealed are checked most often, and locked or electrically supervised valves less often, because supervision reports a change on its own.

  • Outside screw and yoke (OS&Y) valves: a visible threaded stem shows the valve is open.
  • Butterfly valves: a position indicator or flag shows open or shut.
  • Post indicator valves: a window in the post reads OPEN or SHUT.
  • Tamper switches: the supervisory switch on the valve reports to the fire alarm panel when the valve moves.

A valve closed for a repair and never reopened is the classic failure. So is a valve that is open but buried behind boxes, unsigned, or missing its seal, which leaves nobody able to confirm its state quickly.


What do the gauges and the fire pump tell you?

Gauges are the system's pulse. On a wet system they show water pressure above and below the alarm valve, and on dry pipe and preaction systems they also show the air or nitrogen pressure that holds the system ready.

A single reading says little. A series says a lot: water pressure that slowly falls points to a supply problem, and air pressure that keeps dropping and recovering points to a leak the compressor is masking.

Where a fire pump is installed, Chapter 8 covers its inspection, testing and maintenance. The controller's indicator lights, the pump room temperature and the condition of the pump and its piping are all visible checks between the pump's own scheduled tests.


How are data center sprinkler systems different?

Most data halls use preaction sprinklers. The pipes stay dry, filled with supervised air or nitrogen, and water enters only after the fire detection system confirms a fire, which protects servers from water released by a damaged head or pipe.

In a single interlock system, the fire detection system opens the preaction valve and water then flows from any sprinkler that has opened. In a double interlock system, the valve opens only when detection and a drop in pipe pressure from an open sprinkler happen together, which further guards against accidental discharge.

The choice is not only the owner's. San Francisco's fire department publishes a clear guide to the two and accepts only single interlock systems for server and computer rooms in buildings that need sprinklers, because a double interlock can delay water too long.

Preaction adds its own things to watch. The supervisory air pressure, the condition of the preaction valve and its trim, the release panel, and the temperature of the valve room all matter, and the 2026 edition now treats piping found to contain ice as impaired.

Many data halls also have clean agent systems, which follow NFPA 2001 rather than NFPA 25. The two often sit side by side, and both depend on someone noticing when a gauge, a valve or a cylinder changes.


What counts as an impairment?

An impairment is any condition where a fire protection system cannot perform as designed. A closed valve, a system drained for work or a fire pump out of service are all impairments, and Chapter 15 sets the procedure for handling them.

That procedure names an impairment coordinator, tags the impaired system, notifies the fire department, the alarm company and the insurer, and decides whether a fire watch or other measures are needed until service is restored. The 2026 edition makes clear that this applies to emergency impairments as well as planned ones.

The hardest impairment to manage is the one nobody knows about. A valve closed without a tag, or left closed after the work is done, is an impairment with no coordinator, no notice and no end date.


Why do sprinkler conditions go unrecorded between inspections?

The contractor sees the system on the day of the visit. On that day the room is usually tidy, the valves are checked, and the gauges are read, because everyone knew the visit was coming.

Between visits, the space is used. A pallet is delivered and left under a head, a new cabinet goes in, a head is painted during a refit, a valve ends up behind a stack of boxes, and the riser room becomes overflow storage.

Each is a five minute fix on the day it happens and a serious finding months later. The question an auditor or an insurer's risk engineer asks is not whether the annual inspection happened, but whether the system stayed in the state it was signed off in.


The 10 minute NFPA 25 walk for owners

Anyone can run this walk with a phone, and none of it touches the system. Walk the same route each time and photograph each point from the same spot.

