Hunting Control Valves, Unstable Supply Temperatures and Simultaneous Heating and Cooling
A hunting control valve is one that swings back and forth around its setpoint instead of settling, wearing itself out while the temperature it controls wanders.
A control valve that swings from open to closed and back every few minutes is not broken. It is doing exactly what its controller tells it, over and over, while the temperature it is supposed to hold drifts on either side of setpoint.
Hunting is one of the few mechanical room faults you can see happen in real time, if you stand and watch. So is its expensive cousin, simultaneous heating and cooling, where a building pays twice to stand still.
Key takeaways
- Hunting is a control loop oscillating around setpoint. The usual causes are aggressive tuning, oversized valves, sensors far from the valve, actuator backlash and loops fighting each other.
- A stuck valve is the opposite: the command changes but the valve does not move, and the temperature drifts away with no response.
- Cycling chilled water supply temperature spreads through every coil downstream. In data centers, it turns into cycling rack inlet temperature.
- Simultaneous heating and cooling hides in plain sight. A warm heating coil beside a cold cooling coil in the same air handler is the giveaway.
What is a hunting control valve?
A hunting control valve is a valve whose controller keeps overshooting. It opens too far, the temperature overshoots, it closes too far, the temperature undershoots, and the cycle repeats.
The same thing happens with dampers and variable frequency drives (VFDs). Any device driven by a feedback loop can hunt. The loop oscillates around its setpoint instead of settling.
The controlled variable cycles with it. Supply air temperature, chilled water temperature or differential pressure rise and fall in a regular wave, often with a period of a few minutes.
Hunting is easy to miss on a quick round. A valve caught mid stroke looks like any other valve. Standing at it for three to five minutes, or reading the trend on the panel, is what reveals the rhythm.
Normal modulation looks different. A valve following load moves slowly in one direction as the day warms or cools. A hunting valve moves back and forth on a steady rhythm, whatever the load is doing.
What causes hunting?
Hunting has five common causes. Most real cases involve more than one.
Aggressive tuning
Most building loops use PID control, short for proportional, integral and derivative. Gains set too high make the controller react too hard to small errors. The loop overshoots on every correction.
Oversized valves
A valve much larger than needed makes a big flow change for a small stroke change. The controller cannot make fine adjustments, so it swings. This is covered in the next section.
Sensors far from the valve
A sensor far downstream reacts late. By the time it sees the effect of a valve move, the controller has already moved again. Covered below.
Actuator backlash and slipped linkages
Loose linkages, worn gears or a slipped coupling mean the actuator moves before the valve does. The controller keeps pushing, the valve jumps, and the loop overshoots.
Loops fighting each other
Two loops acting on the same system can push against each other. A pump speed loop and a bypass valve loop both trying to hold the same pressure is a classic example.
Why do oversized valves hunt?
Oversized valves hunt because they spend most of their life nearly closed, where small movements cause large flow swings.
A valve sized for a peak that never comes may only need to open 10% to 20% on a normal day. In that narrow band, a 1% stroke change can change flow far more than the controller expects.
The loop becomes unstable at low load. It may behave well on the hottest afternoon, when the valve is open wide, and hunt every night and every mild morning.
Oversized valves also pass excess water when barely open, which narrows delta T. Low delta T is covered in Part 1. An oversized valve that also cannot close tight against pump pressure becomes a passing valve, covered in Leaks Part 9.
Valve size is fixed until the valve is replaced. Tuning can calm an oversized valve, but often at the cost of a slow response. The lasting fix is a correctly sized valve.
What is valve authority, and why does it matter?
Valve authority is the share of a branch's total pressure drop taken by the control valve itself. It matters because it decides how much control the valve really has over flow.
In a branch with a coil, piping, fittings and a valve, the pressure drop is shared among them. If the valve takes a large share, its stroke has a strong, steady effect on flow across its range.
If the valve takes only a small share, the rest of the branch dominates. The valve has little influence over most of its stroke, then a sudden large influence near closed. It behaves more like an on and off device than a modulating one.
Low authority makes hunting likely. It often comes from an oversized valve, but it also appears when pump pressure is far above what the branch needs.
Authority is set by design and by the pump. Lowering the differential pressure setpoint, or resetting it with load, can raise effective authority without touching the valve.
How does sensor placement cause instability?
Sensor placement causes instability when the sensor is too far from what the valve changes, or in the wrong spot to read it well.
Too far downstream
Water and air take time to travel. A supply air sensor at the end of a long duct, or a chilled water sensor far down a header, sees each valve change late. The controller keeps adjusting during the delay and overshoots.