  1. 1. Control valves: open, sealed, locked or supervised, signed, and reachable without moving anything
  2. 2. Gauges: system, supply and air pressure in their normal range and steady compared with last time
  3. 3. Sprinklers: no paint, corrosion, damage, heavy dust, missing trim or knocked heads
  4. 4. Clearance: nothing stored within 18 inches of a deflector, and no new tray, cabinet or panel under a head
  5. 5. Riser and valve rooms: clear, warm enough to keep water from freezing, and not used for storage
  6. 6. Spare sprinkler cabinet: present, stocked, wrench inside, list posted
  7. 7. Fire alarm panel: no supervisory signal standing for a valve, air pressure or pump
  8. 8. The record: date, time, a photo of each valve and gauge, the position of every control valve, and anything that changed

Anything out of place goes to the person who owns that system. Done every week, this turns NFPA 25 from an annual event into a record of how the system actually stood.


How FacilityOps keeps the NFPA 25 record between inspections

A FacilityOps robot walks the route through riser rooms, valve rooms, pump rooms, data halls and corridors on a schedule, including the weeks a manual round would have been skipped. It runs fully autonomously, and technicians can take manual control at any time.

Because FacilityOps is hardware agnostic, the same record can also come from a stationary sensor hub, another robot or a technician's own camera at the marked point. The history of each valve and gauge carries on whatever device takes the reading.

What the robot does at every checkpoint

  1. 1. Navigates to the checkpoint using lidar and simultaneous localization and mapping (SLAM), and confirms the valve, gauge or riser in front of it is the asset the route names before recording.
  2. 2. Captures from the same position and angle as every previous pass and stores that pose with the capture, so a change in the image is a change in the system, not in the camera.
  3. 3. Uses its fisheye camera for the whole scene and its telescopic camera for close ups of valve indicators, gauge faces, tags and sprinkler heads.
  4. 4. Reads gauges and labels into values with gauge reading and optical character recognition, each with a confidence score, so readings can be compared pass to pass.
  5. 5. Updates the 3D digital twin of the space, so heights and clearances are measured rather than estimated.
  6. 6. Writes not read against a valve it cannot see, such as one in a locked riser room or behind stacked boxes, so a missing reading never passes as an open valve.

Seven NFPA 25 conditions the robot measures, not just photographs

  • Control valve position (Chapter 13): the robot reads the OS&Y stem, the butterfly indicator or the post indicator window against the valve's expected open state on every pass. A valve found shut is escalated at once as a possible impairment, not filed with the rest of the round.
  • Valve security and signage (Chapter 13): the camera records whether the seal, lock or tamper switch is present and whether the identification sign is in place and legible, and the twin flags anything newly parked in front of the valve.
  • Gauge series: system, supply and air pressure are read on every pass and kept as a dated series for each gauge, so a slow drop or a compressor working harder shows as a trend long before it shows as an alarm.
  • Sprinkler condition (Chapter 5): the telescopic camera captures heads along the route for paint, corrosion, damage, loading, missing trim and orientation, compared with the same head's last capture.
  • Clearance below deflectors (Chapter 5 and IFC 315.3.1): deflector heights are mapped once in the twin, and each pass measures anything stored beneath them, so a stack inside 18 inches is flagged with its height and location.
  • Riser and valve room conditions: leaks, drips and corrosion on the riser and trim are captured visually, and the FacilityOps sensor hub records room temperature, so a valve room drifting toward freezing is on record before ice forms.
  • Inspection tags and the spare cabinet: optical character recognition reads the tags on risers and the spare sprinkler list, so a missing or out of date tag shows up between contractor visits.

What happens when something changes

  • The FacilityOps platform compares every capture with the same checkpoint's last pass, so a condition that appeared since the last round stands out.
  • A shut valve, a missing seal or a falling gauge goes to the person responsible for the sprinkler system, usually the facilities manager acting for the owner, with the previous pass alongside. It becomes a work order in FacilityOps or in the system the site already uses.
  • A closed valve or a falling pressure goes straight to the impairment coordinator, and the next pass confirms the valve is open and the pressure has recovered, so the record shows the restoration as well as the finding.
  • A riser or valve room that keeps getting flagged can get a stationary FacilityOps sensor hub that watches it between passes, and an alert from the hub sends the robot back to look.