Poorly mixed flow
A sensor right after a mixing point, or in a stratified duct, reads a swirl of warm and cold. Its reading jumps around even when the average is steady. The controller chases the noise.
Mounting problems
A sensor in a dry well without heat transfer paste, or strapped to a pipe without insulation, reacts slowly and reads wrong. Sensor faults belong to the Electrical, Controls and Safety sub-series, but their effect shows up here as unstable control.
Where possible, compare the controller's sensor with a nearby gauge or handheld reading. A loop that hunts while a local gauge shows a steady value points at the sensor or its location.
How do you calm a hunting loop without making it sluggish?
You calm a hunting loop by finding which cause is driving it before touching the tuning. Retuning a loop that hunts because of a slipped linkage only hides the problem.
Check the hardware first
Stroke the valve by hand or from the controller and watch the stem. Look for lost motion, a slipping coupling or a stem that sticks and then jumps. Fix those before anything else.
Check the sensor
Confirm the sensor reads close to a reference and sits where the flow is mixed. A noisy or late sensor makes any tuning look wrong.
Then tune
With sound hardware and a good sensor, a controls technician can reduce the proportional gain or lengthen the integral time until the loop settles. The goal is a loop that settles after a disturbance with little overshoot, without being so slow that it lags the load.
Loops behave differently at high and low load, so test both. A loop tuned on a hot afternoon may still hunt at night when its valve is barely open.
Then record
Note the settings, the date and why they changed. The next person to see that loop hunt will know what was tried.
What is a stuck control valve, and how does it differ from hunting?
A stuck control valve is the opposite of hunting. The actuator commands change, but the valve does not move.
The usual causes are a failed actuator, a seized valve stem or a broken linkage. The controlled temperature drifts away from setpoint with no response. The controller winds its output to 100% or 0% and stays there.
How to tell them apart
Compare the commanded position on the controller with the actuator's position indicator and the valve stem. A hunting valve moves with the command. A stuck valve does not move at all, or the actuator moves while the stem stays put.
A stuck valve can be stuck open or closed. Stuck open on a chilled water coil wastes water and narrows delta T. Stuck closed starves a zone, covered in Part 3.
Routine visual inspection of actuator indicators against the controller's command catches stuck valves before occupants or rack temperatures do.
What does unstable supply water temperature do downstream?
When chilled water supply temperature cycles, every downstream coil valve reacts. The oscillation spreads through the building.
Each coil valve sees its supply air temperature move and adjusts. Hundreds of valves moving together change the load the plant sees, which can make the plant's own loop swing harder.
Causes at the plant include aggressive chiller staging and a badly tuned supply temperature loop. A decoupler or bypass that mixes water unevenly, or chillers whose controls fight, can do the same. Chiller surge and capacity control are covered in Rotating Equipment Part 7.
In data centers
In data centers, cycling supply temperature turns into cycling air temperature at the computer room air handlers and cycling rack inlet temperature. Equipment sees repeated swings that a steady supply would avoid.
Liquid cooled racks are more directly exposed. A coolant distribution unit (CDU) whose facility water supply cycles will pass some of that swing to the cold plates. CDU health is covered in Part 8.
Rack intake temperature readings taken at the same points on each round will show the swing if it is large. Panel trends show it even when it is small.
What is simultaneous heating and cooling, and how does it happen?
Simultaneous heating and cooling is heat added and removed from the same air or water at the same time. The building pays for both and gets neither.
Passing heating valves
A heating valve that reads closed but leaks through warms the air while the cooling coil downstream cools it. This is one of the most common causes, covered in Leaks Part 9.
Reheat left on
Reheat coils are meant to warm overcooled air for zones that need less cooling. Left running in summer, or with supply air colder than needed, they burn heat to undo cooling.
No deadband
If heating and cooling setpoints overlap, or sit too close, a zone flips between heating and cooling all day. A deadband is the gap between them where neither runs.
Zones fighting
Adjacent zones with different setpoints, or served by different units, can fight. One unit heats while its neighbor cools the same open space.
Economizer against mechanical cooling
An economizer brings in cool outside air for free cooling. If its sequence fights the mechanical cooling, or its damper sticks, energy is wasted. The plant either cools air the economizer should have cooled for free, or heats air it overcooled.
How do you find simultaneous heating and cooling?
You find it by temperature. Heating and cooling running together leave a clear temperature signature.
In an air handler, look for a heating coil that is warm to the touch, or warm on a thermal image. If the cooling coil next to it is cold, that is the giveaway. In summer, any warm heating coil is suspicious.
Supply air that is cooled lower than needed and then reheated is another sign. Compare the temperature leaving the cooling coil with the temperature leaving the reheat coil. A large rise in summer means energy is being wasted.