An illustrative record entry

Riser room B, data hall 2 preaction system · Run 64, checkpoints 9 and 10 · Captured from the same pose as run 63

Change found: sectional control valve V 2.3 indicator reads SHUT; tamper switch present; no impairment tag on the valve. Supervisory air pressure steady at its baseline. Valve read OPEN on run 63.

Routed to: impairment coordinator and fire protection contractor, work order opened. Closed: run 65 reads V 2.3 OPEN with the seal in place, and the contractor confirmed the valve was left shut after a trim repair.

The method is proven in a live data center. At the CRSC Data Center, powered by Solutions IS, in Houston, a FacilityOps robot completed 19 autonomous inspection runs and collected more than 1,600 observations from fixed checkpoints in its first three weeks, documenting access control gaps, cable congestion, obstructions and safety hazards along the way.

A valve walk record for one riser room

NFPA 25 sets each control valve's inspection interval by how it is secured: sealed valves weekly, locked or supervised valves monthly, electrically supervised valves quarterly, in the 2017 and 2020 editions. An illustrative weekly pass through riser room C:

  • V 3, main riser, electrically supervised: open, tamper switch in place, sign names the system it controls. Pass.
  • V 3.1, sectional valve, sealed: open, seal intact, nothing parked in front of it. Pass.
  • V 3.2, sectional valve, sealed: open, but the seal is gone since the last pass. Exception: without the seal nobody can say whether the valve was operated.
  • V 3.3, preaction sectional, locked: open and locked, identification sign missing. Exception: each valve needs a sign naming the system or area it controls.
  • Preaction air gauge: same reading as the last four passes. Pass.
  • Main riser water gauge: within its normal weekly swing. Pass.

Two exceptions, both closed on the next pass with photos. If V 3.2 had been shut and reopened, the dated record would show when, and that is the trigger for a main drain test.

Coming next: confirming from the photo that each tamper switch is still seated on its valve, so a switch loosened to quiet a supervisory signal shows up before the next quarterly check.

What the evidence says

  • Where sprinklers did not activate, the system had most often been turned off, in 61 percent of those cases, according to NFPA's US Experience with Sprinklers report as summarized by VdS.
  • Each control valve inspection confirms the valve sits in its normal position, is sealed, locked or supervised, is accessible, is free of leaks and carries a sign naming what it controls, QRFS explains from NFPA 25.
  • Wet system gauges are inspected monthly for condition, and gauges monitoring water pressure quarterly, under the 2017 edition.
  • A main drain test is required whenever a riser control valve is closed and reopened, and a 10 percent drop in full flow pressure means the cause must be found, per a 2020 edition training deck.

The same valve, the same gauge and the same sprinkler, from the same spot on every pass. That is the difference between assuming the system stayed ready and showing that it did.

What the robot will not do

The FacilityOps robot touches nothing. It opens and closes no valve, runs no main drain or flow test, trips no dry pipe or preaction valve, starts no fire pump and performs no internal pipe assessment, which stay with the licensed contractor on their own schedule.

It is not a fire alarm system, a supervisory service or a fire watch, and it performs no life safety function. It records conditions, people act on them, and the authority having jurisdiction decides compliance.


Five questions to ask about your NFPA 25 record

An inspector, an insurer and your own fire protection contractor will each ask a version of these. A dated valve and gauge record answers all three.

  1. 1. Can you show every control valve was open on every week of the last quarter, with the date?
  2. 2. Which valves were closed for work this year, and where is the proof each one was reopened?
  3. 3. What did your preaction air pressure gauges read each week, and did any of them trend down?
  4. 4. Was anything stored within 18 inches of a sprinkler deflector since the last inspection?
  5. 5. Who is your impairment coordinator, and how would they learn about a valve closed without a tag?

NFPA 25 questions we hear most

What is NFPA 25?

NFPA 25 is the National Fire Protection Association's Standard for the Inspection, Testing, and Maintenance of Water Based Fire Protection Systems. It sets how sprinklers, standpipes, fire pumps, tanks, valves and related systems are kept in working order after they are installed.