At the plant, both the boilers and the chillers running on a mild day can be normal for some buildings, but it is worth asking why. Boilers are covered in Part 9.
The energy cost shows up in the building's score too. The ENERGY STAR Portfolio Manager guide explains how equipment condition drives it.
What do hunting and fighting cost?
Hunting and fighting cost energy, comfort and equipment life.
Wear
Hunting multiplies actuator strokes. An actuator that should move a few times an hour may move hundreds of times. It wears actuator gears, valve stems and valve packing far faster than steady control. Packing leaks are covered in Leaks Part 2.
VFDs that hunt ramp motors up and down constantly, adding heat and wear. Motor heating is covered in Rotating Equipment Part 6.
In an office building
Occupants complain about hot and cold swings. Energy is wasted by simultaneous heating and cooling. Actuators and valves fail early, often in clusters.
In a data center
Supply temperatures cycle at CRAHs (computer room air handlers) and CDUs. Cooling is wasted, and conditions at the IT equipment are less stable than they need to be.
What looks like hunting but is not?
Three normal behaviors look like hunting at a glance.
Normal modulation
Valves move as load changes through the day. The movement is slow and follows load. Hunting is fast and rhythmic.
Staging events
When a chiller, pump or fan stages on or off, valves and temperatures move for a few minutes and then settle. That is designed behavior.
Sensor drift
A drifted sensor shows up as an offset, a steady error from the true value, rather than a swing. The loop holds steady at the wrong temperature.
What can a walk past prove, and what needs a follow up test?
A walk past can see hunting, stuck valves and fighting coils directly, but only if someone stops long enough to watch.
Directly observable
An actuator visibly stroking back and forth. Panel trends that saw tooth. A heating coil warm while the cooling coil next to it is cold.
Strong indicators
Supply temperature cycling with a regular period. Valve position and temperature moving out of step. Commanded position not matching the actuator indicator.
Suspected, needs follow up
The root cause in tuning, sizing or sequence. That needs trend data review and controls testing by a controls contractor.
The record matters as much as the observation. A walkthrough record that notes which valves were moving and how often makes repeat offenders obvious. Recurring comfort or cooling calls on the same zone often lead straight to them. HVAC (heating, ventilation and air conditioning) call patterns are covered in inspection evidence for recurring HVAC failures.
Walk up checklist for hunting valves and fighting coils
- Valve actuators and position indicators: watch for a few minutes, not a single glance.
- Supply temperature on panels at the start and end of each stop.
- Commanded position on the controller compared with the actuator indicator.
- Air handlers: heating coil temperature compared with cooling coil temperature.
- Repeated actuator motor or VFD ramp sounds.
How FacilityOps detects it
Coming Soon
Questions to ask about your own equipment
- 1. Which valves on your site move the most each day?
- 2. When were your main control loops last tuned?
- 3. Do your heating and cooling setpoints have a deadband?
- 4. Are any reheat coils running in summer?
- 5. How far is each loop's sensor from the valve it controls?
Frequently asked questions about hunting valves and simultaneous heating and cooling
What is control valve hunting?
Hunting is a control loop oscillating around its setpoint instead of settling. The valve swings back and forth on a regular rhythm, and the controlled temperature or pressure cycles with it.
What causes a control valve to hunt?
Aggressive PID tuning, oversized valves, sensors far from the valve, actuator backlash or slipped linkages, and two loops fighting each other on the same system.
Can an oversized valve cause hunting?
Yes. An oversized valve spends most of its time nearly closed, where small movements cause large flow swings. The loop becomes unstable, especially at low load.
What is valve authority?
Valve authority is the share of a branch's pressure drop taken by the control valve. Low authority gives the valve little control over most of its stroke, so it acts more like an on and off device.
How do you tell a stuck valve from a hunting valve?
Compare the controller's command with the actuator indicator and valve stem. A hunting valve moves with the command. A stuck valve does not move, and the temperature drifts away from setpoint.
Why does chilled water supply temperature fluctuate?
Common causes are aggressive chiller staging, a badly tuned supply temperature loop, uneven mixing at a decoupler or bypass, and chillers whose controls fight each other.
What is simultaneous heating and cooling?
Heat added and removed from the same air or water at the same time. Common causes are passing heating valves, reheat left on, overlapping setpoints, fighting zones and economizer conflicts.
How do you find simultaneous heating and cooling?
Look for a heating coil that is warm while the cooling coil beside it is cold, or supply air cooled and then reheated in summer. A thermal camera shows both quickly.
Does hunting damage actuators?
Yes. Hunting multiplies actuator strokes, wearing gears, valve stems and packing much faster than steady control. Actuators on hunting loops often fail early.
Sources