Who is responsible for NFPA 25 compliance?

The property owner or the owner's designated representative, under Chapter 4. Qualified contractors carry out testing and maintenance, but the owner is responsible for making sure the program happens and the records are kept.

What is the current edition of NFPA 25?

The 2026 edition is the newest. NFPA revises the standard every three years, and many jurisdictions still enforce the 2023 or 2020 edition, so the authority having jurisdiction decides which applies.

What is the difference between NFPA 13 and NFPA 25?

NFPA 13 covers the design and installation of sprinkler systems. NFPA 25 covers keeping them working afterward through inspection, testing and maintenance.

How often are sprinklers inspected under NFPA 25?

Sprinklers are inspected from the floor once a year for damage, paint, corrosion, loading, orientation and obstructions. Valves and gauges are inspected more often, on a schedule that depends on the type of system and how each valve is secured.

Why are control valves so important?

Because a closed valve stops water from reaching the sprinklers. In NFPA's research, the most common reason sprinklers failed to operate in a fire was that the system had been shut off before the fire.

What is an impairment under NFPA 25?

Any condition that keeps a fire protection system from working as designed, such as a closed valve or a system drained for work. Chapter 15 requires an impairment coordinator, tagging and notification, and measures such as a fire watch until service is restored.

What changed in the 2026 edition of NFPA 25?

Industry summaries list several changes. Notification is required for emergency impairments as well as planned ones, piping found to contain ice is treated as impaired, escutcheon and cover plate replacement is spelled out, and the spare sprinkler list must carry more detail.

What sprinkler systems do data centers use?

Most data halls use preaction systems, which keep the pipes dry and admit water only after the detection system confirms a fire. Many also have clean agent suppression, which follows NFPA 2001 rather than NFPA 25.

What is an internal pipe assessment?

A periodic look inside the sprinkler piping for corrosion, scale and debris that could block water, covered in Chapter 14 and generally done about every five years by a qualified contractor. Obstruction investigations are also required when specific warning signs appear.

Can a robot do NFPA 25 inspections?

A robot can document the visual inspection items: valve position, seals and signs, gauge readings, sprinkler condition, clearances and room conditions, from the same points on every pass. Testing, maintenance and every compliance decision stay with qualified people and the authority having jurisdiction.

How does FacilityOps help with NFPA 25?

A FacilityOps robot walks a fixed route on a schedule, reads every control valve, gauge and riser, measures clearance under sprinklers in its digital twin, flags changes since the last pass and escalates a closed valve at once. The record shows how the system stood between contractor visits.

Why do sprinkler systems fail to work in a fire?

The most common reason is that the system was turned off. NFPA data for 2017 to 2021 put it at 61 percent of cases where sprinklers did not activate, followed by manual intervention at 15 percent and damaged components and poor maintenance at 9 percent each. A FacilityOps robot round photographs each control valve's position and seal with dates, so a closed valve shows up between contractor visits.

How often should sprinkler gauges be checked?

Under NFPA 25 (2017), wet system gauges are checked monthly for damage and gauges reading water pressure are checked quarterly. Air or nitrogen gauges on dry and preaction systems are checked monthly, or quarterly when air pressure supervision reports to a constantly attended location. A FacilityOps robot round photographs gauge faces on its route, building a dated pressure history the inspector can review.

What test is required after a sprinkler control valve is reopened?

A main drain test is required whenever a control valve at the riser is closed and reopened, to confirm the valve is truly open and water supply is normal. If full flow pressure drops by 10 percent or more from earlier results, the cause must be found and corrected. A FacilityOps robot round records valve position and gauge readings with dates, so the record shows when a valve changed state.


If you want to see how a closed valve or a falling gauge is captured and closed out, we can send you a sample inspection record.

When was each of your control valves last seen open? Book a call and we will scope a valve walk trial on your risers, with success criteria agreed in writing first.


Everything in this piece, as a checklist you can take on your rounds